12.3.3.5 Drain Elbow and Hose Installation
Fix the drain elbow
2
and packing
9
to the bottom of
indoor unit, like show in illustration.
Use inner diameter 17 mm drain hose in the market.
This hose must to be installed in a continuously
downward direction and in a frost-free environment.
Guides this hose’s outlet to outdoor only.
Do not insert this hose into sewage hose or cleaning
hose that may generate ammonia gas sulfuric gas, etc.
If necessary, use hose clamp to further tighten the hose
at drain hose connector to prevent leakage.
The water may drip from drain hose. Therefore must
ensure the outlet of the hose is always not closed or
blocked.
12.3.4 Connect the Cable to the Indoor Unit
1 Connecting cable between indoor unit and outdoor unit shall be approved polychloroprene sheathed
4 x 4.0 or 6.0 mm
2
flexible cord, type designation 60245 IEC 57 or heavier cord.
o
Ensure the colour of wires of outdoor unit and the terminal No. are the same to the indoor unit’s
respectively.
o
Earth wire shall be longer than the other wires as shown in the figure for the electrical safety in case of
the slipping out of the cord from the Holder (Clamper).
2 An isolating device must be connected to the power supply cable.
o
Isolating device (Disconnecting means) should have minimum 3.0 mm contact gap.
o
Connect the approved polychloroprene sheathed power supply 1 cord (3 x 4.0 or 6.0 mm
2
) and power supply
2 cord (3 x 4.0 mm
2
) and power supply 3 cord (3 x 1.5 mm
2
), type designation 60245 IEC 57 or heavier cord
to the terminal board, and to the other end of the cord to isolating device (Disconnecting means).
3 To avoid the cable and cord being damaged by sharp edges, the cable and cord must be passed through a
bushing (located at the bottom of indoor unit) before being connected to the terminal block. The bushing must
be used and must not be removed.
Connecting with external device (optional)
1
All connections shall
follow to the local national wiring standard.
2 It is strongly recommended to use manufacturer-recommended parts and accessories for installation.
3 Maximum output power of booster heater shall be
≤
3 kW. Booster Heater cord must be (3 x min 1.5 mm
2
), of
type designation 60245 IEC 57 or heavier.
4 Two-way Valve shall be spring and electronic type, refer to “Field Supply Accessories” table for details. Valve
cable shall be (3 x min 0.5 mm
2
), of type designation 60245 IEC 57 or heavier, or similarly double insulation
sheathed cable.
* note: - Two-way Valve shall be CE marking compliance component.
- Maximum load for the valve is 9.8VA.
5 Three-Way Valve shall be spring and electronic type. Valve’s cable shall be (3 x min 0.5 mm
2
), of type
designation 60245 IEC 57 or heavier, or similarly double insulation sheathed cable.
* note: - Shall be CE marking compliance component.
- It shall be directed to heating mode when it is OFF.
- Maximum load for the valve is 9.8 VA.
6 Room Thermostat cable must be (4 or 3 x min 0.5 mm
2
), double insulation layer of PVC-sheathed or rubber-
sheathed cable.
7 Tank OLP cable must be (2 x min 0.5 mm
2
), double insulation layer of PVC-sheathed or rubber-sheathed
cable.
* note: if such connection deemed NO necessary for tank OLP, please connect jumper between terminal no.
13 and 14.
8 Tank Sensor shall be resistance type, please refer to Graph 5.1 for the characteristic and details of
sensor. Its cable shall be (2 x min 0.3 mm
2
), double insulation layer (with insulation strength of min 30 V)
of PVC-sheathed or rubber-sheathed cable.
Summary of Contents for WH-SDC07C3E5
Page 22: ...22 4 Location of Controls and Components 4 1 Indoor Unit 4 1 1 Location of Control ...
Page 23: ...23 ...
Page 24: ...24 ...
Page 25: ...25 4 1 2 Weekly Timer Setting ...
Page 26: ...26 4 1 3 Setting Up the Special Functions ...
Page 27: ...27 4 1 4 Main Components 4 2 Outdoor Unit ...
Page 28: ...28 5 Dimensions 5 1 Indoor Unit ...
Page 29: ...29 5 2 Outdoor Unit 5 2 1 WH UD07CE5 A WH UD09CE5 A WH UD07CE5 A 1 WH UD09CE5 A 1 ...
Page 30: ...30 5 2 2 WH UD12CE5 A WH UD14CE5 A WH UD16CE5 A WH UD12CE5 A 1 WH UD14CE5 A 1 WH UD16CE5 A 1 ...
Page 32: ...32 ...
Page 33: ...33 7 Block Diagram 7 1 WH UD07CE5 A WH UD09CE5 A WH UD07CE5 A 1 WH UD09CE5 A 1 ...
Page 34: ...34 7 2 WH UD12CE5 A WH UD14CE5 A WH UD16CE5 A WH UD12CE5 A 1 WH UD14CE5 A 1 WH UD16CE5 A 1 ...
Page 36: ...36 8 1 2 WH SDC12C6E5 WH SDC14C6E5 WH SDC16C6E5 WH SDC12C6E5 1 WH SDC14C6E5 1 WH SDC16C6E5 1 ...
Page 37: ...37 8 2 Outdoor Unit 8 2 1 WH UD07CE5 A WH UD09CE5 A WH UD07CE5 A 1 WH UD09CE5 A 1 ...
Page 38: ...38 8 2 2 WH UD12CE5 A WH UD14CE5 A WH UD16CE5 A WH UD12CE5 A 1 WH UD14CE5 A 1 WH UD16CE5 A 1 ...
Page 40: ...40 9 1 2 WH SDC12C6E5 WH SDC14C6E5 WH SDC16C6E5 WH SDC12C6E5 1 WH SDC14C6E5 1 WH SDC16C6E5 1 ...
Page 41: ...41 9 2 Outdoor Unit 9 2 1 WH UD07CE5 A WH UD09CE5 A WH UD07CE5 A 1 WH UD09CE5 A 1 ...
Page 42: ...42 9 2 2 WH UD12CE5 A WH UD14CE5 A WH UD16CE5 A WH UD12CE5 A 1 WH UD14CE5 A 1 WH UD16CE5 A 1 ...
Page 43: ...43 10 Printed Circuit Board 10 1 Indoor Unit 10 1 1 Main Printed Circuit Board ...
Page 44: ...44 10 1 2 Solar Printed Circuit Board Optional ...
Page 46: ...46 10 2 1 2 Capacitor Printed Circuit Board 10 2 1 3 Noise Filter Printed Circuit Board ...
Page 48: ...48 10 2 2 2 Capacitor Printed Circuit Board 10 2 2 3 Noise Filter Printed Circuit Board ...
Page 54: ...54 11 3 4 2 Wire Stripping and Connecting Requirement ...
Page 73: ...73 ...
Page 79: ...79 ...
Page 80: ...80 ...
Page 90: ...90 ...
Page 140: ...140 18 3 To Remove Pressure Gauge 18 4 To Remove Control Panel ...
Page 141: ...141 18 5 To Remove RCCB 18 6 To Remove Transformer and Electronic Controller Board ...
Page 166: ...166 19 4 Hydraulic Pump Performance 07C3 09C3 12C6 14C6 16C6 ...
Page 169: ...169 20 2 WH UD07CE5 A WH UD09CE5 A WH UD07CE5 A 1 WH UD09CE5 A 1 ...
Page 170: ...170 ...
Page 174: ...174 20 3 WH UD12CE5 A WH UD14CE5 A WH UD16CE5 A WH UD12CE5 A 1 WH UD14CE5 A 1 WH UD16CE5 A 1 ...
Page 175: ...175 ...