Universal Temperature Converter KCD2-UT2-(Ex)1
Editing device data
EN
The following parameters can be set:
•
Sensor
:
Resistance temperature detector:
Pt10GOST
etc.
Thermocouple:
TXK
etc.
Potentiometer
Voltage
•
Connection mode
(for resistance temperature detectors only, see section 5.2):
2-wire
3-wire
4-wire
•
Unit
:
for resistance temperature detectors and thermocouples:
°F
,
K
or
°C
for potentiometers: fixed
ratio
for voltage (sources): fixed
mV
The unit selected here will be used for
all
respective settings and displays in
PACT
ware
TM
.
•
Cold junction compensation
(for thermocouples only):
external (Reference temperature)
internal (K-CJC-**)
If you have selected
Ext. ref. temp.
, you can enter the external reference temperature
(range of values:
-100 °C
to
320 °C
)
For an
internal
Cold junction compensation
, you require the K-CJC-** terminal block as an
accessory instead of the normal terminal 1 to 4 (see section 5.2).
•
Lead Resistance
: When connecting an RTD with 2-wire connection the lead resistance of the
cabling can be entered numerically if known.
•
2-Wire Calibration
: When connecting an RTD with 2-wire connection the lead resistance of the
cabling can be calibrated if the resistance is unknown. For calibration the sensor must be
jumpered.
•
Sensor-breakage monitoring
(for all types of sensors)