Pentair Biffi F02 Installation And Maintenance Instructions Manual Download Page 19

19

6.2.14 Blinker / Local selector configuration

Default configuration for Blinker / local 
selector relay is off (always open)
in Blinker configuration, during actuator 
movement the relay changes their status each 
500 msecs (Motor running function).
in local selector configuration (with local 
interface oM3 installed), the relay is close 
when oM3 switch is on reMote, while it is 
oPen when oM3 switch is on local.
to configure Blinker or local selector 
monitoring function (when oM3 is present):
• enter set up configuration: move switch sW3 

to position on (configuration function)

• Move switch sW4 to position 4
• Move switch sW6 to position 1 (Blinker) or 2 

(local selector)

• confirm by pushing enter pushbutton sW5
• When pushing sW5, the red leD switches on 

for confirmation

• exit set up configuration (move switch 

sW3 to position 1) or proceed with the next 
parameter

6.3 COnfiguratiOn Of the f02 By a 
pda / pC and ‘a Manager’ sOftWare

if one of the optional module oM1, oM9 or 
oM11 is installed on the f02 and this card 
features Bluetooth interface, the actuator 
configuration can be performed by means of 
the ‘a Manager’ software installed on the PDa 
or Pc.
only Blinker / local selector relay cannot be 
configured by means ‘a Manager’ software.
the relevant instruction and operating Manual 
is available with the ‘a Manager’ software.

Warning

The controls available via Bluetooth allow full 
actuator operability at a distance. Biffi will not 
accept any responsibility for damages or injuries 
caused by an improper use of your Bluetooth PDA.

6.4 hardWare COnfiguratiOn fOr 
MOnitOr reLay

the Monitor relay indicates the followings 
failures:
• loss of power
• stop by torque out of limits
• Direction failure
• temperature too high
• Position sensor failure
• local control panel with selector in local 

position

• Valve jammed
• Hardware malfunction
• alarm on the local control panel (if present)
• stroke failure

the Monitor relay contacts can be set as 
close or oPen by changing the welding of 
JuMPer J1 on logic board.
as a default setting, pins 2 and 3 are welded 
together, and the Monitor relay contact 
operates as follows:
- contact close in normal condition with relay 
energized, and oPen in case of malfunction 
(relay is de-energized).

in case of request, if contact must be oPen 
in normal condition and close in case of 
malfunction, the contact of JuMPer J1 must be 
modified welding pins 1 and 2 together.

Warning

Configuration of Monitor Relay by means 
JUMPER J1 is a hardware configuration. For this 
reason, to configure Monitor Relay is mandatory 
manage actuator without power supply.

Biffi 

f02 quarter-turn electric actuator

InstallatIon and MaIntenance InstructIons

Summary of Contents for Biffi F02

Page 1: ...to F02 are tested according to EN 21680 Noise level is less than 65 dB grade A at 1 m distance F02 electric actuators are designed in accordance with the applicable international rules and specificati...

Page 2: ...nt of Use of the actuator in contravention of local safety at work legislation Incorrect installation disregard or incorrect application of the instructions provided on the actuator nameplate and in t...

Page 3: ...ctuator label Figure 1B 1 4 2 1 ATEX label for application in hazardous areas A Manufacturer logo B Product model C Nominal output torque value D Product code E Serial number F Stroking time range G P...

Page 4: ...ation Control command open counter clockwise or clockwise rotation selectable on the logic board moves the valve to a completely or partially open position Control command closed clockwise or counter...

Page 5: ...from 24 to 48 V DC V AC 2 7 Options label A label is always provided with base actuators where optional modules will have to be checked out once they are installed after delivery at local organisatio...

Page 6: ...erproof they just prevent the entry of undesired objects during transport Biffi cannot accept responsibility for deterioration caused on site when the covers are removed 3 2 2 Storage for a brief peri...

Page 7: ...tuator onto the valve so that the shaft output drive enters the groove of the stem extension This coupling must take place without forcing and only with the weight of the actuator When the actuator ou...

Page 8: ...valve flange and the actuator coupling block Warning Never lift the valve actuator assembly without securing slings to both the valve and the actuator Never use the handwheel to lift the actuator Warn...

Page 9: ...staller s responsibility to select the most appropriate electric protection Figure 7 Setting of the mechanical stop Screw 1 Screw 2 4 6 Setting of the angular stroke mechanical stops It is important f...

Page 10: ...0 580 0 500 2000 8 53 14 50 6 80 3 200 2 520 1 150 1 000 14 00 7 00 3 220 2 530 1 120 0 980 6 100 9 50 4 60 1 900 1 550 0 760 0 670 9 30 4 50 1 920 1 540 0 720 0 620 4 180 7 00 3 40 1 550 1 240 0 600...

Page 11: ...rd Directive and specific Rules applying to the products Figure 9 Overview of the electrical connections Earth connection X 4 9 Removal of the terminal board enclosure Using a 5 mm Allen key loosen th...

Page 12: ...und Blinker local selector relay Output contacts Note 3 4 Optional module OM3 3 Contacts shown in intermediate position CLC1 CLC2 end of travel signaling in closing Contacts shown in intermediate posi...

Page 13: ...to physically separate the power from the signal terminal place the power clamps protection provided with the actuator on the power terminal once you have completed the power cable connection This wi...

Page 14: ...ortant In case the screws of the cover must be replaced SS Class A4 grade 80 screw must be used with minimum yield strength 600 N mm2 Warning Pay attention not to damage the joint surfaces of the cove...

Page 15: ...rried out by specifically qualified personnel for operations on powered electronic cards Important The actuators are set in the workshop with the following configuration default value CL limit switch...

Page 16: ...8 ON PUSH Opening speed 5 4 ON PUSH 6 5 6 ON PUSH 5 8 ON PUSH Closing torque 6 2 50 ON PUSH 9 6 5 75 ON PUSH 6 9 100 ON PUSH Opening torque 7 2 50 ON PUSH 9 7 5 75 ON PUSH 7 9 100 ON PUSH CW CCW 8 0...

Page 17: ...f the above condition is not respected the setup will not be successful and stroke limit error alarm will be signalized red LED blinking The red LED will continuously flash when the actuator is in set...

Page 18: ...et to operate with a 63 Nm or 125 Nm motor and a 250 Nm or 500 Nm motor respectively The difference is based on the technical characteristics of the electric motor itself Actuator model 063 Enter set...

Page 19: ...ftware The relevant Instruction and Operating Manual is available with the A Manager software Warning The controls available via Bluetooth allow full actuator operability at a distance Biffi will not...

Page 20: ...be required from Biffi please refer to the individual item number shown in Chapter 8 In case of malfunction in the mechanical electronic components in case of grease leaks through the seals or in case...

Page 21: ...ers or waste disposal companies Batteries Yes Yes Will require special treatment before disposal use specialist recyclers or waste disposal companies 8 Decommissioning 8 1 Disposal and recycling At th...

Page 22: ...erminal block 1 23 Worm shaft flange 1 24 Anti loosening washer UNI8842 J6 1 25 Base plate ISO 5211 F05 F07 1 26 Cover gasket 1 27 Dowel pin UNI EN 22338 1 28 Earth stud 1 29 Fixed anulus 1 30 Gasket...

Page 23: ...2 Terminal block 1 23 Worm shaft flange 1 24 Anti loosening washer UNI 8842 J6 1 25 Base plate ISO 5211 F07 F10 1 26 Cover gasket 1 27 Dowel pin UNI EN 22338 1 28 Earth stud 1 29 Fixed anulus 1 30 Gas...

Page 24: ...rminal block 1 24 Anti loosening washer UNI 8842 J6 2 25 Base plate ISO 5211 F07 F10 F12 1 26 Cover gasket 1 27 Dowel pin UNI EN 22338 1 28 Earth stud 1 29 Fixed anulus 1 30 Gasket 1 31 Indicator 1 32...

Page 25: ...rive assembly 1 23 Stopper 2 24 Terminal block 1 25 Anti loosening washer UNI 8842 J6 2 26 Base plate ISO 5211 F10 F12 1 27 Cover gasket 1 28 Dowel pin UNI EN 22338 1 29 Earth stud 1 30 Fixed anulus 1...

Page 26: ...minal block 1 23 Terminal cover gasket 2 24 Anti loosening washer UNI 8842 J6 2 25 Base plate ISO 5211 F10 F14 1 26 Cover gasket 1 27 Dowel pin UNI EN 22338 1 28 Earth stud 1 29 Fixed anulus 1 30 Hous...

Page 27: ...10 Base housing 1 11 Base plate F12 F16 EN ISO 5211 1 12 Bearing support 1 13 Bushing 2 14 Bushing 1 15 Bushing 1 16 Bushing 1 17 Dowel pin UNI EN 22338 D 8x20 type B 4 18 Gasket 1 19 Hex head screw U...

Page 28: ...EN 24017 M16x30 2 30 Indicator 1 31 Indicator shaft 1 32 Manual worm shaft 1 33 Motor pinion 1 34 O ring Di 13 94 W 2 62 1 35 O ring Di 25 12 W 1 78 1 36 O ring Di 6 07 W 1 78 1 37 O ring Di 82 22 W 2...

Reviews: