![Pego 100N MASTER3 User And Maintenance Manual Download Page 55](http://html1.mh-extra.com/html/pego/100n-master3/100n-master3_user-and-maintenance-manual_1521988055.webp)
VISION
TOUCH
PAN
Pag. 55
USER AND MAINTENANCE MANUAL
Rev. 01-19
Fst
FAN blocking TEMPERATURE
The fans do not switch on if the value of the temperature read
by the evaporator probe is higher than the value of this
parameter. The block is deactivated when the evaporator probe
is disabled or presents an error, in hot manual mode, when
recipe in progress in phases other than accumulation and
preservation.
-45,0 ÷ 99,0 °C
+99,0 °C
Fd
Differential for Fst
1,0 ÷ 10,0°C
2,0 °C
Fdo
Fan off delay after deactivating the hot output.
It has priority
over standby, switch-port and defrost.
0 ÷ 600 sec
0 sec