Power Supply PS1000-A6-24.5
AC Input
5
AC Input
The device is suitable to be supplied from TN-, TT- and IT mains networks with AC voltage.
For suitable DC supply voltages see
chapter 4
Figure 5.1
Input voltage range
Figure 5.2
Turn-on behavior, definitions
AC input
Nom. AC 100-240V
AC input range
Min.
85-264Vac
Continuous operation
Min.
264-300Vac
Occasionally for maximal 500ms
Allowed voltage L or N to
earth
Max. 300Vac
Continuous, according to IEC 60664-1
Input frequency
Nom. 50–60Hz
±6%
Turn-on voltage
Typ.
80Vac
Steady-state value, see Figure 5.1
Shut-down voltage
Typ.
74Vac
Steady-state value, see Figure 5.1
External input protection
See recommendations in chapter 2
AC 100V AC 120V AC 230V
Input current
Typ.
1.30A
1.09A
0.60A
At 24V, 5A, see Figure 5.3
Power factor
Typ.
0.99
0.98
0.91
At 24V, 5A, see Figure 5.4
Crest factor
Typ.
1.7
1.8
2.2
At 24V, 5A, The crest factor is the
mathematical ratio of the peak value to
RMS value of the input current waveform.
Start-up delay
Typ.
420ms
400ms
385ms
See Figure 5.2
Rise time
Typ.
80ms
85ms
90ms
At 24V, 5A const. current load, 0mF load
capacitance, see Figure 5.2
Typ.
100ms
100ms
110ms
At 24V, 5A const. current load, 5mF load
capacitance, see Figure 5.2
Turn-on overshoot Max.
200mV
200mV
200mV
See Figure 5.2
Tu
rn
-o
n
85V
Rated
input range
max.
500ms
V
IN
P
OUT
300Vac
264V
Shut
-dow
n
Start-up
delay
Rise
Time
O
ve
rs
h
oot
- 5%
Output
Voltage
Input
Voltage