Operating Manual DTS and DTI 6201C / 6301C Multi-Controller (MC) 086100014 © Pfannenberg GmbH
Page 13 / 43
GB
2.6
Technical data
2.6.1
Refrigeration data
Designation
Model DTI/DTS 6201C
Model DTI/DTS 6301C
Cooling capacity A35
/
A35
* / **
Q
0
1000 W
1500 W
Cooling capacity A50 / A35
* / **
Q
0
590 W
850 W
Refrigerant type
*
R 134a
Refrigerant quantity
*
500 g
Temperature setpoint (factory setting)
+35°C (+95°F)
Fault indication: Switch cabinet interior
temperature (factory setting)
> +50°C (+122°F)
Ambient air temperature
+15°C (+59°F) bis +55°C (+131°F)
Switch cabinet interior temperature
+25°C (+77°F) bis +45°C (+113°F)
Air volume flow, exterior circuit
885 m³/h
Air volume flow, interior circuit
885 m³/h
Condensate separation
Condensate evaporator
2.6.1 Electrical data
Designation
Model DTI/DTS 6201C
Model DTI/DTS 6301C
Rated
operating
voltage
*
/
****
400 V 2~
Rated frequency
*
50 / 60 Hz
Functional range
DIN IEC 60038
50 Hz
60 Hz
50 Hz
60 Hz
Power consumption
*
P
el
A35/A35
480 W
570
W
770 W
820 W
Rated current*
I
nom max
1,8 A
2,1 A
3,5 A
3,3 A
Starting current*
I
Start max
9,1 A
16 A
2.6.2 Dimensions
Description
Model DTI/DTS 6201C
Model DTI/DTS 6301C
Height DTS
968 mm
Height DTI
962 mm
Width
410 mm
Depth with cover (standard)
253 mm
Installation depth DTI
60 mm
Weight
DTI: 46 kg / DTS: 47 kg
DTI: 50 kg / DTS: 51 kg
Installation attitude
Vertical
Unit construction
Standard: Steel sheet
2.6.3 Other unit data
Designation
Model DTI/DTS 6201C
Model DTI/DTS 6301C
Anti-corrosion protection
Standard: Galvanized, electrostatic powder-coated (200°C)
Variant: Stainless steel cover
Protection type
When used as intended:
IP 54 against the switch cabinet (EN 60529).
IP 34 against the environment (EN 60529).
*
Data on the type plate.
**
Use of optional filter mats reduces the cooling capacity.
***
Max. rated current UL at 60 Hz.
****
With a change to the rated operating voltage, adapt the
upstream fuse; see
Adapting the upstream fuse .