FL MGUARD 1000 product family
24 / 52
PHOENIX CONTACT
108413_en_06
3.2
Connecting the supply voltage
Connecting the supply voltage
•
Remove COMBICON connector
XD1
from the device.
•
Connect the supply voltage to the COMBICON connector. Observe the polarity:
– 1 = US1 = 24 V
– 2 = GND = 0 V
•
Plug COMBICON connector
XD1
onto the device.
⇒
As soon as one or both US LEDs are lit, the device is connected.
3.2.1
Grounding the device
The devices must be grounded in order to shield the data telegram from any possible inter
-
ference and to discharge such interferences to ground potential.
Grounding the device
•
Mount the module on a grounded DIN rail.
•
Functional grounding of the module is achieved when the module is snapped onto the
grounded DIN rail or via
clamping point 5
(functional ground – FE)
of COMBICON
connector
XD1
.
NOTE: Electrical voltage
The device is designed exclusively for operation with safety extra-low voltage
(SELV/PELV) in accordance with IEC 60950/EN 60950/VDE 0805. The device may only
be connected to devices that meet the requirements of EN 60950. Provide overcurrent
protection (I ≤ 5 A) in the installation.
The device is operated using a 24 V DC voltage.
Table 3
-
1
Power supply via COMBICON connector
COMBICON
1
2
3
4
5
XD1
US1
GND
Not available
Functional
ground
24 V
0 V
N/A
N/A
FE
NOTE: Risk of injury due to voltage
To prevent accidents due to electrical voltage, the device must be grounded correctly,
taking the local conditions into account.
Summary of Contents for 1153079
Page 1: ...User manual UM EN FL MGUARD 1000 FL MGUARD 1000 Installation and startup...
Page 10: ...FL MGUARD 1000 product family 10 52 PHOENIX CONTACT 108413_en_06...
Page 28: ...FL MGUARD 1000 product family 28 52 PHOENIX CONTACT 108413_en_06...
Page 50: ...FL MGUARD 1000 product family 50 52 PHOENIX CONTACT 108413_en_06...
Page 53: ......