Universal Temperature Converter KCD2-UT2-(Ex)1
Mounting and connection
EN
Dimensions of the
KCD2-UT2-(Ex)1 in mm
5.2 Connection
The KC series' slip-off terminals significantly simplify connection and construction of switching
cabinets. They allow quick and error-free exchange of the unit when service is needed.
The terminals can be screwed on, are self-opening, and have generous connection room for a
wire diameter of up to 2.5 mm² and coded plugs, so that leads cannot be confused.
The Intrinsically safe field circuit is connected to the
blue
terminals 1 to 4 of the KCD2-UT2-Ex-1.
These may be conducted using DIN EN 60079-14 compliant leads into the hazardous area.
The non-intrinsically safe field circuit is connected to the
green
terminals 1 to 4 of the
KCD2-UT2-1.
The non-intrinsically safe circuit is connected to the
green
terminals 5 to 10 of the
KCD2-UT2-(Ex)1.
12,7 mm
(0.5")
114 mm (4.49'')
46 mm (1.82'')
58 mm (2.28'')
119 mm (4.7'')
104 mm (4.1'')