Universal Temperature Converter KCD2-UT2-(Ex)1
Editing device data
81
39
68
20
13
-10
EN - 27
EN
7.4.5 Fault current
The following table shows the values of the current output during a fault, depending on the
settings.
Setting
Characteristic
4 mA ... 20 mA
unlimited
Characteristics
4 mA ... 20 mA (NE 43)
4 mA ... 20 mA limited
Characteristic
0 mA ... 20 mA
Upscale
approx. 22 mA
(cannot be distinguished
from value exceeding end
value)
approx. 21.5 mA
approx. 21.5 mA
Downscale
0 mA
(cannot be distinguished
from value below start
value)
2.0 mA
0 mA
(cannot be distinguished
from measurement of the
start value)
Hold
last measured value before the fault
Upscale/
downscale
only makes
sense for RTD
approx. 22 mA
in the case of lead short
circuit
(cannot be distinguished
from value exceeding end
value)
approx. 21.5 mA
in the case of
lead short circuit
approx. 21.5 mA
in the case of lead short
circuit
0 mA
in the case of lead
breakage
(cannot be distinguished
from value below start
value)
2.0 mA
in the case of
lead breakage
0 mA
in the case of lead
breakage
(cannot be distinguished
from measurement of the
start value)