background image

Mounting

Mount System 450 modules on 35 mm DIN rail

(recommended) or directly to an even wall surface. See:

Mounting modules on DIN rail

Direct-mounting modules to wall surfaces

Mounting modules on DIN rail

1.

Provide a section of 35 mm DIN rail that is longer

than the module assembly width, and mount the

DIN rail horizontally in a suitable location using

appropriate mounting hardware/fasteners.

2.

Clip the control module on the rail, position the upper

DIN rail clips on the top rail, and gently snap the

lower clips onto the rail.

3.

Clip the remaining power and/or expansion modules

to the right of the control module on to the DIN

rail and plug the 6-pin module connectors together

(Figure 3).

Note: 

If your System 450 control system uses a

power module, the power module be plugged

into the right-hand side of the control module.

Direct-mounting modules to wall
surfaces

1.

Plug the modules together, remove the module

covers, place the assembly against wall surface

horizontally in a suitable location, and mark the

mount hole locations on the surface (Figure 1).

2.

Install appropriate screw fasteners, leaving screw

heads approximately one to two turns away from

flush to the surface.

3.

Place the assembly over screw heads on the

mounting slots, and carefully tighten the mounting

screws.

Note: 

If you mount the modules on an uneven

surface, do not damage the housings when

tightening mounting screws. Use shims/

washers to mount module assembly evenly on

the surface.
Refer to the control sensor installation

instructions for information on locating and

mounting control sensors.

Wiring

See Figure 2 and Table 1 for electrical termination

locations and wiring information. See 

System 450 Series

Reset Control Modules with Real-Time Clock and Relay

Output technical specifications

 for electrical ratings.

 WARNING

Risk of Electric Shock

Disconnect or isolate all power supplies before mak-

ing electrical connections. More than one disconnec-

tion or isolation may be required to completely de-en-

ergize equipment. Contact with components carrying

hazardous voltage can cause electric shock and may

result in severe personal injury or death.

 AVERTISSEMENT

Risque de décharge électrique

Débrancher ou isoler toute alimentation avant de

réaliser un raccordement électrique. Plusieurs iso-

lations et débranchements sont peut-être néces-

saires pour -couper entièrement l'alimentation de

l'équipement. Tout contact avec des composants por-

teurs de tensions dangereuses risque d'entraîner une

décharge électrique et de provoquer des blessures

graves, voire mortelles.

Important:

• Use copper conductors only. Make all wiring in

accordance with local, national, and regional

regulations.

• Do not exceed the System 450 module electrical

ratings. Exceeding module electrical ratings can

result in permanent damage to the modules and

void any warranty.

• Run all low-voltage wiring and cables separate

from all high-voltage wiring. Shielded cable is

strongly recommended for input (sensor) and

analog output cables that are exposed to high

electromagnetic or radio frequency noise.

• Electrostatic discharge (ESD) can damage System

450 modules. Use proper ESD precautions during

installation and servicing to avoid damaging

System 450 modules.

• Do not connect 24 VAC supply power to the

System 450 modules before finishing wiring and

checking all wiring connections. Short circuits or

improperly connected wires can result in damage

to the modules and void any warranty.

• A System 450 control module and module

assembly can be connected to an internal power

source (a System 450 power module) or an

external power source (24 V power connected

to the 24V and COM terminals on the control

module), but must not be connected to both

power sources simultaneously. Connecting a

control module to both internal and external

power sources can damage the modules and void

any warranty.

System 450 Series Reset Control Modules with Real-Time Clock and Relay Output Installation Guide

2

Summary of Contents for System 450 C450RBN-1

Page 1: ...ith reset control and or real time setback control for temperature and humidity only control applications System 450 expansion modules allow you to control up to 10 outputs which can be relay and anal...

Page 2: ...lies before mak ing electrical connections More than one disconnec tion or isolation may be required to completely de en ergize equipment Contact with components carrying hazardous voltage can cause e...

Page 3: ...and input sensor terminals low voltage less than 30V Labels 5V 24V Sn 1 Sn 2 Sn 3 Note Common terminals C are internally connected 2 6 pin module connector 3 Second output relay and terminal block La...

Page 4: ...ion Module 16 Analog Output 4 Table 1 System 450 terminal wiring information Label Terminal function Wire sizes 24V Accepts 24 VAC supply power when a C450YNN power module is not connected and provide...

Page 5: ...nd Down for 5 seconds to access the Setup Start screens 7 Menu button Press M to move through the sensor and output setup start screens When moving through the status or setup screens press M to retur...

Page 6: ...s of the assembly outputs which requires setting up the outputs again See Figure 4 for an explanation of the System 450 display screen and the 4 button touch pad features and functions See Table 3 for...

Page 7: ...s that the Analog Output is set up with SP EP and OSP OEP and Relay Output 2 has 17 hours of total runtime relay ON Figure 7 System Status screens Accessing the System 450 Setup screens 1 Apply power...

Page 8: ...screens are view only selections cannot be made in Setup Start screens 2 In the Sn 1 Sensor Type Selection screen press Up or Down to select a Sensor Type F C or Press Next to save your selection and...

Page 9: ...Setup Start screen Setting up the System 450 Reset Setpoint The System 450 Reset Control Modules feature temperature and humidity setpoint reset capability based on a Master temperature sensor Sn 1 an...

Page 10: ...screen The remaining figures in this procedure show the setup parameter values selected for the RSP high and low temperature shutdown unoccupied setback and load balancing that are used by the output...

Page 11: ...en The following figure shows an Shutdown High Temperature value of 65 F selected Figure 20 Shutdown High Temperature Selection screen 7 In the Shutdown Low Temperature Selection screen press Up or Do...

Page 12: ...e the following sections Setting up a Relay Output with Reset Setpoint Setting up an Analog Output with Reset Setpoint Setting up a Standard Relay Output A standard relay output provides On Off contro...

Page 13: ...mains off after reaching the OFFT value Minimum Relay OFF Time range is 0 to 300 seconds Press Next to save your selection and go to the next screen The following figure shows 10 seconds selected for...

Page 14: ...et up in Setting up the System 450 Reset Setpoint Figure 35 Relay Output Setup Start screen 2 In the Sensor Selection screen press Up or Down to select the Reset Setpoint Sensor rES for the output to...

Page 15: ...nge is 0 to 300 seconds Press Next to save your selection and go to the next screen The following figure shows 0 seconds selected for the minimum OFF Time for Output 2 Figure 40 Minimum Relay OFF Time...

Page 16: ...gth at End Point OEP The LCD displays different Control Ramp icons for the four control actions The following figure shows an example of the analog output setup values and the resulting output signal...

Page 17: ...e To set up a Standard Analog Output you must select Sn 1 Sn 2 or Sn 3 in this screen and the selected sensor must already be set up in the System 450 UI See Setting up System 450 Sensors for informat...

Page 18: ...re limits to set point excursion The following figure shows 0 selected for the Unoccupied Setback value for Output 3 Figure 51 Unoccupied Setback Selection screen 8 In the Integration Constant Selecti...

Page 19: ...sensor is not selected the remaining output setup screens do not appear If a sensor is already selected for the output the Sensor Selection screen does not appear here the next screen in the setup se...

Page 20: ...tput When properly set up P I control can drive the load closer to Setpoint than proportional only control Press Next to save your selection and go to the next screen Initially you should select the I...

Page 21: ...wing figure shows 12 hour clock format selected Figure 67 12 or 24 Hour Clock Selection screen 3 In the Time of Day Setup screen press Up or Down to set the current time Set the clock to real time Pre...

Page 22: ...e unoccupied times The load balancing feature is not effected in its function as a result of Occupied Unoccupied modes See Figure 3 1 In the Occupied Unoccupied Schedule Setup Start screen press Next...

Page 23: ...eriods for that day and the entire day is occupied and all outputs operate at their occupied setpoint value Occupied and Unoccupied time periods are available at 15 minute intervals only For example 1...

Page 24: ...nd menu flow example System screens Description 1 Main screens Note The Main menu screens auto scroll during normal operation After two minutes of inactivity in any screen the display returns to the m...

Page 25: ...eed 8 Standard analog output setup start screens Mixing valve output 9 Time and day clock setup start screens Note You can set Time and day and occupied or unoccupied schedule for any control system T...

Page 26: ...VAC AC Full load Amperes 4 9 A AC Locked Rotor Amperes 29 4 A _____________________________________ 10 Amperes AC noninductive at 24 240 VAC Pilot Duty 125 VA at 24 240 VAC Clock accuracy 4 minutes pe...

Page 27: ...or more of the following measures Reorient or relocate the receiving antenna Increase the separation between the equipment and receiver Connect the equipment into an outlet on a circuit different fro...

Page 28: ...2020 Johnson Controls All rights reserved All specifications and other information shown were current as of document revision and are subject to change without notice www penncontrols com...

Reviews: