Universal Temperature Converter KCD2-UT2-(Ex)1
Editing device data
81
39
68
20
13
-10
EN - 23
EN
The following parameters can be set:
•
Characteristic
:
4 mA ... 20 mA unlimited
4 mA ... 20 mA (NE 43)
4 mA ... 20 mA limited
0 mA ... 20 mA
For information on the behaviour of the current output at the different settings, see section 7.4.
•
Start value
of the measurement range
The minimum possible value is displayed according to the selected sensor. You can also use
the
Adopt from measured value
button for the start value.
•
End value
of the measurement range
The maximum possible value is displayed according to the selected sensor. You can also use
the
Adopt from measured value
button for the end value.
•
Error Indication
Upscale
Downscale
Hold
Up-/downscale (only suitable for use with RTDs)
•
Characteristic inverted
: see section 7.4; you activate or deactivate the inverted characteristic
by clicking the respective checkbox (
= selected,
= deselected).