ii
Note: Refer to page 3 where (parts index number) is shown
EasyTouch/IntelliTouch Control System Upgrade Kits Installation Guide
P/N 523455 Rev. A 10/2019
Contents
IMPORTANT WARNING AND SAFETY INSTRUCTIONS ...................................................................... ii-vi
OVERVIEW / SUMMARY
..................................................................................................................... 1-2
BOX CONTENTS
..................................................................................................................................... 3
REMOVING THE EXISTING OUTDOOR CONTROL PANEL
............................................................ 4
INSTALL THE NEW 4A AND 5A LOW VOLTAGE CIRCUIT BREAKERS AND SYSTEM
TRANSFORMER
.................................................................................................................................. 6-9
INSTALLING THE INTELLICENTER CONTROL SYSTEM OUTDOOR CONTROL PANEL
....... 10
CONNECTING AND CONFIGURING POOL AND SPA EQUIPMENT
.......................................... 10
INSTALLING THE WIRING LABEL ON THE ENCLOSURE FRONT DOOR
................................. 11
Note: INSTALLING THE WIRELESS ANTENNA KIT.
(See IntelliCenter Control System Installation Guide).
Customer Service
8 AM to 5.30 PM — Eastern and Pacific Times
Phone: (800) 831-7133
Fax: (800) 284-4151
Visit www.pentair.com
Technical Support
Sanford, North Carolina (8 A.M. to 8.30 PM ET)
Phone: (919) 566-8000
Fax: (919) 566-8920
Moorpark, California (8 A.M. to 5.30 PM PT)
Phone: (805) 553-5000 (Ext. 5591)
Fax: (805) 553-5515
CUSTOMER SERVICE / TECHNICAL SUPPORT
General Installation Information
1. All work must be performed by a licensed electrician, and must conform to all national, state, and local
codes.
2. Install to provide drainage of compartment for electrical components.
3. If this system is used to control underwater lighting fixtures, a ground-fault interrupter (GFCI) must be
provided for these fixtures. Conductors on the load side of the ground-fault circuit-interrupter shall not
occupy conduit, junction boxes or enclosures containing other conductors unless such conductors are
also protected by a ground-fault circuit-interrupter. Refer to local codes for details.
4. A terminal bar stamped is located inside the supply terminal box. To reduce the risk of electric
shock, this terminal must be connected to the grounding means provided in the electric supply service
panel with a continuous copper wire equivalent in size to the circuit conductors supplying this equipment
(no smaller than 12 AWG or 3.3 mm). The bonding lug(s) provided on this unit are intended to connect
a minimum of one No. 8 AWG for US installation and two No. 6 AWG for Canadian installations solid
copper conductor between this unit and any metal equipment, metal enclosures or electrical equipment,
metal water pipe, or conduit within 5 feet (1.5 m) of the unit.
5. The electrical supply for this product must include a suitably rated switch or circuit breaker to open all
ungrounded supply conductors to comply with in accordance with the current National Electrical Code
(NEC), NFPA 70 or the Canadian Electrical Code (CEC), CSA C22.1. All applicable local installation
codes and ordinances must also be adhered to. The disconnecting means must be readily accessible to
the tub occupant but installed at least 10 ft. (3.05 m) from the inside wall of the pool.
6. GAS HEATER: This automation control system is designed to supply high voltage (120 VAC / 240 VAC)
to a gas heater and override the thermostat in the heater’s control circuit. This automation control
system is intended to control gas heaters with a high temperature limit switch(s) safety circuit.