VisuNet GMP RM/PC 200 series
Installation and Commissioning
2018-07
33
Mounting VisuNet GMP to Pedestal
1. Attach the VisuNet GMP with 4 countersunk screws with hexagon socket (M5x16). Use a
allen key (3 mm).
2. Tighten the screws (torque: 5-6 Nm)
Figure 3.7
Mounting VisuNet GMP to Pedestal
Tightening/Plugging up the pedestal/wall arm cable glands
1. Screw the cable glands with a fork wrench.
2. To plug up cable glands that are not in use, lightly tighten the cable gland
3. Plug the plugs in.
4. Firmly thighten the cable gland.
Note!
The IP protection is ony ensured if either a cable is run or a plug is plugged in.
Note!
Fuchs recommand to use a cable with a core-cross section of 4 mm
2
for grounding.