GENERAL SAFETY INFORMATION
Please observe the following general safety instructions when assembling and operating the unit:
• Assembly,installation and servicing may only be performed by properly trained specialists.
• When transporting the enclosure with the cooling unit externally mounted, always use an additional shipping brace
to support the cooling unit.
GENERAL TECHNICAL INFORMATION
The evaporator outlet sensor monitors the enclosure return air temperature to prevent ice buildup on the
evaporator coil. If the air temperature drops below -1°C, the compressor and condenser air mover(s) shut off.
They turn back on when the temperature rises above 15°C.
The compressor and the air movers are equipped with overload protection to guard against excess current and
temperatures.
SEQUENCE OF OPERATION
The air conditioner comes standard with smart controller. During cooling modes, the evaporator fan will be
running.
COOLING
When the enclosure temperature is above the cooling setpoint, power is applied to the compressor and
condenser air mover(s).
Operating the air conditioner below the minimum ambient temperature or above the maximum
ambient temperatures indicated on the nameplate voids all warranties. DO NOT adjust the setpoint to a
temperature lower than 20°C. Doing so can increase the likelihood of frost buildup on the evaporator coil.
The moisture that the sealed enclosure air can contain is limited. If moisture flows from the drain tube
continuously this can only mean that ambient air is entering the enclosure. Be aware that frequent
opening of the enclosure’s door admits humid air that the air conditioner must then dehumidify.
COMPONENT OPERATION
NOTE: Do not reduce the time delay setting on the controller to less than 120 seconds. This may
cause the compressor to cycle too rapidly, shortening the life of the compressor.
SMART CONTROLLER (GENERAL ALARMS)
See Smart Controller on page 12
REMOTE ACCESS CONTROL (OPTIONAL)
See Remote Access Control on page 15
DOOR SWITCH
Several door switches may be connected in series and operated on one cooling unit. The door switch
only supports a floating connection, no external voltages. Remove jumper from terminals 3 and 4 of the
connector and connect the door switch to the two terminals if a door switch is available.
NOTE: The alarm code “TP” will appear on the controller display if this jumper wire is removed
without the addition of a customer installed door switch.
ACTIVE CONDENSATE MANAGEMENT
At low temperatures and high humidity levels inside the enclosure, condensation may form on the
evaporator coil.
Slim Fit air conditioners continuously evaporate the water that may be in the drain pan due to
condensation from the evaporator coil into the external air stream. Excess condensate is routed
downwards out of the air conditioner via a barbed fitting at the bottom of the condenser side of the unit. A
10 mm (.40) inside diameter tube can be attached to the fitting and routed to a nearby drain.
Summary of Contents for S06
Page 9: ... 2015 Pentair Equipment Protection 89116616 9 Figure 3 Figure 4 Figure 5 Figure 6 ...
Page 17: ... 2015 Pentair Equipment Protection 89116616 17 S06 WIRE DIAGRAM 300 500W ...
Page 24: ... 2015 Pentair Equipment Protection 89116616 24 1500W 115V 1500W 230V ...
Page 25: ... 2015 Pentair Equipment Protection 89116616 25 1500W 460V 89107589 REV G ...
Page 26: ... 2015 Pentair Equipment Protection 89116616 26 S10 WIRE DIAGRAMS 1000W 115V 230V ...
Page 27: ... 2015 Pentair Equipment Protection 89116616 27 1000W 460V ...
Page 28: ... 2015 Pentair Equipment Protection 89116616 28 1500W 115V ...
Page 29: ... 2015 Pentair Equipment Protection 89116616 29 1500W 230V ...
Page 30: ... 2015 Pentair Equipment Protection 89116616 30 1500W 460V 89107588 REV H ...
Page 38: ... 2015 Pentair Equipment Protection 89116616 38 2000W 460V 89107589 REV G 2500W 115V ...
Page 39: ... 2015 Pentair Equipment Protection 89116616 39 2500W 230V 2500W 460V 89107593 REV G ...
Page 40: ... 2015 Pentair Equipment Protection 89116616 40 4000W 460V ...
Page 41: ... 2015 Pentair Equipment Protection 89116616 41 S16 WIRE DIAGRAMS 2000W 115V ...
Page 42: ... 2015 Pentair Equipment Protection 89116616 42 2000W 230V ...
Page 43: ... 2015 Pentair Equipment Protection 89116616 43 2000W 460V 89107588 REV H ...
Page 44: ... 2015 Pentair Equipment Protection 89116616 44 2500W 115V ...
Page 45: ... 2015 Pentair Equipment Protection 89116616 45 2500W 230V ...
Page 46: ... 2015 Pentair Equipment Protection 89116616 46 2500W 460V 89107592 REV H ...
Page 47: ... 2015 Pentair Equipment Protection 89116616 47 4000W 460V ...
Page 49: ... 2015 Pentair Equipment Protection 89116616 49 4000W W DKE dKZ ϰϲϬs KE zͿ Ͳ W d WKZd ...
Page 58: ... 2015 Pentair Equipment Protection 89116616 58 NOTES ...
Page 63: ... 2015 Pentair Equipment Protection 89116616 63 NOTES ...