SMART UV® UV DISINFECTION STERILIZER Installation and User's Guide

8.  Thread the black retaining nut (see 

Photo F

) onto 

the male threads of the UV vessel. Hand tight only!

9.  Using the instructions given on page 7, perform the 

Mandatory Leak Test. If no leaks are found proceed 
to page 8, 

UV Lamp Installation

, for instructions on 

installing the UV lamp.

Sterilizer Installation and Operation

  DO NOT operate the UV system at flow 

rates higher than 90 GPM (341 LPM). Operating the 
product in this manner may result in product failure 
and voiding of warranty.

SMART UV

®

 Disinfection Sterilizers are used in 

a variety of applications to control waterborne 
pathogens. Pentair encourages the consideration of 
the installation recommendations provided here.

Suspended solid debris will absorb UV light and 
reduce the UV transmittance through water. By 
operating the SMART UV system after the mechanical 
filter, the unit's overall performance will be increased.

The efficiency of the UV sterilizer operation is directly 
related to the recommended water flow rates found 
in the “Sizing Chart”, on page 1.

Mounting the Vessel

Note: The way UV vessels are mounted/positioned 
plays a very important role in the unit’s performance 
and degree of safety. We STRONGLY RECOMMEND 
that you follow these instructions and guidelines 
precisely. Any deviation from these mounting 
instructions will void any warranty associated with 
the UV vessel and all its components and may cause 
unsafe conditions.

  Trapped air inside the UV vessel during 

operation may create excessive heat thus damaging 
internal components.

Vertical Vessel Mounting

Mount the SMART UV Disinfection 
Sterilizer with the electrical end up. 
Use the bottom port as the inlet 
with the top port as the outlet.

Note: The UV vessel should be 
installed with a vertical clearance 
11/2 times the vessel length. This will 
allow sufficient room for servicing 
the unit and replacing the UV lamp

  The inlet and outlet 

plumbing MUST be supported to 
avoid vessel material stress. 

Failure to support the inlet and outlet plumbing may 
lead to damage to the vessel.

Horizontal Vessel Mounting

Mount the SMART UV system horizontally with the 
inlet/outlet facing up. If the unit is mounted but 
not level, the electrical end of the unit should be 
positioned higher than the non-electrical end. Choose 
the lower port of the inlet

NOTE

: The UV vessel should be installed with a 

horizontal clearance 11/2 times the vessel length. This 
will allow sufficient room for servicing the unit and 
replacing the UV lamp.

INSTALLATION

Summary of Contents for SMART UV E120S

Page 1: ...IMPORTANT SAFETY INSTRUCTIONS READ AND FOLLOW ALL INSTRUCTIONS SAVE THESE INSTRUCTIONS SMART UV UV DISINFECTION STERILIZER INSTALLATION AND USER S GUIDE...

Page 2: ...are not used to indicate an affiliation or endorsement between the owners of these names and brands and Pentair Aquatic Eco Systems Inc Those names and brands may be the trademarks or registered trad...

Page 3: ...uartz Sleeve Assembly and Installation 9 Sterilizer Installation and Operation 10 Typical Installation 10 Mounting the Vessel 10 Mounting the Power Supply 11 Mandatory Leak Test 11 Electrical Connecti...

Page 4: ...missing ordamaged When installing and using this electrical equipment basic safety precautions should always be followed include the following FAILURE TO FOLLOW ALL INSTRUCTIONS AND WARNINGS CAN RESU...

Page 5: ...ay overheat Care should be taken to arrange the cord so that it will not be tripped overor pulled If in doubt consult a qualified electrician Warping of the UV body may occurwhen left in direct sunlig...

Page 6: ...t the highest UV C output conversion among all UV lamps UL listed for indoor and outdoor use fresh and salt water use Long lasting GPH T5 and GPH T6 UV lamps 9 000 hours to 80 efficiency Protective Qu...

Page 7: ...EU18 U EU25 U EU40 EU65P SMART UV HO Sterilizer Models Part Numbers E50S E80S E120S E150S Power Supplies The power supply can either be a cylinder POD or a rectangle style Below are the ballasts that...

Page 8: ...ontact the place of original purchase immediately NOTE Save the corrugated lamp packaging after unpacking the UV lamp Storing the lamp and or quartz sleeve in this packaging while performing maintenan...

Page 9: ...sleeve module use your index finger to ensure that the open end of the quartz sleeve mates smoothly with the inside lip of the clear quartz sleeve module this signifies a good fit See Photo A 5 With...

Page 10: ...important role in the unit s performance and degree of safety We STRONGLY RECOMMEND that you follow these instructions and guidelines precisely Any deviation from these mounting instructions will voi...

Page 11: ...uartz sleeve module has been achieved Failure to achieve a proper quartz sleeve quartz sleeve module seal during SMART UV Disinfection Sterilizer operation will allow water to leak into the inside of...

Page 12: ...er or pulled If in doubt consult a qualified electrician GFCI s are designed to sense an imbalance in electrical current flow within the main electrical leads leakage current When this imbalance maxim...

Page 13: ...UV lamp power cord connection complete and the lamp entirely inside the quartz sleeve carefully screw down the Gray Power Supply Adapter 3 onto the Clear Quartz Sleeve Module 6 hand tighten only 5 Scr...

Page 14: ...al tape on all threaded connections Larger Sized Ponds above 5 000 Gallons Using Surface Skimmer and Pressurized Filter This system is simple yet it achieves critical filtering goals such as good wate...

Page 15: ...water flow meter manufacturer s instructions for proper installation and operation See Diagram 4 NOTE Before gluing piping or reducer bushing into the UV s union or socket remove the quartz sleeve ass...

Page 16: ...sits If using muriatic acid a ratio of four parts water to one part acid should suffice Always introduce acid to the water and never introduce the water to the acid Muriatic acid is corrosive and can...

Page 17: ...n solder to make them firm enough to push back in the new lamp connector NOTE Clean away any residual flux off of the wires before assembling them into the lamp connector 7 Using a new 4 pin lamp conn...

Page 18: ...aker is tripping 1 Immediately disconnect power to the SMART UV Disinfection Sterilizer 2 Turn off the pool pump at the circuit breaker and be sure all flow to the unit has been stopped 3 Refer to pag...

Page 19: ...unions EU18 U 18 WATT 960359 EU25 U 25 WATT 20425 EU40 40 WATT 20440 EU65P 65 WATT 20465 EU80P 80 WATT NA EU130P 130 WATT NA KITS ITEM Quartz Sleeve Module QSM Includes 6 thru 11 Z000 005 6 Power Sup...

Page 20: ...IP 13 UV Sterilizer Housing with unions E50S 50 WATT 209050 E80S 80 WATT 209080 E120S 120 WATT 209120 E150S 150 WATT 209150 KITS ITEM Quartz Sleeve Module QSM Includes 6 thru 11 Z000 005 6 Power Supp...

Page 21: ...21 SMART UV UV DISINFECTION STERILIZER Installation and User s Guide NOTES...

Page 22: ...22 SMART UV UV DISINFECTION STERILIZER Installation and User s Guide NOTES...

Page 23: ...23 SMART UV UV DISINFECTION STERILIZER Installation and User s Guide NOTES...

Page 24: ...popka Blvd Apopka FL 32703 USA Phone 407 886 3939 Web PentairAES com 2018 Pentair Aquatic Eco Systems Inc All rights reserved This document is subject to change without notice P N 02934 INS SMART Rev...

Reviews: