Original manual in German Version 1.0.2 2022.10.06
14/39
Fuses
ATTENTION!
Fuses are safety-relevant components!
Only fuses in the specified current range may be used.
Non-compliance poses the risk of fire or destruction of the circuit boards!
Fuse in the control unit housing (accessible from the outside)
Fuse
Current
Fuse type
Function
6.3 A
5 x 20 mm
Primary fuse mains supply
Fuses on the power pack
Fuse
Current
Fuse type
Function
F1
315 mA
Micro fuse
24 VDC sensors (without function in the IQntrol DOS MODBUS)
F2
2 A
Micro fuse
Primary fuse power pack
F3
1 A
Micro fuse
without function in the IQntrol DOS MODBUS
F4
4 A
Micro fuse
230 VDC outlet relay K2 and K3
F5
1 A
Micro fuse
without function in the IQntrol DOS MODBUS
Relay - outlets
The relay outputs K1 to K3 (SL2 to SL4) are non-potential-free 230 VAC. If a potential-free outlet is needed, an external relay must
be used.
ATTENTION!
The maximum load per outlet is a maximum of 450 watts ohmic load. If a higher load is to be switched, this must
be realised via an additional load relay.
The total output of all devices activated simultaneously may not exceed 900 watts (4 ampere)!