120 VAC pool/spa lights must be connected to a Ground Fault Circuit Interrupter (GFCI), with an

appropriately rated circuit breaker. See Figure 1. For Canada, 120 and 12 VAC lights must have a Ground
Fault Circuit Interrupter (GFCI), and have an appropriately rated circuit breaker.

b.

The Junction Box (or 12 volt light models, the low voltage transformer) must be located at least 8 in (20.32

cm) above the maximum water level and at least 4 in (10.2 cm) above the ground level or pool deck which-
ever provides the greater elevation. The junction box shall be no less than 4 ft (1.22 m) from the inside wall
of the pool, unless separated from the pool by a solid fence, wall or other permanent barrier.  See Figure 1.
The Junction Box should also be located at least 48 in (122 cm) minimum (3 m (10 ft.) Canada) from the
edge of the pool, see Figure 1.

c.

The light fixture and all metal items within 5 ft. (153 cm) minimum of the pool must be properly electrically

bonded.

d.

Bond the niche-fixture housing to all other metallic items within 5 ft (1.53 m) of the pool, using a No. 8 AWG

bond wire. The Bond connection is located at the rear of the niche, see Figure 1.

e.

The wet niche is properly installed so the top edge of the underwater light's lens is at least 18 in

(45.7 cm) - (CANADA: 600 mm max to the centerline of the lens), below the surface of the water in the pool,
see Figure 1. Also, the face ring PILOT SCREW must be at the 12 o'clock position.

f.

If non-metallic conduit is used, a No. 8 AWG bonding/grounding wire must be installed through the conduit

from the Junction Box to the bonding/grounding lug inside the niche. Seal the wire/lug connection with a
listed sealant to protect the connection from possible pool water corrosion. See Figure 1. Note: Use only
Pentair wet niches to insure proper bonding and grounding connections.

     

 2. To be certain that the pool’s electrical system meets all applicable requirements, the electrician should

also consult the local building department.

3. Position Junction Box to meet National Electrical Code (NEC) requirements and to prevent hazard to personnel.

4. The center conduit hub is provided with a strain relief for a cord size up to a 10/3 AWG cord. Use underwater lights

with water resistant cord only.

5. Three equipment grounding terminals are provided for internal grounding suitable for #16 AWG to #10 AWG wire.

One pressure wire grounding terminal is provided for a #8 AWG insulated copper bonding wire.

6. Install the Junction Box gasket between the Junction Box base and cover. Replace gasket if worn or damaged (P/N

79300600).

7. Plug any unused conduit hubs with the conduit plugs provided.

Section  I. INSTALLING A JUNCTION BOX DURING NEW POOL CONSTRUCTION.

A. THE FOLLOWING PREPARATORY STEPS MUST BE COMPLETED BY THE CERTIFIED ELECTRICIAN

BEFORE LIGHT IS INSTALLED - SEE FIGURE 1.

1. Ensure that the electrical system of your pool conforms with all requirements of the National Electrical Code (NEC),

and all local codes and ordinances. A licensed or certified electrician must install the electrical system to meet or
exceed those requirements before the Junction Box is installed. Some of the NEC requirements are listed below.

8" min. (20.3 cm) from

To GFCI, Circuit
Breaker and
Power Source..

#8 AWG Ground
Connector bonded
to rebar..

Rigid
Conduit

48" min.

48" min.

(122 cm) min.

(122 cm) min.

4" (10.2 cm) min.

4" (10.2 cm) min.

Pilot Screw at Top.

Coil 4 (four) feet of light
cable around fixture..

bottom of Junction Box or Low

Voltage Transformer to the max.

water level of pool.

18” (42.72 cm ) min. from Water

Line to top of lens.

JUNCTION BOX

        P/N 98743900 Rev. E 7/2012

2

Figure 1.

Summary of Contents for JB 750

Page 1: ...19 566 8000 Customer Support 800 831 7133 10951 W Los Angeles Ave Moorpark CA 93021 USA 805 553 5000 800 831 7133 Part Number Description 78310500 Junction Box Polycarbonate Cover Brass Base 1 2 in po...

Page 2: ...possible pool water corrosion See Figure 1 Note Use only Pentair wet niches to insure proper bonding and grounding connections 2 To be certain that the pool s electrical system meets all applicable r...

Page 3: ...siga los instructivos espec ficos abajo Secci n I Instalaci n de una caja de empalmes durante la construcci n de una piscina nueva A LOS SIGUIENTES PASOS DE PREPARACI N TIENE QUE HABERSE COMPLETADO PO...

Page 4: ...de conexi n del conducto central esta provista de un desahogo de tensi n para un cord n el ctrico de hasta un tama o 10 3 AWG 3 x 2 6 mm Utilice luces que se puedan usar debajo del agua cenicamente co...

Page 5: ...d rivation lors de la construction d une nouvelle piscine A L lectricien devra proc der aux pr paratifs suivants avant d installer l appareil d clairage cf figure 1 1 S assurer d abord que le circuit...

Page 6: ...un serre cable pour cordon de calibre allant jusqu 10 3 AWG 3 x 2 6 mm maximum Pour les lampes submerg es n utiliser que des cordons imperm ables 1 eau 5 Trois prises de terre industrielles pour la c...

Page 7: ...nate bierta de la caja de conexiones con la junta 79300600 Caja de empalmes empaque de la caja de empalmes 79301800 Caja de empalmes Tornillo kit de 13mm 1 2 po 79301900 Caja de empalmes Tornillo kit...

Page 8: ...ly noted names and brands of third parties that may be used in this document are not used to indicate an affiliation or endorsement between the owners of these names and brands and Pentair Water Pool...

Reviews: