DISPLAYING AND CHANGING PROGRAM VARIABLES
Access:
To view and/or change parameters, press and hold the Prg and Sel buttons for greater than 5 seconds.
Press the up or down arrow buttons until 22 is displayed, then press Sel button. When S-P is displayed, press Sel.
Navigation:
Press up or down arrows to display sub-menus then press Sel to select the desired sub-menu. In the
sub-menu, use up or down arrows to display parameters for viewing or changing and press Sel. Use Prg button to
back out of menu levels as desired.
Adjust:
Use the up or down arrows to change the parameter value then push Sel to save that setting. If Sel is not
pressed, the change to the value will not be saved. Navigate to and change other parameters as desired. When
finished, push Prg to back out of the sub-menus to the main menu.
NOTE: The display will revert to normal temperature display mode if no buttons are pressed for
60 seconds.
MODELS WITH °C CONTROLLER
Cooling turns on at r01 (Setpoint), and off at r01 (Setpoint) - r02 (Differential).
For example, using default values from the table below, cooling will turn on at 35 °C (setpoint), and turn
off at 30 °C (setpoint – differential).
OPERATING PARAMETERS
Parameter
Description
Default Value
Range
r01
Cooling set-point
35°C
20°C to 55°C
r02
Cooling differential
5°C
-
ALARM PARAMETERS
Parameter
Default Value
Range
Description
P16
55°C
-
High Temperature Alarm
P19
14°C
-
Low Temperature Alarm
MODELS WITH °F CONTROLLER
Cooling turns on at r01 (Setpoint) + r02 (Differential), and off at r01 (Setpoint).
For example, using default values from the table below, cooling will turn on at 87 °F (se
differential), and turn off at 80 °F (setpoint).
OPERATING PARAMETERS
Parameter
Description
Default Value
Range
r01
Cooling set-point
80°F
72°F to 120°F
r02
Cooling differential
7°F
-
ALARM PARAMETERS
Parameter
Default Value
Range
Description
P16
125°F
-
High Temperature Alarm
P19
40°F
-
Low Temperature Alarm
Summary of Contents for S06
Page 9: ... 2015 Pentair Equipment Protection 89116616 9 Figure 3 Figure 4 Figure 5 Figure 6 ...
Page 17: ... 2015 Pentair Equipment Protection 89116616 17 S06 WIRE DIAGRAM 300 500W ...
Page 24: ... 2015 Pentair Equipment Protection 89116616 24 1500W 115V 1500W 230V ...
Page 25: ... 2015 Pentair Equipment Protection 89116616 25 1500W 460V 89107589 REV G ...
Page 26: ... 2015 Pentair Equipment Protection 89116616 26 S10 WIRE DIAGRAMS 1000W 115V 230V ...
Page 27: ... 2015 Pentair Equipment Protection 89116616 27 1000W 460V ...
Page 28: ... 2015 Pentair Equipment Protection 89116616 28 1500W 115V ...
Page 29: ... 2015 Pentair Equipment Protection 89116616 29 1500W 230V ...
Page 30: ... 2015 Pentair Equipment Protection 89116616 30 1500W 460V 89107588 REV H ...
Page 38: ... 2015 Pentair Equipment Protection 89116616 38 2000W 460V 89107589 REV G 2500W 115V ...
Page 39: ... 2015 Pentair Equipment Protection 89116616 39 2500W 230V 2500W 460V 89107593 REV G ...
Page 40: ... 2015 Pentair Equipment Protection 89116616 40 4000W 460V ...
Page 41: ... 2015 Pentair Equipment Protection 89116616 41 S16 WIRE DIAGRAMS 2000W 115V ...
Page 42: ... 2015 Pentair Equipment Protection 89116616 42 2000W 230V ...
Page 43: ... 2015 Pentair Equipment Protection 89116616 43 2000W 460V 89107588 REV H ...
Page 44: ... 2015 Pentair Equipment Protection 89116616 44 2500W 115V ...
Page 45: ... 2015 Pentair Equipment Protection 89116616 45 2500W 230V ...
Page 46: ... 2015 Pentair Equipment Protection 89116616 46 2500W 460V 89107592 REV H ...
Page 47: ... 2015 Pentair Equipment Protection 89116616 47 4000W 460V ...
Page 49: ... 2015 Pentair Equipment Protection 89116616 49 4000W W DKE dKZ ϰϲϬs KE zͿ Ͳ W d WKZd ...
Page 58: ... 2015 Pentair Equipment Protection 89116616 58 NOTES ...
Page 63: ... 2015 Pentair Equipment Protection 89116616 63 NOTES ...