P70, P72, and P170 Series Controls for Low Pressure Applications Installation Instructions
9
Technical Specifications
Table 6: SPST Electrical Ratings (P70A, B, C, D, and P170A, B, C, D Type Models)
Standard Single-Phase Ratings
Hermetic
Compressor
Single-Phase
Ratings
120
VAC
208
VAC
240
VAC
480
VAC
1
600 VAC
208/240 VAC
Motor Full-Load Amperes
24
18.7
17
5
4.8
24
Motor Locked-Rotor Amperes
144
112.2
102
30
28.8
144
Non-Inductive Amperes
22
22
22
--
--
--
Pilot Duty
125 VA at 120–600 VAC; 57.5 VA at 120–300 VDC
1.
Not for compressor motor loads.
Table 7: SPDT Electrical Ratings Standard Differential Switch (P70E Type Models)
Standard Single-Phase Ratings
120 VAC
208 VAC
240 VAC
277 VAC
1
Motor Full Load Amperes
16.0
9.2
8.0
7.0
Motor Locked Rotor
Amperes
96.0
55.2
48.0
42.0
Non-Inductive Amperes
16.0
16.0
16.0
16.0
Pilot Duty
125 VA at 120–600 VAC
125 VA at 24–600 VAC
1.
Rating for P70EC models only
Table 8: 4-Wire, 2-Circuit Electrical Ratings (P70G, H, J, K, and P170K Type Models)
Standard Single-Phase Ratings
Line-M2(Main Contacts)
Line-M1(Auxiliary Contacts)
120
VAC
208
VAC
240
VAC
277
VAC
480
VAC
1
600
VAC
120
VAC
208
VAC
240
VAC
277
VAC
Motor Full Load
Amperes
16.0
9.2
8.0
--
5
4.8
6.0
3.3
3.0
--
Motor Locked Rotor
Amperes
96.0
55.2
48.0
--
30
28.8
36.0
19.8
18.0
--
Non-Inductive
Amperes
16.0
9.2
8.0
7.2
--
--
6.0
6.0
6.0
6.0
Pilot Duty (for both
sets of contacts)
125 VA at 24–600 VAC; 57.5 VA at 120–300 VDC
1.
Not for compressor motor loads