The dimmer will respond to BASIC and MULTILEVEL SWITCH commands that are 

part of the Z-Wave

 system. If PAD19 is included as a secured node, it will only re-

spond to the security encapsulation command of BASIC and MULTILEVEL SWITCH.

The Basic Command Class is mapped according to the following table.

Basic Command

Mapped Command 

Basic Set (Value) 

Multilevel Switch Set (Value) 

Basic Report (Current Value, Duration) 

Multilevel Switch Report (Value, Dura-

tion). 

Z-Wave

 Association Groups

The PAD19 can be set to send reports to associated Z-Wave

 devices. It supports 

one association group with five nodes support for group 1. 

For group 1, the dimmer will report MULTILEVEL_SWITCH_REPORT, NOTIFICA-

TION_REPORT and DEVICE_RESET_LOCALLY_NOTIFICATION.

1. Grouping 1 Lifeline (Maximum 5 nodes)

.

2. MULTILEVEL_SWITCH_REPORT

When “on” or “off” state has been changed, 

it will send Multilevel Switch Report to the nodes of Grouping 1.

3. NOTIFICATION_REPORT 

When overload occurred.

4. DEVICE_RESET_LOCALLY_NOTIFICATION

When PAD19 is reset manually, it will send 

DEVICE_RESET_LOCALLY_NOTIFICATION to the nodes of group 1.

Z-Wave

 configuration

No.

Name

Size

(Byte)

Default

Value

Description (Info)

1

Power-on recov-

ery status set

1

0

0~2

To set dimmer level when AC 

power on.

Setting value:

0: OFF-0%

1: ON-last level

2: ON-100%

2

RF report set

1

1

0~1

To set if device send Multilevel 

Switch report to gateway when 

dimming finished.

Setting value:

1: report ON

0: report OFF

3

Maximum level

1

99

(Minimum 

level+1)~99

To set dimming level maximum 

value. Dimming level will not over 

the setting value. 

Setting value:

Cannot be lower than the Mini-

6

Summary of Contents for PAD19

Page 1: ...re for the products firmware up grade Main features of Philio s In Wall Micro dimmer Compatible with any Z Wave or Z Wave Plus Controller Supports Z Wave network Security Modes S2 To be installed with LED dimmer or incandescent lamp A single live without neutral lead To be installed in wall switch boxes Specification Operating Rated 100 240Vac 50Hz 60Hz 0 7A Output load Max 0 7A 100 240VAC 160W Di...

Page 2: ...ectrical wire properly 2 The dimmer break down 1 Check power connections 2 Don t open up the dimmer and send it for repair The device can not join to Z Wave network The device may in a Z Wave network Exclude the device then include again Flashing during dimming Minimum load is less than 20W Replace larger load Installation steps There are two wiring methods for PAD19 A Connect the AC L line and th...

Page 3: ...ays performed with disconnected voltage Choosing a Suitable Location 1 Do NOT place the module device direct under sunlight in a humid place or in any location where they may contact moisture dirt dust 2 Do NOT place the module device where exists combustible substance or any source of heat fires radiators boiler etc 3 When the module device be used the module device might get warm This is a norma...

Page 4: ...in 3 seconds to enter inclusion mode SmartStart 1 The product has a DSK string Key in the first five digits to initiate the SmartStart process or scan QR code Ex DSK 18112 24021 48001 62259 57092 27453 08187 47408 2 SmartStart enabled products can be added into a Z Wave network by scanning the Z Wave QR Code on the product with a controller providing SmartStart inclusion No further action is requi...

Page 5: ... has not been allocated a node ID the LED light will flash on and off alternately at 1 second intervals By press ing the On Off button LED light will stop flashing temporarily Learning Flashes when learning is successful Over load LED flashes one time every 0 4 seconds Manual dim level control Long press the button the light will increase the lighting slowly Short press the button the light will b...

Page 6: ...and DEVICE_RESET_LOCALLY_NOTIFICATION 1 Grouping 1 Lifeline Maximum 5 nodes 2 MULTILEVEL_SWITCH_REPORT When on or off state has been changed it will send Multilevel Switch Report to the nodes of Grouping 1 3 NOTIFICATION_REPORT When overload occurred 4 DEVICE_RESET_LOCALLY_NOTIFICATION When PAD19 is reset manually it will send DEVICE_RESET_LOCALLY_NOTIFICATION to the nodes of group 1 Z Wave config...

Page 7: ...he network will act as repeaters regard less of vendor to increase reliability of the network Over The Air Firmware Update The device support the Z Wave firmware update via OTA Let the Z WaveTM Controller into the firmware update mode choose the hex file to update Wait for 10 15 minutes At that time please don t remove the power otherwise it will cause the firmware broken and the device will no fu...

Page 8: ...stallation This equipment generates uses and can radiate radio frequency energy and if not installed and used in accordance with the instructions may cause harmful interfer ence to radio communications However there is no guarantee that interference will not occur in a particular installa tion If this equipment does cause harmful interference to radio or television recep tion which can be determin...

Page 9: ...低功率射頻器材之使用不得影響飛航安全及干擾合法通信 經發現有干擾現象時 應 立即停用 並改善至無干擾時方得繼續使用 前述合法通信 指依電信管理法規定作業之無線電通信 低功率射頻器材須忍受合法通 信或工業 科學及醫療用電波輻射性電機設備之干擾 9 ...

Reviews: