TECHNICAL DATA
Weight
depending on type 4-6 kg
Protection category
IP 44
Operating voltage
1/N/PE x 230 V, 50 Hz
3/N/PE x 400 V, 50 Hz
Power consumption of control unit
approx. 8 W
Control fuse
F1 fine-wire fuse 5x20 mm, 6.3 A T/MT; EN 60127-2-5, DIN 41571-2
Fuse alternating current output
F2 fine-wire fuse 5x20 mm, 2.0 A T/MT; EN 60127-2-5, DIN 41571-2
High water alarm emergency supply (optional)
9 V NiMH rechargeable batteries
Terminals
2.5 mm² push-in terminals on the PCB
4 mm² push-in terminals on top hat rail
Screw terminals 4 mm² at the motor protection relay/motor contactor
Screw terminal 6/10 mm² for potential equalisation
Motor protection
Motor protection switch on top hat rail / motor protection relay on
contactor
Monitoring of rotational field / phase failure
Error message given for anti-clockwise rotating field and if there is a
power phase failure
Temperature range in operation
-20 … 50°C
Temperature range in storage
-20 … 70°C
Air humidity
0 to 90% RH, with no condensation
Compli potentiometer
5 kOhm
Level switch, input
24 V, 4 mA
High water alarm, input
12 V, 7 mA
Powered alarm relay
230 V AC, max 2 A (AC1)
Potential-free alarm relay
5A, 250 V AC
Method used for measuring current
via current transformer and A/D converter
Current transformer
0 - 20 A, ± 10%