P70, P72, and P170 Series Controls for Low Pressure Applications Installation Instructions 

3

Installation

Dimensions

See Figure 1 and Figure 2 for dimensional information. 
These dimensions are nominal and are subject to 
accepted manufacturing tolerances and application 
variables.   

Mounting

   

Observe the following guidelines when installing this 
device:

Mount the control in an accessible position, where 
the control and pressure-connection lines are not 
subject to damage.

Mount the pressure control upright and level. 

Position the pressure-connection lines to allow 
drainage away from control bellows. 

Locate pressure-tap points on the topside of the 
refrigerant lines to reduce the possibility of oil, 
liquids, or sediment accumulating in the bellows, 
which could cause control malfunction.

Mount controls with NEMA 1 enclosures on 
horizontal or vertical flat surfaces.

Use two screws or bolts through the two outer 
holes on the back of the control case when 
mounting the control directly to a flat vertical 
surface. See

 

Figure 3.

Figure 1: Dimensions of P70, P72, and P170 

Pressure Controls with NEMA 1 Enclosures, 

in. (mm)

Figure 2: Dimensions of P70, P72, and P170 

Pressure Controls with NEMA 3R Enclosures, 

in. (mm)

!

CAUTION: Risk of Property Damage.

Mount the pressure control separately 
from the electrical cabinet and seal all 
electrical piping to prevent ammonia from 
migrating to electrical components. 
Where there may be exposure to 
ammonia, use only ammonia-compatible 
control modules and pressure 
connections. System shutdown due to 
improper adjustment may cause property 
damage.

!

CAUTION: Risk of Property Damage.

Mount the P70, P72, or P170 Pressure 
Control according to the instructions and 
guidelines included with the control. 
These instructions and guidelines are 
intended to reduce the risk of malfunction 
of the product and resulting property 
damage. Failure to follow these 
instructions and guidelines could cause 
the control to malfunction, resulting in 
property damage. 

IMPORTANT:

Use only the mounting screws 

supplied with the Universal Mounting Bracket to 
avoid damaging internal components. Be careful not 
to distort or bend the control case when mounting 
the control to an uneven surface. Using other 
screws or bending the control case will void the 
warranty.

Summary of Contents for P170 Series

Page 1: ...ure Limited Knob Adjustment which restricts adjustment of the pressure settings and deters overadjustment or tampering See Limited Knob Adjustment The Manual Reset Lockout mechanism does not allow the...

Page 2: ...Connection Maximum Overpressure psig kPa P70AA 5 SPST Open Low 20 in Hg to 100 psig 68 to 690 kPa Minimum 7 48 Maximum 50 345 1 4 in SS Female NPT 325 2 241 P70CA 4 SPST Open High Table 4 Standard P7...

Page 3: ...ure 1 Dimensions of P70 P72 and P170 Pressure Controls with NEMA 1 Enclosures in mm Figure 2 Dimensions of P70 P72 and P170 Pressure Controls with NEMA 3R Enclosures in mm CAUTION Risk of Property Dam...

Page 4: ...lowing applicable wiring diagrams when wiring the control See Figure 4 through Figure 7 and Table 5 for switch actions and models Also see Technical Specifications WARNING Risk of Electric Shock Disco...

Page 5: ...SPST Open High Cut In Closes Line to M1 Cutout Opens Line to M1 P70C P70D P170C P170D Single Pole Double Throw SPDT Opens 1 to 2 and Closes 1 to 3 Closes 1 to 2 and Opens 1 to 3 P70E 4 Wire 2 Circuit...

Page 6: ...k of Environmental and Property Damage Avoid sharp bends in the capillary tubes Sharp bends can weaken or kink capillary tubes which may result in refrigerant leaks or restrictions of flow CAUTION Ris...

Page 7: ...Kit 1 Adjust control pointers to desired high event and low event setpoints on All Range controls or differential setting on MICRO SET controls 2 Place spacer on the proper adjustment screw All Range...

Page 8: ...necessary Manual Reset Operation Pressure controls with the Manual Reset option lock out when they reach Cutout pressure and must be manually reset by the user to restart the controlled equipment The...

Page 9: ...Standard Single Phase Ratings 120 VAC 208 VAC 240 VAC 277 VAC1 Motor Full Load Amperes 16 0 9 2 8 0 7 0 Motor Locked Rotor Amperes 96 0 55 2 48 0 42 0 Non Inductive Amperes 16 0 16 0 16 0 16 0 Pilot...

Page 10: ...atible Models 1 4 in stainless steel female NPT connection Ambient Temperature P70E and P70F Type Models 50 to 104 F 10 to 40 C All Other Models 40 to 140 F 40 to 60 C Case and Cover NEMA 1 Enclosures...

Page 11: ...la presi n en aplicaciones cr ticas de baja presi n Algunos modelos est n disponibles con Ajuste de Perilla Limitado que restringe ajuste de la presi n y evita un ajuste excesivo o el manejo inexperto...

Page 12: ...baja 20 pulg Hg a 100 psig 68 a 690 kPa M nimo 7 48 M ximo 50 345 NPT Hembra de Acero Inoxidable de 1 4 pulg 325 2 241 P70CA 4 SPST Abierto en alta Tabla 4 Modelos Est ndar de Control P70 P72 y P170 p...

Page 13: ...taje NEMA 1 2 pul 3 1 4 83 13 16 20 2 13 16 71 1 11 16 43 1 3 4 44 FIG NEMA1_LP_span Figura 2 Dimensiones de los Controles de Presi n P70 P72 y P170 con Cajas NEMA 3R pulg mm 4 1 16 104 4 1 16 104 5 8...

Page 14: ...modelos Ver Clasificaciones El ctricas Figura 3 Instalaci n de los Controles de Presi n Baja P70 P72 y P170 con Cajas NEMA 1 Utilice los tornillos de montaje provistos Los tornillos mas largos pueden...

Page 15: ...Eventos Bajos Eventos Altos Tipos de Modelo y Tabla de Referencia de Clasificaci n El ctrica Interruptor y Acci n Evento Bajo Evento Alto Tipos de Modelos Tabla de Referencia de Clasificaci n El ctri...

Page 16: ...esultar a en fugas de refrigerante u obstrucciones de flujo PRECAUCI N Riesgo de da os al medio ambiente y a la propiedad Enrolle y asegure cuidadosamente el exceso de tubo capilar lejos del contacto...

Page 17: ...e rango Para bloquear el punto de ajuste del evento alto y permitir el ajuste limitado del punto de ajuste del evento bajo en controles Todo Rango o ajuste del diferencial en controles MICRO SET insta...

Page 18: ...eben restablecerse manualmente por el usuario para reiniciar el equipo controlado El mecanismo de restablecimiento manual de movimiento Libre y no puede restablecerse al bloquear o sujetar el bot n de...

Page 19: ...Monof sicos Est ndares 120 VCA 208 VCA 240 VCA 277 VCA Amperios del Motor con Carga Completa 16 0 9 2 8 0 7 0 Amperios del Motor con el Rotor Bloqueado 96 0 55 2 48 0 42 0 Amperios No Inductivos 16 0...

Page 20: ...do Rango 100 psig 690 kPa Modelos MICRO SET 80 psig 551 kPa M xima Sobrepresi n no recurrente Modelos de Todo Rango 325 psig 2239 kPa Modelos MICRO SET 525 psig 3617 kPa Condiciones Ambientales Tipos...

Reviews: