74
Table 6 describes the ERROR_NUMBER values for
Lockout Errors. These are errors that require a
manual reset to continue boiler operation. Table 7
describes the ERROR_NUMBER values for Blocking
Errors. Blocking errors are conditions that allow the
boiler to continue operation as soon as the condition
is corrected.
Table 7 shows values for the WARNING_NUMBER
holding register. These conditions primarily concern
the operation of sensors.
If multiple errors are present, the lowest number error
will be communicated.
Table 5
Determination of General Control Status
Control Status
STATE
Value
ERROR_NUMBER
Value
Control is not
Communicating Properly
0x00
0x00
Control is Operating
Correctly with No Errors
Not 0x00
0xFF
Control is Operating
Correctly with Errors
Not 0x00
Not 0xFF
Table 6A
ERROR_NUMBER (Lockout Errors)
Error Number
Error Designation
Description
Decimal
Hexadecimal
0
0x00
E2PROM_READ_ERROR
Internal Software Error
1
0x01
IGNIT_ERROR
3 Consecutive Failed Ignition Attempts
5
0x05
GV_RELAY_ERROR
Gas Valve Relay Problems
6
0x06
SAFETY_RELAY_ERROR
Internal Control Error
8
0x08
FAN_ERROR
Incorrect Fan Speed
9
0x09
RAM_ERROR
Internal Control Error
10
0x0A
WRONG_EEPROM_SIGNATURE
Internal Control Error
11
0x0B
RETURN_HIGHER_THEN_SUPPLY
Boiler Return Temp. Higher Than Supply
12
0x0C
E2PROM_ERROR
Internal Control Error
13
0x0D
STATE_ERROR
Internal Control Error
14
0x0E
ROM_ERROR
Internal Control Error
15
0x0F
AIR_SWITCH_NOT_OPEN
Internal Control Error
16
0x10
15MS_XRL_ERROR
Internal Control Error
17
0x11
AIR_SWITCH_NOT_CLOSED
Internal Control Error
18
0x12
T_MAX_LOCK_ERROR
High Temperature Limit Open
19
0x13
STACK_ERROR
Internal Control Error
20
0x14
FLAME_OUT_TOO_LATE_ERROR
False Flame Detected After Shutdown
21
0x15
FLAME_ERROR_1
False Flame Detected Before Ignition
22
0X16
20MS_XRL_ERROR
Internal Control Error
23
0X17
41MS_ERROR
Internal Control Error
24
0X18
TOO_MANY_FLAME_FAILURES
3 Consecutive Flame Failures
25
0X19
FLOW_SWITCH_NOT_CLOSED
Flow Switch Open / Circulator Off
26
0X1A
FLOW_SWITCH_NOT_OPEN
Flow Switch Closed / Circulator On
27
0X1B
FLAG_BYTE_INTEGRITY_ERROR
Internal Control Error
28
0X1C
AD_HI_CPL_ERROR
Internal Control Error
29
0X1D
AD_LO_CPL_ERROR
Internal Control Error
30
0X1E
REGISTER_ERROR
Internal Control Error
APPENDIX D. 852-1 INTERFACE ADAPTER
Summary of Contents for PUREFIRE PFW-199
Page 20: ...18 WATER PIPING AND CONTROLS Figure 4 3 Schematic Piping One Boiler with a Single Storage Tank...
Page 60: ...58 Figure 13 2 Heat Exchanger Burner Assembly Repair Parts REPAIR PARTS...
Page 63: ...61 APPENDIX A STATUS SCREENS APPENDIX A STATUS SCREENS...
Page 64: ...62 APPENDIX A STATUS SCREENS...
Page 65: ...63 APPENDIX A STATUS SCREENS...
Page 66: ...64 APPENDIX B USER MENU APPENDIX B USER MENU...
Page 67: ...65 APPENDIX B USER MENU...
Page 68: ...66 APPENDIX C INSTALLER MENU APPENDIX C INSTALLER MENU...
Page 69: ...67 APPENDIX C INSTALLER MENU...
Page 70: ...68 APPENDIX C INSTALLER MENU...
Page 71: ...69 APPENDIX C INSTALLER MENU...