FL MGUARD 1000 product family
48 / 52
PHOENIX CONTACT
108413_en_06
Maximum current consumption (US = min, T
amb
= max, DO
I
= max)
FL MGUARD 1102
1.00 A
Typical current consumption (US = 24 V, T
amb
= 20 °C, DO
I
= 0 A)
FL MGUARD 1102
0.12 A
Test voltage
500 V DC for one minute
Supply voltage (US1)
Network interfaces
Properties of RJ45 connections
Number
FL MGUARD 1102
2
Connection format
8-pos. RJ45 jack
Connection medium
Twisted-pair cable with a conductor cross section of 0.14 mm
2
to 0.22 mm
2
Cable impedance
100 ohm
Transmission speed
10/100/1000 Mbps/s
Maximum conductor length (twisted pair)
100 m (per segment)
Digital inputs and outputs
Digital outputs
Number
3
Voltage of output signal
18 V DC ... 36 V DC
Current carrying capacity
250 mA
Digital inputs
Number
3
Voltage of input signal
0 V DC ... 36 V DC
Maximum input current
5 mA
Mechanical tests
Vibration resistance in accordance with IEC 60068-2-6
Operation/storage/transport: 5g, 10 Hz ... 150 Hz
Free fall in accordance with IEC 60068-2-32
1 m
Conformance with EMC directives
Developed in accordance with IEC 61000-6-2
Noise emission in accordance with EN 55016-2-1:2014 (conducted noise
emission)
Class B
Noise emission in accordance with EN 55016-2-3:2010
+ A1:2010 + AC:2013 + A2:2014 (radiated noise emission)
Class A
Immunity in accordance with EN 61000-4-2 (IEC 1000-4-2) (ESD)
Contact discharge:
Air discharge:
Indirect discharge:
Requirements in accordance with DIN EN 61000-6-2
Test intensity 3, criterion B
Test intensity 3, criterion B
Test intensity 3, criterion B
Immunity in accordance with EN 61000-4-3 (IEC 1000-4-3)
(electromagnetic fields)
Requirements in accordance with DIN EN 61000-6-2
Test intensity 3, criterion A
Summary of Contents for 1153079
Page 1: ...User manual UM EN FL MGUARD 1000 FL MGUARD 1000 Installation and startup...
Page 10: ...FL MGUARD 1000 product family 10 52 PHOENIX CONTACT 108413_en_06...
Page 28: ...FL MGUARD 1000 product family 28 52 PHOENIX CONTACT 108413_en_06...
Page 50: ...FL MGUARD 1000 product family 50 52 PHOENIX CONTACT 108413_en_06...
Page 53: ......