MAINTENANCE INSTRUCTIONS
51
PARAMETER
P20
–
CENTRAL
HEATING
MAXIMUM
SET
POINT
This parameter is used to set the central heating maximum temperature the user may increase to. The
user will be unable to increase the maximum heating temperature above this set number.
min = 104°F
max = 194°F
PARAMETER
P21
–
D.H.W.
MAXIMUM
SET
POINT
This parameter is used to set the D.H.W maximum temperature the user may increase to. The user
will be unable to increase the maximum D.H.W. temperature above this set number.
min = 113°F
max = 167°F
PARAMETER
P22
–
∆T
SET
POINT
T°
FLOW
/
T°
RETURN
-
(not applicable)
Value set to “32” – Do not change. If set to anything other than “32”, Error “E15” will appear.
PARAMETER
P23
–
(not applicable)
PARAMETER
P24
–
(not applicable)
PARAMETER
P25
–
(not applicable)
PARAMETER
P26
–
OUTDOOR
RESET
FUNCTION
This parameter is used to set the D.H.W maximum temperature the user may increase to.
00 = Standard Operation 86°F
– 185°F
01 = Outdoor sensor NOT connected the allowed operating temperature range is 86 °F
– 140°F
Outdoor sensor IS connected the allowed operating temperature is 86°F
– 176°F
Professionally qualified personnel in accordance with current laws and
standards and in line with the manufacturer
’s instructions must install the
appliance.
Summary of Contents for PCH 50B-H
Page 8: ...GENERALINFORMATION 5 ...
Page 9: ...GENERALINFORMATION 6 ING ...
Page 10: ...GENERALINFORMATION 7 ...
Page 11: ...GENERALINFORMATION 8 ...
Page 14: ...TECHNICALCHARACTERISTCS 11 2 2 Dimensions ...
Page 35: ...INSTALLATION INSTRUCTION 32 Venting Pictures Illustrations ...
Page 36: ...INSTALLATION INSTRUCTION 33 Part No PAHVK Horizontal Vent Kit ...
Page 40: ...INSTALLATION INSTRUCTION 37 ...
Page 75: ...73 6 12 Sequence of operations ...
Page 76: ...74 ...
Page 77: ...75 ...
Page 78: ...76 ...
Page 79: ...77 ...