PFA SERIES INSTALLATION, OPERATION, MAINTENANCE
INSTALLATION
ELECTRICAL POWER SUPPLY (NORTH AMERICAN MODELS)
• Your PERFECT FRY PFA must be connected to a dedicated electrical circuit that meets your fryer’s requirements
(see table below).
CAUTION Improper installation may damage the fryer and void your warranty.
• All electrical connections to comply with local and national standards and codes.
•
If your fryer’s plug does not fit your wall outlet receptacle, have an electrician install the appropriate NEMA receptacle
within 4 feet of the fryer.
•
See the manufacturer’s label on your fryer for the electrical Model No. PFAXXX, then check off your Model Number.
• Your PERFECT FRY is equipped with a heat lamp outlet for an optional PFW heat lamp rated at 400W (240V/2A).
PFC Model
Voltage
Amps
Circuit Amps
Watts
Power Supply
PFA 720
240
32.0
Fryer 30
Acc. 2
Minimum 40
7600
Fryer 7200
Acc. 400
For Use on an individual branch circuit rated
40A minimum. For supply connectors, use
minimum no. 8 AWG wire (40A rated). This
Fryer must be properly connected to a ground-
ed dededicated 240 VAC single phase circuit
according to local installation standards and
codes
PFA 570
240
26.0
Fryer 24
Acc. 2
Minimum 30
6100
Fryer 5700
Acc. 400
For Use on an individual branch circuit rated
30A minimum. For supply connectors, use
minimum no. 8 AWG wire (40A rated). This
Fryer must be properly connected to a ground-
ed dededicated 240 VAC single phase circuit
according to local installation standards and
codes
PFA 570
208
29.5
Fryer 28
Acc. 1.5
Minimum 30
6000
Fryer 5700
Acc. 300
For Use on an individual branch circuit rated
40A minimum. For supply connectors, use
minimum no. 8 AWG wire (40A rated). This
Fryer must be properly connected to a ground-
ed dededicated 208 VAC single phase circuit
according to local installation standards and
codes
PFA 375
240
18
Fryer 16
Acc. 2
Minimum 20
4150
Fryer 3750
Acc. 400
For Use on an individual branch circuit rated
20A minimum. For supply connectors, use
minimum no. 12 AWG wire (25A rated). This
Fryer must be properly connected to a ground-
ed dededicated 240 VAC single phase circuit
according to local installation standards and
codes
PFA 720*
400/230/3Ø
Wye (4 wire)
11
15
7200
This Fryer must be properly Connected to a
grounded dededicated 400 VAC three phase
circuit according to local installation standards
and codes
PFA 570*
400/230/3Ø
Wye (4 wire)
9
15
5700
This Fryer must be properly Connected to a
grounded dededicated 400 VAC three phase
circuit according to local installation standards
and codes
International only, not available in US or Canada.