13. Regeneration Cycle Step Times
Press the Extra Cycle button. Use this display to set the
Regeneration Cycle Step Times. The different regeneration
cycles are listed in sequence based on the valve type selected
for the system, and are identified by an abbreviation in the upper
left-hand corner of the screen. The abbreviations used are listed
below. If the system has been configured with the “OTHER” valve
type, the regeneration cycles will be identified as R1, R2, R3,
R4, R5, and R6. Each cycle step time can be set from 0 to 199
minutes, or “OFF.” Setting a cycle step to “OFF” will disable all
of the following steps. Setting a cycle step time to 0 will cause
the control to skip that step during regeneration, but keeps the
following steps available. Use the Up and Down buttons to adjust
the value as needed. Press the Extra Cycle button to accept the
current setting and move to the next parameter.
Cycle Step
Abbreviation
BD
Brine Draw
BF
Brine Fill
BW
Backwash
RR
Rapid Rinse
SV
Service
Range: 0-199 minutes
14. Day of Week Settings
Press the Extra Cycle button. Use this display to set the
regeneration schedule for a system configured as a Day of Week
control. The different days of the week are identified as D1,
D2, D3, D4, D5, D6, and D7 in the upper left-hand corner of the
display. Set the value to “ON” to schedule a regeneration or “OFF”
to skip regeneration for each day. Use the Up and Down buttons
to adjust the setting as needed. Press the Extra Cycle button
to accept the setting and move to the next day. Note that the
control requires at least one day to be set to “ON.” If all 7 days are
set to “OFF”, the unit will return to Day One until one or more days
are set to “ON.”
15. Current Day (Display Code CD)
Press the Extra Cycle button. Use this display to set the current
day on systems that have been configured as Day of Week
controls. This setting is identified by “CD” in the upper left-hand
corner of the screen. Use the Up and Down buttons to select
from Day 1 through Day 7.
MASTER PROGRAMMING MODE
CONTINUED
16. Flow Meter Type (Display Code FM)
Press the Extra Cycle button. Use this display to set the type
of flow meter connected to the control. This option setting is
identified by “FM” in the upper left-hand corner of the screen.
Use the Up and Down buttons to select one of the seven
available settings.
t0.7
Fleck 3/4 inch Turbine Meter
P0.7
Fleck 3/4 inch Paddle Wheel Meter
t1.0
Fleck 1 inch Turbine Meter
P1.0
Fleck 1 inch Paddle Wheel Meter
t1.5
Fleck 1-1/2 inch Turbine Meter
P1.5
Fleck 1-1/2 inch Paddle Wheel Meter
GEn
Generic/Other Meter
17. Meter Pulse Setting (Display Code K)
Press the Extra Cycle button. Use this display to specify the
meter pulse setting for a non-standard flow meter. This option
setting is identified by “K” in the upper left-hand corner of
the screen. Use the Up and Down buttons to enter the meter
constant in pulses per unit volume.
18.
Press the Extra Cycle button to save all settings and exit Master
Programming Mode.