background image

20

INSTALLATION AND OPERATING INSTRUCTIONS  PRECISION

®

 FILTER CLEANING SYSTEM CONTROLS

The Precision is programmed with system self-diagnostics. Most issues can be resolved by reference to the system messages 
and alarms present on the interface and listed in the previous section, ‘Messages and Alarms’. For issues which cannot be 
resolved in this way, refer to the table below or contact your system supplier. 

General/Startup.

SYMPTOM

CAUSE

RESOLUTION

System does not power up. Power LED 
remains off.

Power is not connected to the baseboard.
Power wiring is incorrect. 

Power supplied is below the minimum 
required to operate the controller.
Ribbon cable to P1 or P2 interface is loose. 

Blown fuse.
Defective on-board power supply or interface.

Check connection.
Check wiring to socket is in accordance with 
this manual.
Check power supply is within tolerance. 

Check and ensure fit to interface and 
baseboard is secure.
Replace fuse.
Contact your supplier.

Some or all expansion cards are not detected 
on startup.

Cabling between expansion cards and the 
baseboard is incorrect.
Broken cabling between expansion cards and 
the baseboard.
Damaged fuse on expansion card or 
baseboard.

Check connections are in accordance with 
this manual.
Replace cable. 

Replace fuse. 

Some or all connected solenoids are not 
detected on startup.

Cabling between expansion cards and the 
baseboard is incorrect.
Broken cabling between expansion cards and 
the baseboard.
The common terminals between each bank 
of solenoids (or between solenoids) are not 
linked or returned to the common terminal 
on the relevant baseboard or expansion card.
The solenoid active terminal is not properly 
linked to its relevant system output terminal.
Damaged fuse on expansion card or 
baseboard.

Check connections are in accordance with 
this manual.
Replace the cable. 

Ensure commons are linked. 
 
 

Check connections and repair if necessary. 

Replace fuse.

TROUBLESHOOTING 

Summary of Contents for Goyen Precision Deine-007

Page 1: ...PENTAIR CLEAN AIR SYSTEMS FILTER CLEANING SYSTEM CONTROLS PRECISION INSTALLATION AND OPERATING INSTRUCTIONS...

Page 2: ...ontrol 15 P2 Enhanced Demand Control 16 Messages and Alarms 18 Messages 18 Troubleshooting 20 General Startup 20 Operational 21 P MOD Modbus Communications 21 Precision System Specifications 22 Instal...

Page 3: ...isplay units kPa Demand cleaning by limits default High dP Low dP 1 0 kPa 0 5 kPa Demand cleaning by bandwidth High dP band 1 0 kPa 40 Alarm delay s 0 High dP alarm 2 0 kPa Precoating None Pattern cle...

Page 4: ...all push in contacts Figure 1 P1 Interface and Controller Top View 4 5 3 22 6 1 2 7 8 9 23 4 5 Figure 2 Controller Front View 7 12 11 20 10 DIRTY CLEAN 21 Note Controller assemblies in Figures 1 and 2...

Page 5: ...card optional 9 P CTX I O card optional 10 Power in 11 Expansion card connection 12 Fan contacts 13 PS C compact expansion card 10 output 14 Expansion card contacts 15 Solenoid terminals and LEDs 16...

Page 6: ...between the baseboard and mounting bracket enclosure etc Please follow all local electrical standards ELECTRICAL INSTALLATION Warnings Electrical installation to be undertaken by suitably qualified te...

Page 7: ...s are required for power supply to the solenoids plus drain Note that solenoid power is provided by this connection no additional external power is required Communication between baseboard and AC outp...

Page 8: ...NSTALLATION AND OPERATING INSTRUCTIONS PRECISION FILTER CLEANING SYSTEM CONTROLS Figure 8 Wiring Diagram for the AC DC and DC DC Baseboard with P CTX CTX Card P MOD Modbus Expansion Cards and Tube Cle...

Page 9: ...09 INSTALLATION AND OPERATING INSTRUCTIONS PRECISION FILTER CLEANING SYSTEM CONTROLS Figure 9 Wiring Diagram for the AC AC Baseboard with P CTX CTX Card P MOD Modbus P1 and P2 Option...

Page 10: ...10 INSTALLATION AND OPERATING INSTRUCTIONS PRECISION FILTER CLEANING SYSTEM CONTROLS Figure 10 Wiring Diagram for Compact Expansion Cards on the AC AC Baseboard...

Page 11: ...11 INSTALLATION AND OPERATING INSTRUCTIONS PRECISION FILTER CLEANING SYSTEM CONTROLS Figure 11 Wiring Diagram for Large Expansion Cards on the AC AC Baseboard...

Page 12: ...V DC 11 Purge valve for optional tube cleaner function only Output Common 24V DC 12 Demand Continuous switch Allows remote switching between continuous and demand control modes when P2 interface is fi...

Page 13: ...riggers the corresponding function 4 20mA Output The P CTX features a 4 20mA output that can be used for differential pressure reporting The output consists of a ground terminal 24V DC terminal and 0V...

Page 14: ...rms Line 2 Time to next pulse seconds Output ID of next pulse P2 Enhanced Demand Interface The P2 interface provides cleaning on demand basis i e in accordance with the differential pressure across th...

Page 15: ...age Precision may be run in one of five languages as listed above Reset Factory Defaults Puts all settings back to defaults set at time of manufacture On Time Sets electrical output duration between 3...

Page 16: ...Values 0 to 255 and OFF Setting to OFF takes the Precision off the network Run Returns the controller to operating mode P2 ENHANCED DEMAND CONTROL Menu Structure LEVEL 1 ENTRY LEVEL 2 MENU ITEM LEVEL...

Page 17: ...leaning pattern allows solenoids to be wired in a sequential manner to the controller outputs while pulsing in a non sequential manner Three options are available OFF SKIP 1 SKIP 2 With baseboard outp...

Page 18: ...hen in Demand Mode Pattern Cleaning xxxP2 Allows the controller to Off Skip 1 or Skip 2 outputs refer to cleaning patterns Alarm Delay xxx secP2 Delays high dP and Auxiliary Alarm for this amount of t...

Page 19: ...g in board has been identified as number xx where xx is 3 P CTX 4 P MOD Contact Goyen for replacement board Unknown Fault xx Firmware Error Contact Goyen Exception xx Contact Goyen with Exception cate...

Page 20: ...heck and ensure fit to interface and baseboard is secure Replace fuse Contact your supplier Some or all expansion cards are not detected on startup Cabling between expansion cards and the baseboard is...

Page 21: ...or another circuit breaker is not connected to the Precision the fan contact terminals should be open If the fan is connected to the baseboard check that the contacts at the fan are normally open typ...

Page 22: ...qual to input voltage Output current 2 4A 10 on baseboard 10 on each expansion card Maximum number of expansion 19 giving 200 outputs total cards connected Maximum distance between 100m expansion card...

Page 23: ...23 INSTALLATION AND OPERATING INSTRUCTIONS PRECISION FILTER CLEANING SYSTEM CONTROLS REGISTER DEFINITIONS P MOD MODBUS...

Page 24: ...24 INSTALLATION AND OPERATING INSTRUCTIONS PRECISION FILTER CLEANING SYSTEM CONTROLS REGISTER DEFINITIONS P MOD MODBUS...

Page 25: ...25 INSTALLATION AND OPERATING INSTRUCTIONS PRECISION FILTER CLEANING SYSTEM CONTROLS REGISTER DEFINITIONS P MOD MODBUS...

Page 26: ...26 INSTALLATION AND OPERATING INSTRUCTIONS PRECISION FILTER CLEANING SYSTEM CONTROLS REGISTER DEFINITIONS P MOD MODBUS...

Page 27: ...27 INSTALLATION AND OPERATING INSTRUCTIONS PRECISION FILTER CLEANING SYSTEM CONTROLS REGISTER DEFINITIONS P MOD MODBUS...

Page 28: ...Goyen Precision Inst Ops Manual Rev02 11 14 CLEANAIRSYSTEMS COM 2014 Pentair Clean Air Systems reserves the right to change product designs and specifications without notice...

Reviews: