RAD-900-...
PHOENIX CONTACT
3827_en_B
4-wire connection technology
The RAD-PT100-4-IFS does not support the 4-wire connection technology.
•
If you want to use a 4-wire sensor, only connect three of the four wires.
•
The fourth wire should be left unwired. Otherwise there will be a different resistance in
the +I and -I cables owing to the parallel connection of two cable resistances.
Figure 3-7
4-wire connection technology
3.2.2
Measuring errors using 2-wire connection technology
Figure 3-8
Systematic temperature measuring error
Δ
T depending on the cable
length l
Curves depending on cable cross section A
1
Temperature measuring error for A = 0.25 mm
2
2
Temperature measuring error for A = 0.5 mm
2
3
Temperature measuring error for A = 1.0 mm
2
4
Temperature measuring error for A = 1.5 mm
2
(Measuring error valid for: copper cable
χ
= 57 m/
Ω
mm
2
, T
A
= 25°C and Pt 100 sensor)
µC
2.1
2.2
2.3
3.1
3.2
3.3
5.1
5.2
5.3
4.1
4.2
4.3
IO-MAP
0 1
DC
DC
IFS
IFS
A
D
1mA
A
D
1mA
A
D
1mA
A
D
1mA
-I2
-U2
+I2
+I1
-U1
-I1
+I3
-U3
-I3
+I4
-U4
-I4
RL
I+
(U+)
RTD
ϑ
RL
I–
U–
0
2,5
5
7,5
10
12,5
15
17,5
20
0
2
4
6
8
T [K]
I [m]