Switch back 3 ways valve to room side, Heat pump and water pump turn OFF, IF
o
External Room Thermo ON back
OR
Under Solar Priority Set condition:
Tank temperature > Tank THERMO OFF TEMP. for continuous 3 minutes
OR
Solar Valve
ON
Under Solar Priority Not Set condition:
Tank temperature > Tank THERMO OFF TEMP for continuous 3 minutes
* THERMO ON and THERMO OFF point refer to case below.
Operation condition when 3 ways valve switch to tank side:
Tank water set temperature = tank set temperature or [50°C] whichever lower
Heat Pump Water Outlet set temperature is set to [53°C] during tank interval
Initial Tank THERMO ON TEMP = heat pump tank target tempe
[-1°C]
Case 1:
o
THERMO OFF TEMP:
1. THERMO OFF TEMP = Heat pump tank target tempe
[1°C]
.
2. Tank temperature > THERMO OFF TEMP for continuous 10 seconds after compressor off, switch 3
ways valve to room side.
o
Next THERMO ON TEMP:
1. THERMO ON TEMP = Heat pump tank target tempe
[-1°C]
or
2. If tank temperature < THERMO ON TEMP
AND
External Room Thermo OFF, switch to tank side.
Case 2:
o
Heat pump THERMO OFF TEMP:
1. Heat pump THERMO OFF TEMP = 53°C +
[+4°C]
.
2. Water outlet temperature > Heat pump THERMO OFF TEMP for continuous 3 minutes, heat pump
OFF.
o
Next THERMO ON TEMP:
1. THERMO ON TEMP = Water inlet when heat pump THERMO OFF +
[-3°C]
.
2. If water outlet temperature < THERMO ON TEMP
AND
External Room Thermo OFF, heat pump ON.
Case 3:
o
Heat pump THERMO OFF TEMP:
1. Water inlet temperature > 55°C for continuous 60 secs, heat pump OFF.
o
Next THERMO ON TEMP:
1. THERMO ON TEMP = Water inlet temperature < 55°C.
2. If water inlet temperature < THERMO ON TEMP AND External Room Thermo OFF, heat pump ON.
Case 4: (Only during solar priority is set condition)
o
When solar request ON, solar valve will ON and switch 3 ways valve to room side.
o
THERMO ON TEMP:
1. THERMO ON TEMP = Heat pump tank target tempe
[-1°C]
.
2. If tank temperature < THERMO ON TEMP AND External Room Thermo OFF
AND
Solar 3WV OFF,
switch to tank side.
3 Backup Heater control:-
o
During External Room Thermo ON time, follow normal backup heater control operation.
o
During External Room Thermo OFF time, Backup heater OFF.
4 Booster heater control:
o
Booster heater On/Off follow normal operation.
* Under solar priority is set condition, when solar 3 way valve is ON, booster heater turn OFF.
Summary of Contents for WH-SDC07C3E5
Page 22: ...22 4 Location of Controls and Components 4 1 Indoor Unit 4 1 1 Location of Control ...
Page 23: ...23 ...
Page 24: ...24 ...
Page 25: ...25 4 1 2 Weekly Timer Setting ...
Page 26: ...26 4 1 3 Setting Up the Special Functions ...
Page 27: ...27 4 1 4 Main Components 4 2 Outdoor Unit ...
Page 28: ...28 5 Dimensions 5 1 Indoor Unit ...
Page 29: ...29 5 2 Outdoor Unit 5 2 1 WH UD07CE5 A WH UD09CE5 A WH UD07CE5 A 1 WH UD09CE5 A 1 ...
Page 30: ...30 5 2 2 WH UD12CE5 A WH UD14CE5 A WH UD16CE5 A WH UD12CE5 A 1 WH UD14CE5 A 1 WH UD16CE5 A 1 ...
Page 32: ...32 ...
Page 33: ...33 7 Block Diagram 7 1 WH UD07CE5 A WH UD09CE5 A WH UD07CE5 A 1 WH UD09CE5 A 1 ...
Page 34: ...34 7 2 WH UD12CE5 A WH UD14CE5 A WH UD16CE5 A WH UD12CE5 A 1 WH UD14CE5 A 1 WH UD16CE5 A 1 ...
Page 36: ...36 8 1 2 WH SDC12C6E5 WH SDC14C6E5 WH SDC16C6E5 WH SDC12C6E5 1 WH SDC14C6E5 1 WH SDC16C6E5 1 ...
Page 37: ...37 8 2 Outdoor Unit 8 2 1 WH UD07CE5 A WH UD09CE5 A WH UD07CE5 A 1 WH UD09CE5 A 1 ...
Page 38: ...38 8 2 2 WH UD12CE5 A WH UD14CE5 A WH UD16CE5 A WH UD12CE5 A 1 WH UD14CE5 A 1 WH UD16CE5 A 1 ...
Page 40: ...40 9 1 2 WH SDC12C6E5 WH SDC14C6E5 WH SDC16C6E5 WH SDC12C6E5 1 WH SDC14C6E5 1 WH SDC16C6E5 1 ...
Page 41: ...41 9 2 Outdoor Unit 9 2 1 WH UD07CE5 A WH UD09CE5 A WH UD07CE5 A 1 WH UD09CE5 A 1 ...
Page 42: ...42 9 2 2 WH UD12CE5 A WH UD14CE5 A WH UD16CE5 A WH UD12CE5 A 1 WH UD14CE5 A 1 WH UD16CE5 A 1 ...
Page 43: ...43 10 Printed Circuit Board 10 1 Indoor Unit 10 1 1 Main Printed Circuit Board ...
Page 44: ...44 10 1 2 Solar Printed Circuit Board Optional ...
Page 46: ...46 10 2 1 2 Capacitor Printed Circuit Board 10 2 1 3 Noise Filter Printed Circuit Board ...
Page 48: ...48 10 2 2 2 Capacitor Printed Circuit Board 10 2 2 3 Noise Filter Printed Circuit Board ...
Page 54: ...54 11 3 4 2 Wire Stripping and Connecting Requirement ...
Page 73: ...73 ...
Page 79: ...79 ...
Page 80: ...80 ...
Page 90: ...90 ...
Page 140: ...140 18 3 To Remove Pressure Gauge 18 4 To Remove Control Panel ...
Page 141: ...141 18 5 To Remove RCCB 18 6 To Remove Transformer and Electronic Controller Board ...
Page 166: ...166 19 4 Hydraulic Pump Performance 07C3 09C3 12C6 14C6 16C6 ...
Page 169: ...169 20 2 WH UD07CE5 A WH UD09CE5 A WH UD07CE5 A 1 WH UD09CE5 A 1 ...
Page 170: ...170 ...
Page 174: ...174 20 3 WH UD12CE5 A WH UD14CE5 A WH UD16CE5 A WH UD12CE5 A 1 WH UD14CE5 A 1 WH UD16CE5 A 1 ...
Page 175: ...175 ...