ELECTRICAL CONNECTIONS :
- As the HP is installed outdoors, the cable must pass through a protection sheath provided for that purpose. The power supply of the HP must be provided
with a protection system according to the applicable law.
- The electric cables must be buried at a depth of 50 cm (85 cm under a road or path) in an electric sheath (ringed and red). When a buried sheathed cable
intersects with another cable or a duct (water, gas...), the distance between the two must be greater than 20 cm.
Electrical connections (power supply, remote control (RS-485) as an option)
Note: your HP can be controlled through a dry contact (switch) or the Pentair RS-485 bus.
1: Remove the access hatch by unscrewing the two screws
2: Use the existing cable pullers to pull each cable of a suitable cross section (see the diagram below)
into the free strain relief bushing (2.1 for the supply, 2.2 for the switch / RS-485).
3: Lead the cable up to the respective terminal and tightly secure the cable clamp. Pull on the cable to check that it does not slip.
4: Connect the supply (3 strands for single phase, 5 strands for three phase) in accordance with the diagrams below.
5: Connect the switch or BUS RS-485 in accordance with the diagram below
6: Replace and screw on the hatch again