Operating Manual DTS and DTI 6201C / 6301C Multi-Controller (MC) 086100014 © Pfannenberg GmbH
Page 37 / 43
GB
5.3
Cooling unit and filter mat cleaning tasks
NOTE
Danger of damage to the filter mat due to improper cleaning
Do not wring out the filter mat.
Avoid water jets with high pressure.
Immediately replace filter mats that are contaminated with oil or grease.
Requirements
-
The cooling unit is de-energized.
-
The unit cover is removed
.
Time intervals for the cleaning or replacement of filter mats depend heavily on the ambient air contamination.
Required tools and material
- Brush
- Water below 40 °C
- Mild detergent
- Vacuum or compressed air cleaner
Procedure
Clean the heat exchangers using a soft brush or compressed air.
If the cooling units have a pre-filter, the filter mat must be cleaned at regular intervals.
Wash the filter mat with water at a temperature of up to 40 °C and commercially available mild detergent.
If the dirt is dry, vacuum, blow or knock the dirt off of the filter mat.
Ensure that correct and safe operation is assured after cleaning.
The cooling unit is clean.