USER AND MAINTENANCE MANUAL
Rev. 01-19
DIGITAL OUTPUT CONNECTION ON 100N MASTER3
PIN
TERMINALS
DIGITAL
OUTPUT
DEFAULT SETTINGS
DIGITAL OUTPUTS
RELAY OUTPUT FEATURES
(Voltage-free contacts)
3-4
DO1
2 = Cold
(contact N.O)
Relay 30A 240V~ (AC1)
10A 240V~ (AC3) (2HP)
5-6
DO2
1 = Hot
(contact N.O)
Relay 16A 240V~ (AC1)
3A 240V~ (AC3)
7-8
DO3
3 = Fans high speed
(contact N.O)
Relay 16A 240V~ (AC1)
3A 240V~ (AC3)
9-10
DO4
4 = Fans low speed
(contact N.O)
Relay 16A 240V~ (AC1)
3A 240V~ (AC3)
11-12
DO5
5 = Humidify
(contact N.O)
Relay 16A 240V~ (AC1)
3A 240V~ (AC3)
13-14
DO6
6 = Dehumidify
(contact N.O)
Relay 16A 240V~ (AC1)
3A 240V~ (AC3)
15-16
DO7
7 = Light
(contact N.O)
Relay 16A 240V~ (AC1)
3A 240V~ (AC3)
25-26
DO8
8 = Air renewal
(contact N.O)
Relay 16A 240V~ (AC1)
3A 240V~ (AC3)
23-24
DO9
11 = Oven advance ignition
(contact N.O)
Relay 16A 240V~ (AC1)
3A 240V~ (AC3)
21-22
DO10
9 = Defrosting
(contact N.O)
Relay 16A 240V~ (AC1)
3A 240V~ (AC3)
19-20
DO11
10 = End recipe
(contact N.O)
Relay 16A 240V~ (AC1)
3A 240V~ (AC3)
17-18
DO12
12 = Alarm
(contact N.O)
Relay 16A 240V~ (AC1)
3A 240V~ (AC3)
POSSIBLE CONFIGURATIONS
DIGITAL OUTPUTS DO1
÷
DO12
Access menu:
Parameters > Configure I/O > Digital outputs
0 = Disabled
1 = Hot
2 = Cold
3 = Fan high speed
4 = Fan low speed
5 = Humidification
6 = Dehumidification
7 = Light
8 = Air Renewal
9 = Defrosting
10 = End recipe
11 = Oven advance ignition
12 = Alarm (only DO12)
Positive values = Contact N.O.
Negative values = Contact N.C.