DIAGNOSTICS
If any faults occur, the
200VTOUCHPAN
controller informs the operator, by means of alarm
codes visualised on the display (via pop-
up or on the ‘Alarms’ page) and an acoustic signal emitted
by a buzzer inside the operating Console (if enabled). One of the following messages appears on
the screen when an alarm condition occurs:
ALARM
CODE
POSSIBLE CAUSE
SOLUTION
E0
EEPROM Vision Touch alarm
Switch the appliance off and back on.
Select 'Repair EEPROM’ in the
'Software' menu.
If the problem persists, contact the
technical assistance service.
E0m
EEPROM 100N MASTER alarm
Switch the appliance off and back on.
If the problem persists, contact the
technical assistance service.
E1
Probe connected to channel 1 functional fault
Check the probe status.
Verify that its configuration is correct in
the "Configure I/O>Analogue Inputs"
menu.
E2
Probe connected to channel 2 functional fault
Check the probe status.
Verify that its configuration is correct in
the "Configure I/O>Analogue Inputs"
menu.
E3
Probe connected to channel 3 functional fault
Check the probe status.
Verify that its configuration is correct in
the "Configure I/O>Analogue Inputs"
menu.
E4
Probe connected to channel 4 functional fault
Check the probe status.
Verify that its configuration is correct in
the "Configure I/O>Analogue Inputs"
menu.
E5
Probe connected to channel 5 functional fault
Check the probe status.
Verify that its configuration is correct in
the "Configure I/O>Analogue Inputs"
menu.
Eg
General alarm
(e.g. Thermal protection or max
pressure switch)
(The outputs are all disabled apart from the alarm
output, if present)
Check compressor absorption.
If the problem persists, contact the
technical assistance service.
Ec
Compressor protection alarm
(The compressor output is disabled)
Check compressor absorption.
If the problem persists, contact the
technical assistance service.
EU
Humidifier alarm
(The humidifier output is disabled)
Check the humidifier status.
If the problem persists, contact the
technical assistance service.
EF
Fans protection
(The fans output is disabled)
Check the fans status.
If the problem persists, contact the
technical assistance service.
CHAPTER 10: DIAGNOSTICS