INSTALLATION AND OPERATING INSTRUCTIONS  PRECISION

®

 FILTER CLEANING SYSTEM CONTROLS

MECHANICAL 

The Precision may be supplied as PCB only, in 316 stainless steel IP65 (Nema 4) enclosures, or in painted steel IP65 (Nema 4) 
enclosures. 

General.

• 

Install Precision in areas of minimal vibration. 

• 

Install in an area free from high electrical noise or interference. 

• 

Install in an area where there is low risk of impact to the Precision. 

• 

The Precision will operate in ambient temperatures of 70

°

C (158

°

F). At temperatures higher than this the display may become 

difficult to read and the high temperature alarm will activate. Cooling should be provided if the Precision is to be installed in 
conditions with ambient temperatures of 70

°

C (158

°

F) or higher. 

P2.Enhanced.Demand.Mode.

• 

Ensure pneumatic sensing lines are kept as short as possible to minimise pressure losses. 

• 

Ensure pneumatic sensing lines are free from blockages, kinks or leaks. 

Installations.where.PCB.only.has.been.supplied.

• 

Ensure that installation is made into enclosures chosen with due consideration of the nature of the location, and that the 
boards are protected from moisture, heat above 70

°

C (158

°

F), dust, and chemical attack. 

• 

Ensure a common earth connection is present for all conductive material within immediate proximity to the device being 
powered, e.g. a common earth connection between the baseboard and mounting bracket, enclosure, etc. Please follow all 
local electrical standards. 

ELECTRICAL INSTALLATION 

Warnings:.

• 

Electrical installation to be undertaken by suitably qualified technicians. 

• 

Ensure that mains power has been isolated before conducting any work on the Precision. 

Connecting.power.to.the.Precision.

Applying power to the AC/DC and AC/AC Precision motherboard (AC Voltage models): 

• 

Ensure input voltage is 110 or 240 V AC (

+

/

 10%), 50/60 Hz. 

• 

Ensure power supply is not affected by high load or noisy electrical machinery such as fans, which may cause unreliable 
system operation. 

• 

Connect Earth, Active and Neutral supply to their respective terminals (ref. Figures 2 and 5, item 10). 

Applying power to the DC/DC Precision motherboard (DC Voltage models): 

• 

Ensure input voltage is 24 to 48 V DC (

+

/

 10%).

• 

Ensure power supply is not affected by high load or noisy electrical machinery such as fans, which may cause unreliable 
system operation. 

• 

Connect Earth, Positive and Negative supply to their respective terminals (ref. Figure 2, item 10). 

Surge.Protection.and.Earthing.

• 

Goyen Controls recommends the use of a Metal Oxide Varistor (MOV)-based surge protection device between the supply 
voltage and the Precision. Clamping voltage 

=

 275 V RMS (approx.), Energy Absorption 

=

 175 joules (approx.). 

• 

Ensure that when using a metal enclosure, both lid and box are connected to the supply earth. 

Connection.of.solenoid.valves.and.expansion.cards.to.Precision.outputs.

Please refer to the system wiring diagrams (Figures 8–11) on pages 8–11. 

INSTALLATION 

GENERAL 

Summary of Contents for Goyen Precision Deine-007

Page 1: ...PENTAIR CLEAN AIR SYSTEMS FILTER CLEANING SYSTEM CONTROLS PRECISION INSTALLATION AND OPERATING INSTRUCTIONS...

Page 2: ...ontrol 15 P2 Enhanced Demand Control 16 Messages and Alarms 18 Messages 18 Troubleshooting 20 General Startup 20 Operational 21 P MOD Modbus Communications 21 Precision System Specifications 22 Instal...

Page 3: ...isplay units kPa Demand cleaning by limits default High dP Low dP 1 0 kPa 0 5 kPa Demand cleaning by bandwidth High dP band 1 0 kPa 40 Alarm delay s 0 High dP alarm 2 0 kPa Precoating None Pattern cle...

Page 4: ...all push in contacts Figure 1 P1 Interface and Controller Top View 4 5 3 22 6 1 2 7 8 9 23 4 5 Figure 2 Controller Front View 7 12 11 20 10 DIRTY CLEAN 21 Note Controller assemblies in Figures 1 and 2...

Page 5: ...card optional 9 P CTX I O card optional 10 Power in 11 Expansion card connection 12 Fan contacts 13 PS C compact expansion card 10 output 14 Expansion card contacts 15 Solenoid terminals and LEDs 16...

Page 6: ...between the baseboard and mounting bracket enclosure etc Please follow all local electrical standards ELECTRICAL INSTALLATION Warnings Electrical installation to be undertaken by suitably qualified te...

Page 7: ...s are required for power supply to the solenoids plus drain Note that solenoid power is provided by this connection no additional external power is required Communication between baseboard and AC outp...

Page 8: ...NSTALLATION AND OPERATING INSTRUCTIONS PRECISION FILTER CLEANING SYSTEM CONTROLS Figure 8 Wiring Diagram for the AC DC and DC DC Baseboard with P CTX CTX Card P MOD Modbus Expansion Cards and Tube Cle...

Page 9: ...09 INSTALLATION AND OPERATING INSTRUCTIONS PRECISION FILTER CLEANING SYSTEM CONTROLS Figure 9 Wiring Diagram for the AC AC Baseboard with P CTX CTX Card P MOD Modbus P1 and P2 Option...

Page 10: ...10 INSTALLATION AND OPERATING INSTRUCTIONS PRECISION FILTER CLEANING SYSTEM CONTROLS Figure 10 Wiring Diagram for Compact Expansion Cards on the AC AC Baseboard...

Page 11: ...11 INSTALLATION AND OPERATING INSTRUCTIONS PRECISION FILTER CLEANING SYSTEM CONTROLS Figure 11 Wiring Diagram for Large Expansion Cards on the AC AC Baseboard...

Page 12: ...V DC 11 Purge valve for optional tube cleaner function only Output Common 24V DC 12 Demand Continuous switch Allows remote switching between continuous and demand control modes when P2 interface is fi...

Page 13: ...riggers the corresponding function 4 20mA Output The P CTX features a 4 20mA output that can be used for differential pressure reporting The output consists of a ground terminal 24V DC terminal and 0V...

Page 14: ...rms Line 2 Time to next pulse seconds Output ID of next pulse P2 Enhanced Demand Interface The P2 interface provides cleaning on demand basis i e in accordance with the differential pressure across th...

Page 15: ...age Precision may be run in one of five languages as listed above Reset Factory Defaults Puts all settings back to defaults set at time of manufacture On Time Sets electrical output duration between 3...

Page 16: ...Values 0 to 255 and OFF Setting to OFF takes the Precision off the network Run Returns the controller to operating mode P2 ENHANCED DEMAND CONTROL Menu Structure LEVEL 1 ENTRY LEVEL 2 MENU ITEM LEVEL...

Page 17: ...leaning pattern allows solenoids to be wired in a sequential manner to the controller outputs while pulsing in a non sequential manner Three options are available OFF SKIP 1 SKIP 2 With baseboard outp...

Page 18: ...hen in Demand Mode Pattern Cleaning xxxP2 Allows the controller to Off Skip 1 or Skip 2 outputs refer to cleaning patterns Alarm Delay xxx secP2 Delays high dP and Auxiliary Alarm for this amount of t...

Page 19: ...g in board has been identified as number xx where xx is 3 P CTX 4 P MOD Contact Goyen for replacement board Unknown Fault xx Firmware Error Contact Goyen Exception xx Contact Goyen with Exception cate...

Page 20: ...heck and ensure fit to interface and baseboard is secure Replace fuse Contact your supplier Some or all expansion cards are not detected on startup Cabling between expansion cards and the baseboard is...

Page 21: ...or another circuit breaker is not connected to the Precision the fan contact terminals should be open If the fan is connected to the baseboard check that the contacts at the fan are normally open typ...

Page 22: ...qual to input voltage Output current 2 4A 10 on baseboard 10 on each expansion card Maximum number of expansion 19 giving 200 outputs total cards connected Maximum distance between 100m expansion card...

Page 23: ...23 INSTALLATION AND OPERATING INSTRUCTIONS PRECISION FILTER CLEANING SYSTEM CONTROLS REGISTER DEFINITIONS P MOD MODBUS...

Page 24: ...24 INSTALLATION AND OPERATING INSTRUCTIONS PRECISION FILTER CLEANING SYSTEM CONTROLS REGISTER DEFINITIONS P MOD MODBUS...

Page 25: ...25 INSTALLATION AND OPERATING INSTRUCTIONS PRECISION FILTER CLEANING SYSTEM CONTROLS REGISTER DEFINITIONS P MOD MODBUS...

Page 26: ...26 INSTALLATION AND OPERATING INSTRUCTIONS PRECISION FILTER CLEANING SYSTEM CONTROLS REGISTER DEFINITIONS P MOD MODBUS...

Page 27: ...27 INSTALLATION AND OPERATING INSTRUCTIONS PRECISION FILTER CLEANING SYSTEM CONTROLS REGISTER DEFINITIONS P MOD MODBUS...

Page 28: ...Goyen Precision Inst Ops Manual Rev02 11 14 CLEANAIRSYSTEMS COM 2014 Pentair Clean Air Systems reserves the right to change product designs and specifications without notice...

Reviews: