background image

300 mm mini

1m = OK

300 mm mini

1m OK

300 mm mini

 X

 Y

IVTP-1M-LT / IVTP-2M-LT / IVTP-3M-LT / IVTP-4M-LT :
X : 1200 mm  Y : 650 mm  
IVTP-5M-LT / IVTP-6M-LT:
X : 1300 mm  Y : 700 mm  

3m

IVTP-7M-LT / IVTP-8T-LT:
X : 1400 mm  Y : 750 mm  

4

INSTALLATION (SITE, TYPE OF SUPPORT, NECESSARY SPACE)

 –Install the HP outdoors at more than 2 metres from the pool, as per applicable laws (NF C 15 100).
 –Place the HP on the provided vibration absorbers on a surface that is stable, solid (able to bear the weight of the device) and level (prepare a concrete base if 

necessary). 

 –Maintain 1 m (30 cm minimum) of open space in front of the vertical air intake grids (behind and on the side of the HP) and 3 m at the outlet of the fan (in front) 

of open space without any obstacles.

 –Prepare sufficient space around the HP for maintenance operations.
 –Prepare a water evacuation system close to the HP to protect the installation zone.
 –Keep the HP out of the reach of children, insofar as possible.

The HP should never be installed:

 –in an area covered by sprinkling systems, or subject to spray or running water or mud (close to a road, take into account the effects of wind),
 –under a tree,
 –close to a source of heat or of flammable gas,
 –in an area where it would be exposed to oil, flammable gases, corrosive products, and compounds containing sulphur,
 –close to equipment operating at high frequencies,
 –in a place where snow is likely to accumulate,
 –in a place where it could be flooded by the condensates produced by the device as it operates,
 –on a surface that could transfer the vibrations to the house. 

Advice: dampen the possible noise nuisance caused by your HP.

 –Do not install it close to or underneath a window.
 –Do not direct the outlet of the fan towards your neighbours’ property.
 –Do not direct the fan outlet (cold air) towards the swimming pool.
 –Install it in an open area (sound waves bounce off surfaces). 
 –Install a sound barrier around the HP, making sure to maintain the required distances.
 –Install 50 cm of PVC piping at the water inlet and outlet of the HP. 

To improve its performance, it is recommended to insulate the piping between the HP and the swimming pool, especially if the distance is significant.

Space to maintain around the HP:

Provided skid 

if screen (option)

Minimum dimensions of the concrete slab

The HP must be installed and maintained on a fixed and solid basis, with the skids placed under the 

feet.

 

For concrete, use adapted ø8 mm lag screws fitted with washers to prevent any loosening.

 

For wood, use adapted ø8 mm hexagon head screws fitted with locking washers to prevent any 

loosening.

Summary of Contents for INVERTEMP IVTP-1M-LT

Page 1: ...CTIONS PLEASE READ AND FOLLOW ALL THE INSTRUCTIONS KEEP THESE INSTRUCTIONS PENTAIR AQUATIC SYSTEMS Rev 12 2021 Download the manual available in EN FR NL DE IT ES PT on www pentairpooleurope com EN IVT...

Page 2: ...LT Max power consumption 2 7 kW Weight 43 kg Product IVTP 8T LT Max power consumption 5 4 kW Weight 88 kg Processing by individuals of electronic appliances reaching the end of their lifespan The cros...

Page 3: ...ere injuries and even death Do not touch the fan or the moving parts and do not insert objects or your fingers close to the moving parts when the device is operating Moving parts can cause severe inju...

Page 4: ...2 98 29 9 dB a C 25 A 3G 6 mm 86 kg 24 2 kW 6 5 4 24 2 7 8 kW 10 8 5 4 16 3 7 8 kW 10 8 8 3 22 8 kW 4 5 4 2 22 8 8 1 kW 6 5 4 2 12 5 8 1 kW 6 5 5 6 12 11 kW 2 81 30 7 dB a C 16 A 5G 2 5mm2 86 kg 27 8...

Page 5: ...k that the pressure reading on the pressure gauge is equal to the pressure mentioned on the box depending on the measured outdoor temperature as different values might indicate a leak The HP should al...

Page 6: ...an area where it would be exposed to oil flammable gases corrosive products and compounds containing sulphur close to equipment operating at high frequencies in a place where snow is likely to accumul...

Page 7: ...n order blue water in red water out A bypass must be installed to facilitate work on the HP Before connecting the PVC pipes to the HP make sure the circuit is clean of any work residue stone soil etc...

Page 8: ...in force in the country where the system is installed Crimping the electric cables on appropriate terminals lugs for the diameter of the selected cable before connecting to the HP is recommended The...

Page 9: ...power supply remote control RS 485 as an option Note your HP can be controlled through a dry contact switch or the Pentair RS 485 bus 1 Remove the access hatch by unscrewing the two screws 2 Use the...

Page 10: ...iltration pump Indicative colour Indicative colour Indicative colour Phase Neutral Earthing Phase Yellow Green Black Phase Phase Neutral Earthing Inlet general power supply 230 V 50Hz Dry contact inpu...

Page 11: ...d intermediate circuit breaker properly insulated and connected to the earthing connection The conditions of installation and use described above have all been met The outdoor temperature is between 0...

Page 12: ...essure in the recommended range When stopped the temperature reading should be close to the temperature of the swimming pool water If the hand shows 0 the device should not be used contact your distri...

Page 13: ...ower and sound level automatically adjust depending on the external temperature and the temperature of your pool water BOOST heating or cooling mode maximum HP power The HP can vary the component spee...

Page 14: ...ctronic card in the device Sensor error water inlet Check that the sensor in question is correct ly connected Sensor error water outlet Sensor error evaporator Sensor error compressor outlet Sensor er...

Page 15: ...an account and log in Follow the account creation instructions 3 Add the heat pump 3 1 Click Add 3 2 Select Large device 3 3 Select Smart Heat Pump BLE WiFi 4 Input the Wi Fi 4 3 Select the desired n...

Page 16: ...er household products might damage the surface of the casing and change its properties The evaporator at the rear of the HP can be cleaned carefully using a soft brush vacuum cleaner just a soft brush...

Page 17: ...AMS Reactor Terminal strip 2 Terminal strip 2 Terminal strip 2 Towards the pump 1kW Dry contact Heating resistance of the evaporator Heating resistance of the compressor Reducer Flow detector Wired co...

Page 18: ...OUT1 OUT3 OUT4 OUT5 OUT6 OUT7 OUT8 OUT9 OUT2 OUT10 OUT11 OUT12 OUT13 L EGND N LP HP COM T1 T2 T3 T4 T5 T6 T7 CN2 t t t t t t E VALVE 3 E VAL 2 5 Heating resistance of the compressor PCB N Terminal st...

Page 19: ...grid of the fan 2 Front panel 3 Fan propeller 4 Fan motor 5 Motor support 6 Frame 7 Left panel 8 Board 1 connector 9 Modbus board 10 Electronic board 11 Cable channel 12 Electric casing 13 Cover for...

Page 20: ...1004 LAUSANNE Switzerland Copyright Limited license unless expressly authorised herein no part of the content of the present document can be reproduced in any form or by any means without the prior wr...

Reviews: