CONTACTRON Speed Starter
PHOENIX CONTACT
109908_en_00
13.2
Safety information
–
The safety function must be requested once every 24 hours in order to comply with
Category 4 PL e safety integrity.
–
The safety function must be requested once every 3 months in order to comply with the
safety integrity of Category 3 PL e.
–
The safety function must be requested once every year in order to comply with the
safety integrity of Category 3 PL d.
–
An inadmissible restart may occur after removal of the STO function. This must be
blocked by a higher-level safety system.
–
A double failure may result in an unintentional jerk. The angle of rotation depends on
the number of poles of the selected drive and on the gear ratio of the selected gearbox.
–
The device may not be exposed to mechanical or thermal influences that exceed the
limits as described in the operating instructions. To protect against mechanical or
electrical damage, install the device in an appropriate housing with a suitable degree of
protection (minimum IP54) in accordance with IEC/EN 60529.
–
For the STO+ and STO- inputs, suitably insulated fixed wires or stranded wires with end
ferrules have to be used.
–
The requirements of IEC/EN 61800-5-2 must be observed in order to reliably exclude
short circuits and cross-connections of the safety-relevant cables.
–
Only qualified personnel may install and commission safety technology.
–
The inputs STO+ and STO- may only be operated from a single SELV/PELV 24 V
supply.
–
The maximum length and the maximum frequency of the light and dark test impulses
are defined in
Table A-4 “Digital input (STO+ / STO-)”
–
Electrical parameters see
Table A-4 “Digital input (STO+ / STO-)”
13.3
STO input
In order to operate the motor that is connected to the CONTACTRON Speed Starter, you
must issue the release to the device via the STO input.
As soon as a valid signal is applied to the STO input (terminals STO+ and STO-), the device
receives control commands and the motor can be operated.
With non-safety-related applications, you can also issue the release by bridging terminals
(STO-) and (GND) and terminals (STO+) and (24V OUT).
Summary of Contents for 1201132
Page 1: ...User manual CONTACTRON Speed Starter...
Page 14: ...CONTACTRON Speed Starter 14 146 PHOENIX CONTACT 109908_en_00...
Page 18: ...CONTACTRON Speed Starter 18 146 PHOENIX CONTACT 109908_en_00...
Page 24: ...CONTACTRON Speed Starter 24 146 PHOENIX CONTACT 109908_en_00...
Page 46: ...CONTACTRON Speed Starter 46 146 PHOENIX CONTACT 109908_en_00...
Page 48: ...CONTACTRON Speed Starter 48 146 PHOENIX CONTACT 109908_en_00...
Page 86: ...CONTACTRON Speed Starter 86 146 PHOENIX CONTACT 109908_en_00...
Page 90: ...CONTACTRON Speed Starter 90 146 PHOENIX CONTACT 109908_en_00...
Page 106: ...CONTACTRON Speed Starter 106 146 PHOENIX CONTACT 109908_en_00...
Page 108: ...CONTACTRON Speed Starter 108 146 PHOENIX CONTACT 109908_en_00 14 1 2 3 phase...
Page 113: ...Application notes 109908_en_00 PHOENIX CONTACT 113 146 14 3 2 3 phase...
Page 114: ...CONTACTRON Speed Starter 114 146 PHOENIX CONTACT 109908_en_00...
Page 132: ...CONTACTRON Speed Starter 132 146 PHOENIX CONTACT 109908_en_00...
Page 136: ...CONTACTRON Speed Starter 136 146 PHOENIX CONTACT 109908_en_00...
Page 140: ...CONTACTRON Speed Starter 140 146 PHOENIX CONTACT 109908_en_00...
Page 147: ......