DISPLAYING TEMPERATURE SENSOR #2
Sensor number 2, the air outlet or evaporator coil sensor, can be viewed at any time by pressing the up or down
arrow button on the front panel of the controller display. The display will revert to displaying temperature sensor
number 1 (the evaporator air inlet temperature) after 60 seconds. Both sensors can also be read through the
Ethernet and USB connections with the optional communications board.
COMPRESSOR RESTART TIME DELAY
A factory set 5 minute (300 second) restart delay exists to reduce residual back pressure before allowing the
compressor to restart. The compressor will stay off for the entire restart duration after the compressor is
disabled. A flashing 1 on the controller display will indicate the unit is in a compressor restart delay while calling
for cooling. If the time delay is reduced to less than five (5) minutes, this may cause reduced compressor life.
ALARM OUTPUT CONTACT
The smart controller has a normally open dry contact alarm output with a resistive load rating of 250 VAC at 3
amps. A connector located on the enclosure side of the unit provides a 2 pin connection to this output marked
YEL/ALARM.
ALARM INPUT CONNECTION
The smart controller can accept a dry contact/switch input via the connector terminals marked WHT/DS1 and
WHT/DS2 located on the enclosure side of the unit. This input is associated with the controller display alarm
mnemonic TP (door open and/or smoke detected). To use this feature, remove the jumper wire connecting
terminals DS1 and DS2 and replace with customer supplied wires from the enclosure door switch to DS1 and DS2
terminals.
ALARM CONDITION DISPLAY
There are seven possible non-latching alarm conditions detectable by the controller and are indicated on the
controller display. All alarms can also be accessed through the Ethernet and USB connections with the optional
communications board.
Alarm Mnemonic
Description
Cause
Result
Alarm Relay
TP
General Alarm
Door open and/or smoke
detected
Unit turns off for duration
of alarm
Relay Contacts Close
LA
High Pressure Warning
MALF high pressure
switch opens (See Note 3
below)
No effect on function
N/A
E1
Air Inlet Temperature
Sensor Alarm
Sensor Failure
See Note 1 below
Relay Contacts Close
E2
Air Outlet Temperature
Sensor Alarm
Sensor Failure
See Note 2 below
Relay Contacts Close
Ht
High Temperature Alarm
Default = 55°C
Air inlet temperature
greater than 55°C
No effect on function
Relay Contacts Close
Lt
Low Temperature Alarm
Default = 14°C
Air inlet temperature less
than 14°C
No effect on function
Relay Contacts Close
A1
Frost Alarm
Air outlet temperature
less than or equal to
-1.0°C
Compressor and
Condenser fan off for
duration of alarm
Relay Contacts Close
NOTE 1: Air inlet temperature sensor will default to air outlet temperature sensor. Cooling set point defaults to 10°C.
NOTE 2: Unit continues to operate without evaporator freeze protection.
NOTE 3: The MALF high pressure switch is optional.
Summary of Contents for S06
Page 9: ... 2015 Pentair Equipment Protection 89116616 9 Figure 3 Figure 4 Figure 5 Figure 6 ...
Page 17: ... 2015 Pentair Equipment Protection 89116616 17 S06 WIRE DIAGRAM 300 500W ...
Page 24: ... 2015 Pentair Equipment Protection 89116616 24 1500W 115V 1500W 230V ...
Page 25: ... 2015 Pentair Equipment Protection 89116616 25 1500W 460V 89107589 REV G ...
Page 26: ... 2015 Pentair Equipment Protection 89116616 26 S10 WIRE DIAGRAMS 1000W 115V 230V ...
Page 27: ... 2015 Pentair Equipment Protection 89116616 27 1000W 460V ...
Page 28: ... 2015 Pentair Equipment Protection 89116616 28 1500W 115V ...
Page 29: ... 2015 Pentair Equipment Protection 89116616 29 1500W 230V ...
Page 30: ... 2015 Pentair Equipment Protection 89116616 30 1500W 460V 89107588 REV H ...
Page 38: ... 2015 Pentair Equipment Protection 89116616 38 2000W 460V 89107589 REV G 2500W 115V ...
Page 39: ... 2015 Pentair Equipment Protection 89116616 39 2500W 230V 2500W 460V 89107593 REV G ...
Page 40: ... 2015 Pentair Equipment Protection 89116616 40 4000W 460V ...
Page 41: ... 2015 Pentair Equipment Protection 89116616 41 S16 WIRE DIAGRAMS 2000W 115V ...
Page 42: ... 2015 Pentair Equipment Protection 89116616 42 2000W 230V ...
Page 43: ... 2015 Pentair Equipment Protection 89116616 43 2000W 460V 89107588 REV H ...
Page 44: ... 2015 Pentair Equipment Protection 89116616 44 2500W 115V ...
Page 45: ... 2015 Pentair Equipment Protection 89116616 45 2500W 230V ...
Page 46: ... 2015 Pentair Equipment Protection 89116616 46 2500W 460V 89107592 REV H ...
Page 47: ... 2015 Pentair Equipment Protection 89116616 47 4000W 460V ...
Page 49: ... 2015 Pentair Equipment Protection 89116616 49 4000W W DKE dKZ ϰϲϬs KE zͿ Ͳ W d WKZd ...
Page 58: ... 2015 Pentair Equipment Protection 89116616 58 NOTES ...
Page 63: ... 2015 Pentair Equipment Protection 89116616 63 NOTES ...