Wireless LAN access points/Ethernet clients
7190_en_02
PHOENIX CONTACT
2-7
2.2.5
Status and diagnostic indicators
2.2.6
Mounting/removal
2.2.6.1
Attaching the mounting plate
Select a mounting location where the devices are not shielded by highly attenuating
materials (steel supporting structure, concrete, etc.).
Use DIN 84-M4 x 16-8.8 countersunk screws. These screws do not require additional
measures to prevent them from loosening.
Table 2-1
Status and diagnostic indicators
Des.
Color
Status
Meaning
PWR
Green
ON
Supply via 24 V DC (230 V AC) present
OFF
Supply via 24 V DC (230 V AC) not present
POE
Green
ON
Supply via Power over Ethernet present
OFF
Supply via Power over Ethernet not present
HOST
(right)
Orange ON
Link
active
OFF
Link inactive
HOST
(left)
Green
Flashing
Evenly: Device in the boot process
Erratically: Data is being transmitted
OFF
Device is not in the boot process or transmitting data
HOST
(left and right)
Orange
Flashing
Device reset to default state upon delivery or firmware is being updated
NOTE:
Prevent overheating
Make sure that the device is not exposed to direct sunlight or other heat radiation.
NOTE:
Observe lightning protection measures
In outdoor installations, the device may only be operated within the range of lightning
protection systems, all outdoor cables must be led indoors via a lightning protection
equipotential bonding system.
The mounting surface must be flat to avoid strain on the module.
Do not mount the device behind or close to objects, which adversely affect its receive and
transmit properties.