The PFlow Industries, Inc. Vertical
Reciprocating Conveyor (VRC) is equipped
with an Overcurrent Sensor (OCS). The OCS
is pre wired and located inside the electrical
control panel. See Figure 21-1.
The OCS monitors the motor amp draw and
provides enhanced over current protection of
the lift motor. The OCS must be adjusted to the
maximum “expected” current draw. If the motor
current rises above the OCS set point, the OCS
will trip. Tripping can be caused by a circuit
malfunction, overloading the capacity of the lift,
or an overhanging load trapped between floors.
1. Turn the trip point dial to its lowest position.
2. Place the maximum product load on the carriage.
Overcurrent Sensor
(OCS) Purpose
Before You Begin
Test and Calibrate the OCS
Overcurrent Sensor Figure 21-1
Read this entire manual.
YES
YES
YES
YES
YES
YES
Run the carriage down.
Run the carriage up.
Run the carriage up and
down several times.
The OCS is
properly adjusted.
NO
NO
NO
Did the OCS trip?
Did the OCS trip?
Did the OCS trip?
Did the OCS trip?
Did the OCS trip?
Did the OCS trip?
Turn the trip point
dial clockwise a
small amount and
run the carriage
down.
Turn the trip point
dial clockwise a
small amount and
run the carriage up.
Turn the trip point
dial clockwise a
small amount and
run the carriage up
and down several
times.