background image

P70, P72, and P170 Series Controls for Low Pressure Applications Installation

Instructions

1

 Refer to the 

QuickLIT Web site

 for the most up-to-date version of this document.

Applications

P70, P72, and P170 Series Controls for Low Pressure 
Applications provide low-side pressure control on 
commercial refrigeration and air

-

conditioning 

applications.  

P70A and P170A type models with Single-Pole Single-
Throw (SPST) Open-Low switch action are the most 
popular models and are typically used for Open-Low 
operation and pump-down control. See Table 1 through 
Table 4.

P70 and P170 Series control models are also available 
with SPST Open-High switch action and are typically 
used for capacity control. See Table 3 and Table 4
Control models with Single-Pole Double-Throw (SPDT) 
or 4-wire, 2-circuit switch action allow users to install 
alarm devices or other control circuits. See Table 4.

P72 Series control models have a Double-Pole Single-
Throw (DPST) switch with load-carrying contacts that 
provide direct control of 208/240 VAC single-phase 
motors up to 3 hp, 480 VAC single-phase, 
non-compressor motors, and 208/220 VAC 3-phase 
motors up to 5 hp. See Table 4.

These controls are available in several pressure 
ranges and are compatible with most common 
refrigerants. They may also be used on air, water, 
and other non-corrosive fluid applications. 
Ammonia-compatible models are also available. See 
Table 3.

The MICRO-SET® option provides fine adjustment of 
the differential setting for precision pressure control of 
critical low pressure applications.

Some models feature Limited Knob Adjustment, which 
restricts adjustment of the pressure settings and deters 
overadjustment or tampering. See 

Limited Knob 

Adjustment

.

The Manual Reset Lockout mechanism does not allow 
the control to automatically reset after the control has 
Cutout, providing shutdown capability for unmonitored 
equipment. See 

Manual Reset Operation

.

NEMA 1 enclosures are standard on most models. 
NEMA 3R enclosures are available on select models.

Table 1 through Table 4 list the standard models and 
features of P70, P72, and P170 controls for low 
pressure applications. These standard models are 
available through most authorized 
Johnson Controls/PENN® distributors.         

IMPORTANT:

Use this P70, P72, or P170 Series 

Control for Low Pressure Applications only as an 
operating control. Where failure or malfunction of the 
P70, P72, or P170 Series Control could lead to 
personal injury or property damage to the controlled 
equipment or other property, additional precautions 
must be designed into the control system. 
Incorporate and maintain other devices, such as 
supervisory or alarm systems or safety or limit 
controls, intended to warn of or protect against 
failure or malfunction of the P70, P72, or P170 
Series Control.

Table 1:  Standard P70, P72 and P170 MICRO-SET® Control Models for Low Pressure Applications (for 

Non-corrosive Refrigerants)

Model 
Number

Switch Action

Range
in. Hg to psig 
(kPa)

Differential 
psi (kPa)

Pressure 
Connection

Maximum 
Overpressure 
psig (kPa)

P70AB-12

SPST
Open-Low

12 in. Hg to 80 psig 
(-41 to 551 kPa)

Minimum 5 (34)
Maximum 35 (241)

36 in. Cap. with 
1/4 in. Flare Nut

325
(2,241)

P170AB-12

1/4 in. Male Flare 
Connector

P70, P72, and P170 Series Controls for Low 
Pressure Applications

Installation Instructions

Part No. 24-7664-1601, Rev. G

Issued March 2016

Summary of Contents for P170 Series

Page 1: ...ure Limited Knob Adjustment which restricts adjustment of the pressure settings and deters overadjustment or tampering See Limited Knob Adjustment The Manual Reset Lockout mechanism does not allow the...

Page 2: ...Connection Maximum Overpressure psig kPa P70AA 5 SPST Open Low 20 in Hg to 100 psig 68 to 690 kPa Minimum 7 48 Maximum 50 345 1 4 in SS Female NPT 325 2 241 P70CA 4 SPST Open High Table 4 Standard P7...

Page 3: ...ure 1 Dimensions of P70 P72 and P170 Pressure Controls with NEMA 1 Enclosures in mm Figure 2 Dimensions of P70 P72 and P170 Pressure Controls with NEMA 3R Enclosures in mm CAUTION Risk of Property Dam...

Page 4: ...lowing applicable wiring diagrams when wiring the control See Figure 4 through Figure 7 and Table 5 for switch actions and models Also see Technical Specifications WARNING Risk of Electric Shock Disco...

Page 5: ...SPST Open High Cut In Closes Line to M1 Cutout Opens Line to M1 P70C P70D P170C P170D Single Pole Double Throw SPDT Opens 1 to 2 and Closes 1 to 3 Closes 1 to 2 and Opens 1 to 3 P70E 4 Wire 2 Circuit...

Page 6: ...k of Environmental and Property Damage Avoid sharp bends in the capillary tubes Sharp bends can weaken or kink capillary tubes which may result in refrigerant leaks or restrictions of flow CAUTION Ris...

Page 7: ...Kit 1 Adjust control pointers to desired high event and low event setpoints on All Range controls or differential setting on MICRO SET controls 2 Place spacer on the proper adjustment screw All Range...

Page 8: ...necessary Manual Reset Operation Pressure controls with the Manual Reset option lock out when they reach Cutout pressure and must be manually reset by the user to restart the controlled equipment The...

Page 9: ...Standard Single Phase Ratings 120 VAC 208 VAC 240 VAC 277 VAC1 Motor Full Load Amperes 16 0 9 2 8 0 7 0 Motor Locked Rotor Amperes 96 0 55 2 48 0 42 0 Non Inductive Amperes 16 0 16 0 16 0 16 0 Pilot...

Page 10: ...atible Models 1 4 in stainless steel female NPT connection Ambient Temperature P70E and P70F Type Models 50 to 104 F 10 to 40 C All Other Models 40 to 140 F 40 to 60 C Case and Cover NEMA 1 Enclosures...

Page 11: ...la presi n en aplicaciones cr ticas de baja presi n Algunos modelos est n disponibles con Ajuste de Perilla Limitado que restringe ajuste de la presi n y evita un ajuste excesivo o el manejo inexperto...

Page 12: ...baja 20 pulg Hg a 100 psig 68 a 690 kPa M nimo 7 48 M ximo 50 345 NPT Hembra de Acero Inoxidable de 1 4 pulg 325 2 241 P70CA 4 SPST Abierto en alta Tabla 4 Modelos Est ndar de Control P70 P72 y P170 p...

Page 13: ...taje NEMA 1 2 pul 3 1 4 83 13 16 20 2 13 16 71 1 11 16 43 1 3 4 44 FIG NEMA1_LP_span Figura 2 Dimensiones de los Controles de Presi n P70 P72 y P170 con Cajas NEMA 3R pulg mm 4 1 16 104 4 1 16 104 5 8...

Page 14: ...modelos Ver Clasificaciones El ctricas Figura 3 Instalaci n de los Controles de Presi n Baja P70 P72 y P170 con Cajas NEMA 1 Utilice los tornillos de montaje provistos Los tornillos mas largos pueden...

Page 15: ...Eventos Bajos Eventos Altos Tipos de Modelo y Tabla de Referencia de Clasificaci n El ctrica Interruptor y Acci n Evento Bajo Evento Alto Tipos de Modelos Tabla de Referencia de Clasificaci n El ctri...

Page 16: ...esultar a en fugas de refrigerante u obstrucciones de flujo PRECAUCI N Riesgo de da os al medio ambiente y a la propiedad Enrolle y asegure cuidadosamente el exceso de tubo capilar lejos del contacto...

Page 17: ...e rango Para bloquear el punto de ajuste del evento alto y permitir el ajuste limitado del punto de ajuste del evento bajo en controles Todo Rango o ajuste del diferencial en controles MICRO SET insta...

Page 18: ...eben restablecerse manualmente por el usuario para reiniciar el equipo controlado El mecanismo de restablecimiento manual de movimiento Libre y no puede restablecerse al bloquear o sujetar el bot n de...

Page 19: ...Monof sicos Est ndares 120 VCA 208 VCA 240 VCA 277 VCA Amperios del Motor con Carga Completa 16 0 9 2 8 0 7 0 Amperios del Motor con el Rotor Bloqueado 96 0 55 2 48 0 42 0 Amperios No Inductivos 16 0...

Page 20: ...do Rango 100 psig 690 kPa Modelos MICRO SET 80 psig 551 kPa M xima Sobrepresi n no recurrente Modelos de Todo Rango 325 psig 2239 kPa Modelos MICRO SET 525 psig 3617 kPa Condiciones Ambientales Tipos...

Reviews: