background image

5.

In the 

Output Signal Strength at Setpoint

Selection

 screen, press 

Up

 or 

Down

 to select the

output’s %Output Signal Strength at Setpoint value.

Select the strength of the signal that the output

generates when the sensed condition is at the

Setpoint value. Signal strength range is 0 to 100 (%).

Press 

Next

 to save your selection and go to the next

screen.

The following figure shows Analog Output 3

is set up to generate 10% of the total signal

strength when the input is at the Setpoint value

(= 1 V or 5.6 mA).

Figure 49: Output Signal Strength at Setpoint Selection

screen

6.

In the 

Output Signal Strength at End Point

Selection

 screen, press 

Up

 or 

Down

 to select the

output’s %Output Signal Strength at End Point value.

Select the strength of the signal that the output

generates when the sensed condition is at the End

Point value. Signal strength range is 0 to 100 (%).

Press 

Next

 to save your selection and go to the next

screen.

The following figure shows Output 3 is set up to

generate 90% of the total signal strength when

the input is at the End Point value (= 9 V or 18.4

mA).

Figure 50: Output Signal Strength at End Point Selection

screen

7.

In the 

Unoccupied Setback Selection

 screen, press

Up

 or 

Down

 to select the Unoccupied Setback value.

The selected setback (SbK) value (temperature

or humidity) is added to the SP value (SP+SbK)

and EP value (EP+SbK) to calculate a setback

proportional band that the output references during

the unoccupied times set up in the Occupied/

Unoccupied Schedule Setup screens. Press 

Next

 to

save the selected value and go to the next screen.

Note: 

To use the Setback feature in your

control system, you must also set up the (real)

time and day of week, and a weekly occupied/

unoccupied schedule. See 

Setting up time

and day of week

 and 

Setting up an occupied/

unoccupied schedule

 for more information and

setup procedures.

Note: 

Setback set point temperature does

not exceed MXSP or go lower than MNSP. In

reset, MNSP and MXSP are limits to set point

excursion.
The following figure shows 0 selected for the

Unoccupied Setback value for Output 3.

Figure 51: Unoccupied Setback Selection screen

8.

In the 

Integration Constant Selection

 screen, press

Up

 or 

Down

 to select the Integration Constant for

the output. An integration constant allows you to set

up Proportional plus Integral (P+I) control for this

analog output. When properly set up, P+I control can

drive the load closer to Setpoint than proportional-

only control. Press 

Next

 to save your selection and

go to the next screen.

Initially, you should select the I-C value of 0

(zero) for no integration constant. Refer to the

System 450 Series Modular Controls Technical Bul-

letin (LIT-12011459)

 for more information on pro-

portional plus integral control and setting an

integration constant in the System 450 UI.

The following figure shows an Integration Con-

stant of 0 (zero) selected for Output 3.

Figure 52: Integration Constant Selection screen

9.

In the 

Sensor Failure Mode Selection

 screen, press

Up

 or 

Down

 to select the Sensor Failure Mode for

the output. You can select the output’s mode of

operation in the event of a sensor or sensor wiring

failure. The output operates in the selected mode

until the failure is fixed. Press 

Next

 to save your

selection and go to the next screen.

Sensor Failure Mode selections for Analog Out-

puts include:

-

ON

—output goes to the OEP value.

-

OFF

—output goes to the OSP value.

The following figure shows the OFF Sensor Fail-

ure Mode selected for Output 3.

Figure 53: Sensor Failure Mode Selection screen

10. If you do not need to change the output’s sensor,

press 

Next

 in the 

Edit Sensor

 screen to save the

current sensor selection, complete the output setup,

and return to the Output Setup Start screen.

To change the output’s sensor, press 

Up

 or

Down

 in the 

Edit Sensor

 screen to select the

sensor that the output references. After you

select a different sensor, press 

Next

 to go to

the required output selection screen and repeat

the output setup procedure for the new Sensor

Type values.

System 450 Series Reset Control Modules with Real-Time Clock and Relay Output Installation Guide

18

Summary of Contents for System 450 C450RBN-1

Page 1: ...ith reset control and or real time setback control for temperature and humidity only control applications System 450 expansion modules allow you to control up to 10 outputs which can be relay and anal...

Page 2: ...lies before mak ing electrical connections More than one disconnec tion or isolation may be required to completely de en ergize equipment Contact with components carrying hazardous voltage can cause e...

Page 3: ...and input sensor terminals low voltage less than 30V Labels 5V 24V Sn 1 Sn 2 Sn 3 Note Common terminals C are internally connected 2 6 pin module connector 3 Second output relay and terminal block La...

Page 4: ...ion Module 16 Analog Output 4 Table 1 System 450 terminal wiring information Label Terminal function Wire sizes 24V Accepts 24 VAC supply power when a C450YNN power module is not connected and provide...

Page 5: ...nd Down for 5 seconds to access the Setup Start screens 7 Menu button Press M to move through the sensor and output setup start screens When moving through the status or setup screens press M to retur...

Page 6: ...s of the assembly outputs which requires setting up the outputs again See Figure 4 for an explanation of the System 450 display screen and the 4 button touch pad features and functions See Table 3 for...

Page 7: ...s that the Analog Output is set up with SP EP and OSP OEP and Relay Output 2 has 17 hours of total runtime relay ON Figure 7 System Status screens Accessing the System 450 Setup screens 1 Apply power...

Page 8: ...screens are view only selections cannot be made in Setup Start screens 2 In the Sn 1 Sensor Type Selection screen press Up or Down to select a Sensor Type F C or Press Next to save your selection and...

Page 9: ...Setup Start screen Setting up the System 450 Reset Setpoint The System 450 Reset Control Modules feature temperature and humidity setpoint reset capability based on a Master temperature sensor Sn 1 an...

Page 10: ...screen The remaining figures in this procedure show the setup parameter values selected for the RSP high and low temperature shutdown unoccupied setback and load balancing that are used by the output...

Page 11: ...en The following figure shows an Shutdown High Temperature value of 65 F selected Figure 20 Shutdown High Temperature Selection screen 7 In the Shutdown Low Temperature Selection screen press Up or Do...

Page 12: ...e the following sections Setting up a Relay Output with Reset Setpoint Setting up an Analog Output with Reset Setpoint Setting up a Standard Relay Output A standard relay output provides On Off contro...

Page 13: ...mains off after reaching the OFFT value Minimum Relay OFF Time range is 0 to 300 seconds Press Next to save your selection and go to the next screen The following figure shows 10 seconds selected for...

Page 14: ...et up in Setting up the System 450 Reset Setpoint Figure 35 Relay Output Setup Start screen 2 In the Sensor Selection screen press Up or Down to select the Reset Setpoint Sensor rES for the output to...

Page 15: ...nge is 0 to 300 seconds Press Next to save your selection and go to the next screen The following figure shows 0 seconds selected for the minimum OFF Time for Output 2 Figure 40 Minimum Relay OFF Time...

Page 16: ...gth at End Point OEP The LCD displays different Control Ramp icons for the four control actions The following figure shows an example of the analog output setup values and the resulting output signal...

Page 17: ...e To set up a Standard Analog Output you must select Sn 1 Sn 2 or Sn 3 in this screen and the selected sensor must already be set up in the System 450 UI See Setting up System 450 Sensors for informat...

Page 18: ...re limits to set point excursion The following figure shows 0 selected for the Unoccupied Setback value for Output 3 Figure 51 Unoccupied Setback Selection screen 8 In the Integration Constant Selecti...

Page 19: ...sensor is not selected the remaining output setup screens do not appear If a sensor is already selected for the output the Sensor Selection screen does not appear here the next screen in the setup se...

Page 20: ...tput When properly set up P I control can drive the load closer to Setpoint than proportional only control Press Next to save your selection and go to the next screen Initially you should select the I...

Page 21: ...wing figure shows 12 hour clock format selected Figure 67 12 or 24 Hour Clock Selection screen 3 In the Time of Day Setup screen press Up or Down to set the current time Set the clock to real time Pre...

Page 22: ...e unoccupied times The load balancing feature is not effected in its function as a result of Occupied Unoccupied modes See Figure 3 1 In the Occupied Unoccupied Schedule Setup Start screen press Next...

Page 23: ...eriods for that day and the entire day is occupied and all outputs operate at their occupied setpoint value Occupied and Unoccupied time periods are available at 15 minute intervals only For example 1...

Page 24: ...nd menu flow example System screens Description 1 Main screens Note The Main menu screens auto scroll during normal operation After two minutes of inactivity in any screen the display returns to the m...

Page 25: ...eed 8 Standard analog output setup start screens Mixing valve output 9 Time and day clock setup start screens Note You can set Time and day and occupied or unoccupied schedule for any control system T...

Page 26: ...VAC AC Full load Amperes 4 9 A AC Locked Rotor Amperes 29 4 A _____________________________________ 10 Amperes AC noninductive at 24 240 VAC Pilot Duty 125 VA at 24 240 VAC Clock accuracy 4 minutes pe...

Page 27: ...or more of the following measures Reorient or relocate the receiving antenna Increase the separation between the equipment and receiver Connect the equipment into an outlet on a circuit different fro...

Page 28: ...2020 Johnson Controls All rights reserved All specifications and other information shown were current as of document revision and are subject to change without notice www penncontrols com...

Reviews: