17.4 Error Codes Table
Diagnosis display
Abnormality/Protection control
Abnormality judgement
Primary location to verify
H00
No abnormality detected
—
—
H12
Indoor/Outdoor capacity unmatched
90s after power supply
Indoor/outdoor connection wire
Indoor/outdoor PCB
Specification and combination table in
catalogue
H15
Outdoor compressor temperature sensor
abnormality
Continue for 5 sec.
Compressor temperature sensor
(defective or disconnected)
H23
Indoor refrigerant liquid temperature
sensor abnormality
Continue for 5 sec.
Refrigerant liquid temperature sensor
(defective or disconnected)
H42
Compressor low pressure abnormality
—
Outdoor pipe temperature sensor
Clogged expansion valve or strainer
Insufficient refrigerant
Outdoor PCB
Compressor
H62
Water flow switch abnormality
Continue for 1 min.
Water flow switch
H64
Refrigerant high pressure abnormality
Continue for 5 sec.
Outdoor high pressure sensor
(defective or disconnected)
H70
Back-up heater OLP abnormality
Continue for 60 sec.
Back-up heater OLP
(Disconnection or activated)
H72
Tank sensor abnormal
Continue for 5 sec.
Tank sensor
H76
Indoor - control panel communication
abnormality
—
Indoor - control panel
(defective or disconnected)
H90
Indoor/outdoor abnormal communication
> 1 min after starting operation
Internal/external cable connections
Indoor/Outdoor PCB
H91
Tank heater OLP abnormality
Continue for 60 sec.
Tank heater OLP
(Disconnection or activated)
H95 Indoor/Outdoor
wrong
connection
—
Indoor/Outdoor supply voltage
H98
Outdoor high pressure overload
protection
—
Outdoor high pressure sensor
Water pump or water leakage
Clogged expansion valve or strainer
Excess refrigerant
Outdoor PCB
H99
Indoor heat exchanger freeze prevention
—
Indoor heat exchanger
Refrigerant shortage
F12
Pressure switch activate
4 times occurrence within 20
minutes
Pressure switch
F14
Outdoor compressor abnormal revolution
4 times occurrence within 20
minutes
Outdoor compressor
F15
Outdoor fan motor lock abnormality
2 times occurrence within 30
minutes
Outdoor PCB
Outdoor fan motor
F16
Total running current protection
3 times occurrence within 20
minutes
Excess refrigerant
Outdoor PCB
F20
Outdoor compressor overheating
protection
4 times occurrence within 30
minutes
Compressor tank temperature sensor
Clogged expansion valve or strainer
Insufficient refrigerant
Outdoor PCB
Compressor
F22
IPM (power transistor) overheating
protection
3 times occurrence within 30
minutes
Improper heat exchange
IPM (Power transistor)
F23
Outdoor Direct Current (DC) peak
detection
7 times occurrence
continuously
Outdoor PCB
Compressor
F24
Refrigeration cycle abnormality
2 times occurrence within 20
minutes
Insufficient refrigerant
Outdoor PCB
Compressor low compression
F25 Cooling/Heating
cycle
changeover
abnormality
4 times occurrence within 30
minutes
4-way valve
V-coil
F27
Pressure switch abnormality
Continue for 1 min.
Pressure switch
F36
Outdoor air temperature sensor
abnormality
Continue for 5 sec.
Outdoor air temperature sensor
(defective or disconnected)
F37
Indoor water inlet temperature sensor
abnormality
Continue for 5 sec.
Water inlet temperature sensor
(defective or disconnected)
F40
Outdoor discharge pipe temperature
sensor abnormality
Continue for 5 sec.
Outdoor discharge pipe temperature
sensor (defective or disconnected)
Summary of Contents for WH-SDC07C3E5
Page 22: ...22 4 Location of Controls and Components 4 1 Indoor Unit 4 1 1 Location of Control ...
Page 23: ...23 ...
Page 24: ...24 ...
Page 25: ...25 4 1 2 Weekly Timer Setting ...
Page 26: ...26 4 1 3 Setting Up the Special Functions ...
Page 27: ...27 4 1 4 Main Components 4 2 Outdoor Unit ...
Page 28: ...28 5 Dimensions 5 1 Indoor Unit ...
Page 29: ...29 5 2 Outdoor Unit 5 2 1 WH UD07CE5 A WH UD09CE5 A WH UD07CE5 A 1 WH UD09CE5 A 1 ...
Page 30: ...30 5 2 2 WH UD12CE5 A WH UD14CE5 A WH UD16CE5 A WH UD12CE5 A 1 WH UD14CE5 A 1 WH UD16CE5 A 1 ...
Page 32: ...32 ...
Page 33: ...33 7 Block Diagram 7 1 WH UD07CE5 A WH UD09CE5 A WH UD07CE5 A 1 WH UD09CE5 A 1 ...
Page 34: ...34 7 2 WH UD12CE5 A WH UD14CE5 A WH UD16CE5 A WH UD12CE5 A 1 WH UD14CE5 A 1 WH UD16CE5 A 1 ...
Page 36: ...36 8 1 2 WH SDC12C6E5 WH SDC14C6E5 WH SDC16C6E5 WH SDC12C6E5 1 WH SDC14C6E5 1 WH SDC16C6E5 1 ...
Page 37: ...37 8 2 Outdoor Unit 8 2 1 WH UD07CE5 A WH UD09CE5 A WH UD07CE5 A 1 WH UD09CE5 A 1 ...
Page 38: ...38 8 2 2 WH UD12CE5 A WH UD14CE5 A WH UD16CE5 A WH UD12CE5 A 1 WH UD14CE5 A 1 WH UD16CE5 A 1 ...
Page 40: ...40 9 1 2 WH SDC12C6E5 WH SDC14C6E5 WH SDC16C6E5 WH SDC12C6E5 1 WH SDC14C6E5 1 WH SDC16C6E5 1 ...
Page 41: ...41 9 2 Outdoor Unit 9 2 1 WH UD07CE5 A WH UD09CE5 A WH UD07CE5 A 1 WH UD09CE5 A 1 ...
Page 42: ...42 9 2 2 WH UD12CE5 A WH UD14CE5 A WH UD16CE5 A WH UD12CE5 A 1 WH UD14CE5 A 1 WH UD16CE5 A 1 ...
Page 43: ...43 10 Printed Circuit Board 10 1 Indoor Unit 10 1 1 Main Printed Circuit Board ...
Page 44: ...44 10 1 2 Solar Printed Circuit Board Optional ...
Page 46: ...46 10 2 1 2 Capacitor Printed Circuit Board 10 2 1 3 Noise Filter Printed Circuit Board ...
Page 48: ...48 10 2 2 2 Capacitor Printed Circuit Board 10 2 2 3 Noise Filter Printed Circuit Board ...
Page 54: ...54 11 3 4 2 Wire Stripping and Connecting Requirement ...
Page 73: ...73 ...
Page 79: ...79 ...
Page 80: ...80 ...
Page 90: ...90 ...
Page 140: ...140 18 3 To Remove Pressure Gauge 18 4 To Remove Control Panel ...
Page 141: ...141 18 5 To Remove RCCB 18 6 To Remove Transformer and Electronic Controller Board ...
Page 166: ...166 19 4 Hydraulic Pump Performance 07C3 09C3 12C6 14C6 16C6 ...
Page 169: ...169 20 2 WH UD07CE5 A WH UD09CE5 A WH UD07CE5 A 1 WH UD09CE5 A 1 ...
Page 170: ...170 ...
Page 174: ...174 20 3 WH UD12CE5 A WH UD14CE5 A WH UD16CE5 A WH UD12CE5 A 1 WH UD14CE5 A 1 WH UD16CE5 A 1 ...
Page 175: ...175 ...