94
14.1.6 Low Frequency Protection Control 1
When the compressor continuously operates at frequency lower than 25 Hz for 240 minutes, the operation
frequency will change to 24 Hz for 2 minutes.
14.1.7 Low Frequency Protection Control 2
When all the below conditions comply, the minimum compressor frequency will change to lower frequency.
Temperature, T, for:
Heating
Cooling
Outlet water (°C)
T < 14 or T 48
T < 14 or T 30
Outdoor air (°C)
T < 4 or T 24
T < 13 or T 38
Indoor heat exchanger (°C)
T 0
T < 30
14.1.8 High Pressure Sensor Control
Purpose:
- To protect the system operation.
Detection
period:
- After compressor on for 5 minutes.
Detection
conditions:
- When abnormal high voltage detection, 5 V or when open circuit detection 0V for 5 seconds continuously.
After
detection:
- When abnormality is detected continue 5 seconds, unit stop operation.
- OFF/ON control panel LED will blink (H64 error occurs).
14.1.9 Outside Temperature Current Control
14.1.10 Crank Case Heater Control
Purpose:
- For compressor protection during low outdoor ambient operation (during heating low temperature operation).
Control
content:
a. Trigger heater START condition
o
When the outdoor air temperature is 4°C or below, and discharge temperature is 12°C or below.
b. Resetting heater STOP condition
1.
When the outdoor air temperature exceeds entry condition (6°C)
2.
When the discharge temperature exceeds entry condition (19°C)
Summary of Contents for WH-SDC07C3E5
Page 22: ...22 4 Location of Controls and Components 4 1 Indoor Unit 4 1 1 Location of Control ...
Page 23: ...23 ...
Page 24: ...24 ...
Page 25: ...25 4 1 2 Weekly Timer Setting ...
Page 26: ...26 4 1 3 Setting Up the Special Functions ...
Page 27: ...27 4 1 4 Main Components 4 2 Outdoor Unit ...
Page 28: ...28 5 Dimensions 5 1 Indoor Unit ...
Page 29: ...29 5 2 Outdoor Unit 5 2 1 WH UD07CE5 A WH UD09CE5 A WH UD07CE5 A 1 WH UD09CE5 A 1 ...
Page 30: ...30 5 2 2 WH UD12CE5 A WH UD14CE5 A WH UD16CE5 A WH UD12CE5 A 1 WH UD14CE5 A 1 WH UD16CE5 A 1 ...
Page 32: ...32 ...
Page 33: ...33 7 Block Diagram 7 1 WH UD07CE5 A WH UD09CE5 A WH UD07CE5 A 1 WH UD09CE5 A 1 ...
Page 34: ...34 7 2 WH UD12CE5 A WH UD14CE5 A WH UD16CE5 A WH UD12CE5 A 1 WH UD14CE5 A 1 WH UD16CE5 A 1 ...
Page 36: ...36 8 1 2 WH SDC12C6E5 WH SDC14C6E5 WH SDC16C6E5 WH SDC12C6E5 1 WH SDC14C6E5 1 WH SDC16C6E5 1 ...
Page 37: ...37 8 2 Outdoor Unit 8 2 1 WH UD07CE5 A WH UD09CE5 A WH UD07CE5 A 1 WH UD09CE5 A 1 ...
Page 38: ...38 8 2 2 WH UD12CE5 A WH UD14CE5 A WH UD16CE5 A WH UD12CE5 A 1 WH UD14CE5 A 1 WH UD16CE5 A 1 ...
Page 40: ...40 9 1 2 WH SDC12C6E5 WH SDC14C6E5 WH SDC16C6E5 WH SDC12C6E5 1 WH SDC14C6E5 1 WH SDC16C6E5 1 ...
Page 41: ...41 9 2 Outdoor Unit 9 2 1 WH UD07CE5 A WH UD09CE5 A WH UD07CE5 A 1 WH UD09CE5 A 1 ...
Page 42: ...42 9 2 2 WH UD12CE5 A WH UD14CE5 A WH UD16CE5 A WH UD12CE5 A 1 WH UD14CE5 A 1 WH UD16CE5 A 1 ...
Page 43: ...43 10 Printed Circuit Board 10 1 Indoor Unit 10 1 1 Main Printed Circuit Board ...
Page 44: ...44 10 1 2 Solar Printed Circuit Board Optional ...
Page 46: ...46 10 2 1 2 Capacitor Printed Circuit Board 10 2 1 3 Noise Filter Printed Circuit Board ...
Page 48: ...48 10 2 2 2 Capacitor Printed Circuit Board 10 2 2 3 Noise Filter Printed Circuit Board ...
Page 54: ...54 11 3 4 2 Wire Stripping and Connecting Requirement ...
Page 73: ...73 ...
Page 79: ...79 ...
Page 80: ...80 ...
Page 90: ...90 ...
Page 140: ...140 18 3 To Remove Pressure Gauge 18 4 To Remove Control Panel ...
Page 141: ...141 18 5 To Remove RCCB 18 6 To Remove Transformer and Electronic Controller Board ...
Page 166: ...166 19 4 Hydraulic Pump Performance 07C3 09C3 12C6 14C6 16C6 ...
Page 169: ...169 20 2 WH UD07CE5 A WH UD09CE5 A WH UD07CE5 A 1 WH UD09CE5 A 1 ...
Page 170: ...170 ...
Page 174: ...174 20 3 WH UD12CE5 A WH UD14CE5 A WH UD16CE5 A WH UD12CE5 A 1 WH UD14CE5 A 1 WH UD16CE5 A 1 ...
Page 175: ...175 ...