7. Carefully check the compressor for proper operation - motor should cause slight vibration and the
outer case of the compressor should be warm. Is the compressor showing signs of this?
YES, wait 5 minutes, proceed to step 9.
NO, possible problem:
» Defective start or run capacitor
» Defective overload
» Defective start relay
» Defective contactor
» Defective compressor
Repair or Replace
defective part
8. Make sure the coils are clean then check the evaporator air in and air out temperatures. If the
temperatures are the same:
» Possible loss of refrigerant
» Possible bad valves in compressor
Repair or Replace
defective part
BASIC AIR CONDITIONING TROUBLE SHOOTING CHECKLIST
SYMPTOM
POSSIBLE CAUSE
Unit won’t cool
Clogged fins on coil(s)
Dirty filter
Impeller(s) not running
Compressor not running
Compressor runs, but has bad valves
Loss of refrigerant
Compressor tries to start but won’t run
Low line voltage at start. Should be +/-10% rated voltage.
Compressor motor stuck
Bad contactor
Bad overload switch
Bad run/start capacitor
Unit blows breakers
Undersized breaker/fuse or not time delayed
Short in system
Getting water in enclosure
Drain plugged
Drain tube kinked
Enclosure not sealed (allowing humidity in)
Mounting gasket damaged
For additional support, refer to Pentair Cooling Sales and Service Contacts on page 4.
Summary of Contents for S06
Page 9: ... 2015 Pentair Equipment Protection 89116616 9 Figure 3 Figure 4 Figure 5 Figure 6 ...
Page 17: ... 2015 Pentair Equipment Protection 89116616 17 S06 WIRE DIAGRAM 300 500W ...
Page 24: ... 2015 Pentair Equipment Protection 89116616 24 1500W 115V 1500W 230V ...
Page 25: ... 2015 Pentair Equipment Protection 89116616 25 1500W 460V 89107589 REV G ...
Page 26: ... 2015 Pentair Equipment Protection 89116616 26 S10 WIRE DIAGRAMS 1000W 115V 230V ...
Page 27: ... 2015 Pentair Equipment Protection 89116616 27 1000W 460V ...
Page 28: ... 2015 Pentair Equipment Protection 89116616 28 1500W 115V ...
Page 29: ... 2015 Pentair Equipment Protection 89116616 29 1500W 230V ...
Page 30: ... 2015 Pentair Equipment Protection 89116616 30 1500W 460V 89107588 REV H ...
Page 38: ... 2015 Pentair Equipment Protection 89116616 38 2000W 460V 89107589 REV G 2500W 115V ...
Page 39: ... 2015 Pentair Equipment Protection 89116616 39 2500W 230V 2500W 460V 89107593 REV G ...
Page 40: ... 2015 Pentair Equipment Protection 89116616 40 4000W 460V ...
Page 41: ... 2015 Pentair Equipment Protection 89116616 41 S16 WIRE DIAGRAMS 2000W 115V ...
Page 42: ... 2015 Pentair Equipment Protection 89116616 42 2000W 230V ...
Page 43: ... 2015 Pentair Equipment Protection 89116616 43 2000W 460V 89107588 REV H ...
Page 44: ... 2015 Pentair Equipment Protection 89116616 44 2500W 115V ...
Page 45: ... 2015 Pentair Equipment Protection 89116616 45 2500W 230V ...
Page 46: ... 2015 Pentair Equipment Protection 89116616 46 2500W 460V 89107592 REV H ...
Page 47: ... 2015 Pentair Equipment Protection 89116616 47 4000W 460V ...
Page 49: ... 2015 Pentair Equipment Protection 89116616 49 4000W W DKE dKZ ϰϲϬs KE zͿ Ͳ W d WKZd ...
Page 58: ... 2015 Pentair Equipment Protection 89116616 58 NOTES ...
Page 63: ... 2015 Pentair Equipment Protection 89116616 63 NOTES ...