background image

19

INSTALLATION AND OPERATING INSTRUCTIONS  PRECISION

®

 FILTER CLEANING SYSTEM CONTROLS

Alarm.Messages

DISPLAY

DESCRIPTION

Coil OC Fail – xx:yy*

Coil yy on Slave xx has failed Open Circuit – Replace coil.

Coil CC Fail – xx.yy*

Coil yy on Slave xx has failed Closed Circuit – Replace coil.

Low Coil Voltage – xx.yy

Voltage outside the recommended voltage is being delivered to the coil yy on Slave xx or to the 
baseboard – check connections.

Slave Removed – xx

Slave xx has been lost since power-up – Check connections.

Over Temperature – Slowed

Power Supply is warm. Off Time has been increased to allow the Power Supply to return to normal.

Over Temperature – Stopped

Power Supply is hot. Controller has ceased to function to allow the Power Supply to return to normal 
temperature. The controller will then automatically operate.

Power Supply Low

Power Supply voltage is below the minimum voltage. Once voltage is within operating range, the 
controller will automatically operate normally.

Stop (Over Temp)

Power Supply is hot. Controller has ceased to function to allow the Power Supply to return to normal 
temperature. The controller will then automatically operate.

Bad MOD board xx

A faulty ‘plug-in’ board has been identified as number xx where xx is:
3.  P-CTX
4.  P-MOD
Contact Goyen for replacement board.

Unknown Fault xx

Firmware Error – Contact Goyen.

Exception # xx

Contact Goyen with Exception category # and Exception number xx – Contact Goyen.
1.  P2 interface Board requires calibration
2.  Could not communicate to baseboard slave (may indicate problem with external slave bus, but most 

likely a problem with the micro or the RS485 comms on the baseboard;  other options are a fault on 
the micro on the P1/2 interface or possibly the 50-way cable).

3.  3.3 V rail is low (

<

 3 V) – this message indicates a fault in the 3V3 supply on the baseboard.

Aux. Alarm

Auxiliary Alarm is present (P-CTX must be present).

Low Header P

Insufficient compressed-air pressure exists in header. Solenoid operation is ceased until pressure is at 
acceptable levels once again (P-CTX must be fitted).

Service Alarm 100 000 cycles

100 000 complete cleaning cycles have been completed – Check control system parameters.

Service Alarm 500 000 cycles

500 000 complete cleaning cycles have been completed – Check condition of filter elements.

Service Alarm 950 000 cycles

950 000 complete cleaning cycles have been completed – Replace kits in valves.

*   In the case of solenoid failure, all other solenoids will continue to operate. Alarm will be automatically cancelled on connection of a good 

solenoid to the output in question.

Summary of Contents for Goyen Precision Deine-007

Page 1: ...PENTAIR CLEAN AIR SYSTEMS FILTER CLEANING SYSTEM CONTROLS PRECISION INSTALLATION AND OPERATING INSTRUCTIONS...

Page 2: ...ontrol 15 P2 Enhanced Demand Control 16 Messages and Alarms 18 Messages 18 Troubleshooting 20 General Startup 20 Operational 21 P MOD Modbus Communications 21 Precision System Specifications 22 Instal...

Page 3: ...isplay units kPa Demand cleaning by limits default High dP Low dP 1 0 kPa 0 5 kPa Demand cleaning by bandwidth High dP band 1 0 kPa 40 Alarm delay s 0 High dP alarm 2 0 kPa Precoating None Pattern cle...

Page 4: ...all push in contacts Figure 1 P1 Interface and Controller Top View 4 5 3 22 6 1 2 7 8 9 23 4 5 Figure 2 Controller Front View 7 12 11 20 10 DIRTY CLEAN 21 Note Controller assemblies in Figures 1 and 2...

Page 5: ...card optional 9 P CTX I O card optional 10 Power in 11 Expansion card connection 12 Fan contacts 13 PS C compact expansion card 10 output 14 Expansion card contacts 15 Solenoid terminals and LEDs 16...

Page 6: ...between the baseboard and mounting bracket enclosure etc Please follow all local electrical standards ELECTRICAL INSTALLATION Warnings Electrical installation to be undertaken by suitably qualified te...

Page 7: ...s are required for power supply to the solenoids plus drain Note that solenoid power is provided by this connection no additional external power is required Communication between baseboard and AC outp...

Page 8: ...NSTALLATION AND OPERATING INSTRUCTIONS PRECISION FILTER CLEANING SYSTEM CONTROLS Figure 8 Wiring Diagram for the AC DC and DC DC Baseboard with P CTX CTX Card P MOD Modbus Expansion Cards and Tube Cle...

Page 9: ...09 INSTALLATION AND OPERATING INSTRUCTIONS PRECISION FILTER CLEANING SYSTEM CONTROLS Figure 9 Wiring Diagram for the AC AC Baseboard with P CTX CTX Card P MOD Modbus P1 and P2 Option...

Page 10: ...10 INSTALLATION AND OPERATING INSTRUCTIONS PRECISION FILTER CLEANING SYSTEM CONTROLS Figure 10 Wiring Diagram for Compact Expansion Cards on the AC AC Baseboard...

Page 11: ...11 INSTALLATION AND OPERATING INSTRUCTIONS PRECISION FILTER CLEANING SYSTEM CONTROLS Figure 11 Wiring Diagram for Large Expansion Cards on the AC AC Baseboard...

Page 12: ...V DC 11 Purge valve for optional tube cleaner function only Output Common 24V DC 12 Demand Continuous switch Allows remote switching between continuous and demand control modes when P2 interface is fi...

Page 13: ...riggers the corresponding function 4 20mA Output The P CTX features a 4 20mA output that can be used for differential pressure reporting The output consists of a ground terminal 24V DC terminal and 0V...

Page 14: ...rms Line 2 Time to next pulse seconds Output ID of next pulse P2 Enhanced Demand Interface The P2 interface provides cleaning on demand basis i e in accordance with the differential pressure across th...

Page 15: ...age Precision may be run in one of five languages as listed above Reset Factory Defaults Puts all settings back to defaults set at time of manufacture On Time Sets electrical output duration between 3...

Page 16: ...Values 0 to 255 and OFF Setting to OFF takes the Precision off the network Run Returns the controller to operating mode P2 ENHANCED DEMAND CONTROL Menu Structure LEVEL 1 ENTRY LEVEL 2 MENU ITEM LEVEL...

Page 17: ...leaning pattern allows solenoids to be wired in a sequential manner to the controller outputs while pulsing in a non sequential manner Three options are available OFF SKIP 1 SKIP 2 With baseboard outp...

Page 18: ...hen in Demand Mode Pattern Cleaning xxxP2 Allows the controller to Off Skip 1 or Skip 2 outputs refer to cleaning patterns Alarm Delay xxx secP2 Delays high dP and Auxiliary Alarm for this amount of t...

Page 19: ...g in board has been identified as number xx where xx is 3 P CTX 4 P MOD Contact Goyen for replacement board Unknown Fault xx Firmware Error Contact Goyen Exception xx Contact Goyen with Exception cate...

Page 20: ...heck and ensure fit to interface and baseboard is secure Replace fuse Contact your supplier Some or all expansion cards are not detected on startup Cabling between expansion cards and the baseboard is...

Page 21: ...or another circuit breaker is not connected to the Precision the fan contact terminals should be open If the fan is connected to the baseboard check that the contacts at the fan are normally open typ...

Page 22: ...qual to input voltage Output current 2 4A 10 on baseboard 10 on each expansion card Maximum number of expansion 19 giving 200 outputs total cards connected Maximum distance between 100m expansion card...

Page 23: ...23 INSTALLATION AND OPERATING INSTRUCTIONS PRECISION FILTER CLEANING SYSTEM CONTROLS REGISTER DEFINITIONS P MOD MODBUS...

Page 24: ...24 INSTALLATION AND OPERATING INSTRUCTIONS PRECISION FILTER CLEANING SYSTEM CONTROLS REGISTER DEFINITIONS P MOD MODBUS...

Page 25: ...25 INSTALLATION AND OPERATING INSTRUCTIONS PRECISION FILTER CLEANING SYSTEM CONTROLS REGISTER DEFINITIONS P MOD MODBUS...

Page 26: ...26 INSTALLATION AND OPERATING INSTRUCTIONS PRECISION FILTER CLEANING SYSTEM CONTROLS REGISTER DEFINITIONS P MOD MODBUS...

Page 27: ...27 INSTALLATION AND OPERATING INSTRUCTIONS PRECISION FILTER CLEANING SYSTEM CONTROLS REGISTER DEFINITIONS P MOD MODBUS...

Page 28: ...Goyen Precision Inst Ops Manual Rev02 11 14 CLEANAIRSYSTEMS COM 2014 Pentair Clean Air Systems reserves the right to change product designs and specifications without notice...

Reviews: