System 450 Series Reset Control Modules with

Real-Time Clock and Relay Output Installation

Guide

Application

Important: 

Use this System 450™ Series Reset

Control Modules with Real-Time Clock and Relay

Output only as an operating control. Where failure

or malfunction of the System 450 Series Control

Module could lead to personal injury or property

damage to the controlled equipment or other

property, additional precautions must be designed

into the control system. Incorporate and maintain

other devices, such as supervisory or alarm systems

or safety or limit controls, intended to warn of or

protect against failure or malfunction of the System

450 Series Control Module.

Important: 

Utiliser ce System 450 Series Reset

Control Modules with Real-Time Clock and

Relay Output uniquement en tant que dispositif

de régulation. Lorsqu'une défaillance ou un

dysfonctionnement du System 450 Series Control

Module risque de provoquer des blessures ou

d'endommager l'équipement contrôlé ou un

autre équipement, la conception du système de

contrôle doit intégrer des dispositifs de protection

supplémentaires. Veiller dans ce cas à intégrer de

façon permanente d'autres dispositifs, tels que

des systèmes de supervision ou d'alarme, ou des

dispositifs de sécurité ou de limitation, ayant une

fonction d'avertissement ou de protection en cas de

défaillance ou de dysfonctionnement du System 450

Series Control Module.

System 450 is a family of modular, digital electronic

controls that is easily assembled and set up to provide

reliable temperature, pressure, and humidity control for a

wide variety of HVACR and commercial/industrial process

applications.
The System 450 reset control modules allow you to

configure custom application-specific control systems

with reset control and/or real-time setback control for

temperature and humidity (only) control applications.

System 450 expansion modules allow you to control up to

10 outputs, which can be relay and analog outputs.
C450RxN-1 and C450RxN-3 Reset Control models are

Single-Pole, Double-Throw (SPDT) relay control modules

with temperature reset capability, real-time setback

capability, a Liquid Crystal Display (LCD), and a four-button

touch pad User Interface (UI) that allow you to set up

custom System 450 control systems.
The C450RBN-1 and C450RBN-3 model provide one SPDT

relay.
The C450RCN-1 and C450RCN-3 model provide two SPDT

relays.
Refer to the 

System 450 Series Modular Control Systems with

Reset Control Modules Technical Bulletin (LIT-12011842) 

for

more detailed information on designing, installing, setting

up, and troubleshooting System 450 Series components

and control systems.

Figure 1: System 450 Module dimensions, mm

Installation

Observe the following System 450 location guidelines:
• Ensure that the mounting surface can support the

module assembly, mounting hardware, and any (user-

supplied) panel or enclosure.

• Mount the modules upright and plugged together in

a horizontal row where possible (Figure 3). DIN rail

mounting is highly recommended.

• Mount modules on flat, even surfaces.

• Allow sufficient space for wires and connections.

• Mount the modules in locations free of corrosive vapors

and observe the ambient operating conditions in the

System 450 Series Reset Control Modules with Real-

Time Clock and Relay Output technical specifications

.

• Do not mount the modules on surfaces that are prone

to vibration or in locations where radio frequency or

electromagnetic emissions may cause interference.

• Do not install the modules in airtight enclosures.

• Do not install heat-generating devices in an enclosure

with the modules that may cause the temperature to

exceed the ambient operating limit.

Part No. 24-7664-2888 Rev. E

2020-04-01

C450RBN, C450RCN

Summary of Contents for System 450 C450RBN-1

Page 1: ...ith reset control and or real time setback control for temperature and humidity only control applications System 450 expansion modules allow you to control up to 10 outputs which can be relay and anal...

Page 2: ...lies before mak ing electrical connections More than one disconnec tion or isolation may be required to completely de en ergize equipment Contact with components carrying hazardous voltage can cause e...

Page 3: ...and input sensor terminals low voltage less than 30V Labels 5V 24V Sn 1 Sn 2 Sn 3 Note Common terminals C are internally connected 2 6 pin module connector 3 Second output relay and terminal block La...

Page 4: ...ion Module 16 Analog Output 4 Table 1 System 450 terminal wiring information Label Terminal function Wire sizes 24V Accepts 24 VAC supply power when a C450YNN power module is not connected and provide...

Page 5: ...nd Down for 5 seconds to access the Setup Start screens 7 Menu button Press M to move through the sensor and output setup start screens When moving through the status or setup screens press M to retur...

Page 6: ...s of the assembly outputs which requires setting up the outputs again See Figure 4 for an explanation of the System 450 display screen and the 4 button touch pad features and functions See Table 3 for...

Page 7: ...s that the Analog Output is set up with SP EP and OSP OEP and Relay Output 2 has 17 hours of total runtime relay ON Figure 7 System Status screens Accessing the System 450 Setup screens 1 Apply power...

Page 8: ...screens are view only selections cannot be made in Setup Start screens 2 In the Sn 1 Sensor Type Selection screen press Up or Down to select a Sensor Type F C or Press Next to save your selection and...

Page 9: ...Setup Start screen Setting up the System 450 Reset Setpoint The System 450 Reset Control Modules feature temperature and humidity setpoint reset capability based on a Master temperature sensor Sn 1 an...

Page 10: ...screen The remaining figures in this procedure show the setup parameter values selected for the RSP high and low temperature shutdown unoccupied setback and load balancing that are used by the output...

Page 11: ...en The following figure shows an Shutdown High Temperature value of 65 F selected Figure 20 Shutdown High Temperature Selection screen 7 In the Shutdown Low Temperature Selection screen press Up or Do...

Page 12: ...e the following sections Setting up a Relay Output with Reset Setpoint Setting up an Analog Output with Reset Setpoint Setting up a Standard Relay Output A standard relay output provides On Off contro...

Page 13: ...mains off after reaching the OFFT value Minimum Relay OFF Time range is 0 to 300 seconds Press Next to save your selection and go to the next screen The following figure shows 10 seconds selected for...

Page 14: ...et up in Setting up the System 450 Reset Setpoint Figure 35 Relay Output Setup Start screen 2 In the Sensor Selection screen press Up or Down to select the Reset Setpoint Sensor rES for the output to...

Page 15: ...nge is 0 to 300 seconds Press Next to save your selection and go to the next screen The following figure shows 0 seconds selected for the minimum OFF Time for Output 2 Figure 40 Minimum Relay OFF Time...

Page 16: ...gth at End Point OEP The LCD displays different Control Ramp icons for the four control actions The following figure shows an example of the analog output setup values and the resulting output signal...

Page 17: ...e To set up a Standard Analog Output you must select Sn 1 Sn 2 or Sn 3 in this screen and the selected sensor must already be set up in the System 450 UI See Setting up System 450 Sensors for informat...

Page 18: ...re limits to set point excursion The following figure shows 0 selected for the Unoccupied Setback value for Output 3 Figure 51 Unoccupied Setback Selection screen 8 In the Integration Constant Selecti...

Page 19: ...sensor is not selected the remaining output setup screens do not appear If a sensor is already selected for the output the Sensor Selection screen does not appear here the next screen in the setup se...

Page 20: ...tput When properly set up P I control can drive the load closer to Setpoint than proportional only control Press Next to save your selection and go to the next screen Initially you should select the I...

Page 21: ...wing figure shows 12 hour clock format selected Figure 67 12 or 24 Hour Clock Selection screen 3 In the Time of Day Setup screen press Up or Down to set the current time Set the clock to real time Pre...

Page 22: ...e unoccupied times The load balancing feature is not effected in its function as a result of Occupied Unoccupied modes See Figure 3 1 In the Occupied Unoccupied Schedule Setup Start screen press Next...

Page 23: ...eriods for that day and the entire day is occupied and all outputs operate at their occupied setpoint value Occupied and Unoccupied time periods are available at 15 minute intervals only For example 1...

Page 24: ...nd menu flow example System screens Description 1 Main screens Note The Main menu screens auto scroll during normal operation After two minutes of inactivity in any screen the display returns to the m...

Page 25: ...eed 8 Standard analog output setup start screens Mixing valve output 9 Time and day clock setup start screens Note You can set Time and day and occupied or unoccupied schedule for any control system T...

Page 26: ...VAC AC Full load Amperes 4 9 A AC Locked Rotor Amperes 29 4 A _____________________________________ 10 Amperes AC noninductive at 24 240 VAC Pilot Duty 125 VA at 24 240 VAC Clock accuracy 4 minutes pe...

Page 27: ...or more of the following measures Reorient or relocate the receiving antenna Increase the separation between the equipment and receiver Connect the equipment into an outlet on a circuit different fro...

Page 28: ...2020 Johnson Controls All rights reserved All specifications and other information shown were current as of document revision and are subject to change without notice www penncontrols com...