REGULATION INSTRUCTIONS
44
5. REGULATING THE APPLIANCE
5.1 Parameters table
PARAMETER
N°
TYPE OF OPERATION
PARAMETER
VALUE
FUNCTION
P00
Selects the model of boiler
00-06
01 = 18 KW
04 = 34 kW
05 = 50 kW
All other numbers N/A
P01
Selects the type of boiler
00-05
00 = N/A
01 = PCC 34
02 = PCI 18/8 & PCI 34/20
03 = PCH 18/B, PCH 50/B & PCH 50/B
(with
indirect)
04 = N/A
05 = Only heating boiler
(NO indirect connected.
See 3.6)
P02
Selects the type of gas supply
00
01
02
00 = Natural gas
01 = LPG
02 = N/A
P03
Sets the central heating
temperature
00
01
00 = Standard (95-185°F)
01 = Reduced (77-113°F)
P04
Heating output rising time
00-04
00 = 0 seconds (Disabled)
01 = 50 seconds (Default)
02 = 100 seconds
03 = 200 seconds
04 = 400 seconds
P05
Water hammer prevention
function
00
01
00 = Off (default)
01 = On
P06
D.H.W priority function.
(Delays
heat call for 90 seconds after
DHW call)
00
01
00 = Off
01 = On
P07
Central heating timer
00 - 90
Displayed in multiples of 5 seconds
(default value 36 x 5 = 180”)
P08
Central heating pump overrun
timer
00 - 90
Displayed in multiples of 5 seconds
(default value 36 x 5 = 180”)
P09
D.H.W/Storage cylinder pump
overrun timer
00 - 90
Displayed in multiples of 5 seconds
(default value 18 x 5 = 90”)
P10
Minimum fan speed
– DHW
38 Hz (Nat Gas)
50 Hz (Propane)
Displayed in hertz
(1Hz = 30 rpm)
P11
Maximum fan speed - DHW
185 Hz (Nat Gas)
183 Hz (Propane)
Displayed in hertz
(1Hz = 30 rpm)
P12
Minimum fan speed
–
Heating
38 Hz (Nat Gas)
50 Hz (Propane)
Displayed in hertz
(1Hz = 30 rpm)
P13
Maximum fan speed
–
Heating
145 Hz (Nat Gas)
14 Hz (Propane)
Displayed in hertz
(1Hz = 30 rpm)
P14
Sets the ignition sequence
90 Hz (Nat Gas)
110Hz (Propane)
Displayed in hertz
(1Hz = 30 rpm)
P15
Legionella prevention function
(for storage boilers only)
00
01
00 = Off
01 = On (default)
P16
Outdoor reset curve
(w/outdoor temperature
sensor only installation)
00-30
See the graph in the parameter setting
explanation
P17
Sets the temperature
measurement unit
00
01
00 = °C
01 = °F
Summary of Contents for PCH 50B-H
Page 8: ...GENERALINFORMATION 5 ...
Page 9: ...GENERALINFORMATION 6 ING ...
Page 10: ...GENERALINFORMATION 7 ...
Page 11: ...GENERALINFORMATION 8 ...
Page 14: ...TECHNICALCHARACTERISTCS 11 2 2 Dimensions ...
Page 35: ...INSTALLATION INSTRUCTION 32 Venting Pictures Illustrations ...
Page 36: ...INSTALLATION INSTRUCTION 33 Part No PAHVK Horizontal Vent Kit ...
Page 40: ...INSTALLATION INSTRUCTION 37 ...
Page 75: ...73 6 12 Sequence of operations ...
Page 76: ...74 ...
Page 77: ...75 ...
Page 78: ...76 ...
Page 79: ...77 ...