13.13 Sterillization Mode
Purpose:
o
Boil tank temperature to customer set boiling temperature to operate sterilization.
Control start condition:
o
Tank connection set to YES by remote controlller
o
Serilization function selection is YES
o
Sterilization signal received from remote controller by timer.
Control
stop
condition:
o
After boiling timer completed. Boiling timer start counting once tank achieve boiling set temperature OR
o
After 4 hours of operation since sterilization function start OR
Control
content:
o
Once the sterilization function enable, set the target tank temperature to Boiling Set Temperature.
o
Booster heater will allow to ON during solar priority SET condition.
Booster heater OFF Temp. = Boiling Set Temperature 0°C
Booster heater ON Temp. = Boiling Set Temperature - 7°C
o
The sterilization set temperature may not achieve if tank booster heater function is deactivated.
o
Boiling timer which set by remote controller will start count after tank achieve boiling set temperature.
o
Sterilization
operation
will end after complete boiling timer or Max 4 hrs from function start.
o
Target tank temperature will set back to normal tank set temperature.
* Tank heater control is not affected by solar pump when solar priority set.
13.14 Quiet Operation
Purpose:
- To provide quiet operation compare to normal operation by reduces outdoor unit noise.
Starting
condition:
1 When quiet button is presses.
2 When quiet request ON time by weekly timer (Refer to control panel.)
When any of above mentioned condition is achieved, this control is activated.
New target FM speed = Present target FM speed - 80 rpm
Minimum target FM speed = 200 rpm
Cancellation
condition:
1 Cancel by press quiet button
2 Stop by OFF/ON button
3 When quiet request OFF time by weekly timer
When any of above mentioned condition is achieved, this control is cancelled.
13.15 Anti Freeze Control
Anti freeze protection control can be select YES or NO from control panel. Default setting is YES.
In heatpump system, there are 2 types of anti freeze control:
1 Water pump circulation anti frost control
Water pump turns ON when
ALL
the below conditions are fulfilled:
o
Heatpump OFF (standby) OR water pump stop (Tank Mode) OR error occurs
o
Water flow switch is not abnormal
o
Outdoor ambient temp. < 3°C
o
Water inlet/outlet temp. < 6°C
o
After 5 minutes from previous water pump OFF
Water pump turns OFF when
ANY
of the below conditions is fulfilled:
o
Outdoor ambient temp.
≥
4°C
o
During -5°C < outdoor ambient temp. < 4°C
After water pump ON for 4 minutes, and water inlet/outlet temp.
≥
8°C
Else, shift to backup heater anti freeze control
o
During outdoor ambient temp. < -5°C
After water pump ON for 4 minutes, and water inlet/outlet temp.
≥
20°C
Else, shift to backup heater anti freeze control
However, if flow switch is abnormal (H62), then water pump circulation anti freeze control will not activate.
Summary of Contents for WH-SDC07C3E5
Page 22: ...22 4 Location of Controls and Components 4 1 Indoor Unit 4 1 1 Location of Control ...
Page 23: ...23 ...
Page 24: ...24 ...
Page 25: ...25 4 1 2 Weekly Timer Setting ...
Page 26: ...26 4 1 3 Setting Up the Special Functions ...
Page 27: ...27 4 1 4 Main Components 4 2 Outdoor Unit ...
Page 28: ...28 5 Dimensions 5 1 Indoor Unit ...
Page 29: ...29 5 2 Outdoor Unit 5 2 1 WH UD07CE5 A WH UD09CE5 A WH UD07CE5 A 1 WH UD09CE5 A 1 ...
Page 30: ...30 5 2 2 WH UD12CE5 A WH UD14CE5 A WH UD16CE5 A WH UD12CE5 A 1 WH UD14CE5 A 1 WH UD16CE5 A 1 ...
Page 32: ...32 ...
Page 33: ...33 7 Block Diagram 7 1 WH UD07CE5 A WH UD09CE5 A WH UD07CE5 A 1 WH UD09CE5 A 1 ...
Page 34: ...34 7 2 WH UD12CE5 A WH UD14CE5 A WH UD16CE5 A WH UD12CE5 A 1 WH UD14CE5 A 1 WH UD16CE5 A 1 ...
Page 36: ...36 8 1 2 WH SDC12C6E5 WH SDC14C6E5 WH SDC16C6E5 WH SDC12C6E5 1 WH SDC14C6E5 1 WH SDC16C6E5 1 ...
Page 37: ...37 8 2 Outdoor Unit 8 2 1 WH UD07CE5 A WH UD09CE5 A WH UD07CE5 A 1 WH UD09CE5 A 1 ...
Page 38: ...38 8 2 2 WH UD12CE5 A WH UD14CE5 A WH UD16CE5 A WH UD12CE5 A 1 WH UD14CE5 A 1 WH UD16CE5 A 1 ...
Page 40: ...40 9 1 2 WH SDC12C6E5 WH SDC14C6E5 WH SDC16C6E5 WH SDC12C6E5 1 WH SDC14C6E5 1 WH SDC16C6E5 1 ...
Page 41: ...41 9 2 Outdoor Unit 9 2 1 WH UD07CE5 A WH UD09CE5 A WH UD07CE5 A 1 WH UD09CE5 A 1 ...
Page 42: ...42 9 2 2 WH UD12CE5 A WH UD14CE5 A WH UD16CE5 A WH UD12CE5 A 1 WH UD14CE5 A 1 WH UD16CE5 A 1 ...
Page 43: ...43 10 Printed Circuit Board 10 1 Indoor Unit 10 1 1 Main Printed Circuit Board ...
Page 44: ...44 10 1 2 Solar Printed Circuit Board Optional ...
Page 46: ...46 10 2 1 2 Capacitor Printed Circuit Board 10 2 1 3 Noise Filter Printed Circuit Board ...
Page 48: ...48 10 2 2 2 Capacitor Printed Circuit Board 10 2 2 3 Noise Filter Printed Circuit Board ...
Page 54: ...54 11 3 4 2 Wire Stripping and Connecting Requirement ...
Page 73: ...73 ...
Page 79: ...79 ...
Page 80: ...80 ...
Page 90: ...90 ...
Page 140: ...140 18 3 To Remove Pressure Gauge 18 4 To Remove Control Panel ...
Page 141: ...141 18 5 To Remove RCCB 18 6 To Remove Transformer and Electronic Controller Board ...
Page 166: ...166 19 4 Hydraulic Pump Performance 07C3 09C3 12C6 14C6 16C6 ...
Page 169: ...169 20 2 WH UD07CE5 A WH UD09CE5 A WH UD07CE5 A 1 WH UD09CE5 A 1 ...
Page 170: ...170 ...
Page 174: ...174 20 3 WH UD12CE5 A WH UD14CE5 A WH UD16CE5 A WH UD12CE5 A 1 WH UD14CE5 A 1 WH UD16CE5 A 1 ...
Page 175: ...175 ...