Power Supply PS1000-A6-24.5
Installation Instructions
20
21
-1
1
9
Keep the following minimum installation clearances: 40mm on top, 20mm on the bottom,
5mm left and right side. Increase the 5mm to 15mm in case the adjacent device is a heat
source. When the device is permanently loaded with less than 50%, the 5mm can be reduced
to zero.
The device is designed, tested and approved for branch circuits up to 32A (IEC) and 30A (UL)
without additional protection device. If an external fuse is utilized, do not use circuit breakers
smaller than 6A B- or C-Characteristic to avoid a nuisance tripping of the circuit breaker.
The maximum surrounding air temperature is +70°C (+158°F). The operational temperature
is the same as the ambient or surrounding air temperature and is defined 2cm below
the device.
The device is designed to operate in areas between 5% and 95% relative humidity.